The text of a manual · part 33 of 41
SIMATIC ET 200B Distributed I/O Station Manual: 8 Analog Modules, pages 271 to 272
Pages 271 to 272 of 344, from SIMATIC ET 200B Distributed I/O Station Manual
The original document is the PDF (2.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens ET 200B
Page 271
Analog Modules
Technical Data
The technical data of the ET 200B-4AO electronics block are listed in the table below. Outputs, continued
Technical specifications Baud rates*
9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud
Bus protocol
PROFIBUS-DP
Galvanic isolation to SINEC L2-DP bus
Yes
Power losses
Typically 2.4 W
Weight (EB and TB)
Approx. 550 g (19.25 oz.)
Dimensions (EB and TB: W x H x D)
160 x 130 x 60 mm (6.24 x 5.07 x 2.34 in.)
Diagnostics functions, alarms Voltage monitoring
Green “RUN” LED
Bus monitoring SINEC L2-DP
Red “BF” LED
Group diagnostics
Red “DIA” LED, parameterizable
Diagnostics alarm Yes, parameterizable Supply voltage for outputs and internal logic Supply voltage (L+) Rated value Permissible range Value for t < 0.5s
24 V DC 18.5 to 30.2 V 35 V
Current consumption from L+ Logic Max. 200 mA Outputs Number of outputs
4
Galvanic isolation to inter- No nal electronic circuits
Connection type Load resistance Voltage output Load impedance for current output Capacitive load Inductive load
11-bit complement of twos
Overrange
Approx. 17.5 %
Conversion time
Approx. 1 ms
Settling time For resistive load For capacitive load For inductive load Permissible potential difference MA to PE or M
0.1 ms 3.3 ms 0.5 ms
Max. 75 V DC/60 V AC
Crosstalk between outputs 40 dB Working error limit (over entire temperature range in relation to output range) Voltage 0.5 % Current
Basic error limit (working error limit at 25°C (77 °F) in relation to output range) Voltage 0.2 % Current 0.3 % Temperature error (in rela- 0.02 %/K tion to output range) Linearity error (in relation to output range)
8
0.05 %
Repeatability (in 0.05 % state condition at 25°C (77 °F), in relation to output range) Output ripple (in relation to output range)
0.05 %
Voltage output Short-circuit protection Short-circuit current
Yes, max. 1 output simultaneously Max. 25 mA
10 V, 0 to 10 V 20 mA, 0 to 20 mA, 4 to 20 mA
Current output Idle voltage
Max. 18 V
2- or 4-wire connection
Cable length Shielded
Max. 100 m (328 ft.)
Galvanic isolation to volt- Yes age supply of internal logic Output ranges Voltage range Current ranges
Data input format
Min. 3.3 kW Max. 300 W
*
In operation with the IM 308-B, the maximum possible baud rate is 1500 kbaud.
Max. 1 mF Max. 1 mH
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-91
Page 272
Analog Modules
8
8-92