For the Siemens ET 200B

Page 271

Analog Modules

Technical Data

The technical data of the ET 200B-4AO electronics block are listed in the table below. Outputs, continued

Technical specifications Baud rates*

9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud

Bus protocol

PROFIBUS-DP

Galvanic isolation to SINEC L2-DP bus

Yes

Power losses

Typically 2.4 W

Weight (EB and TB)

Approx. 550 g (19.25 oz.)

Dimensions (EB and TB: W x H x D)

160 x 130 x 60 mm (6.24 x 5.07 x 2.34 in.)

Diagnostics functions, alarms Voltage monitoring

Green “RUN” LED

Bus monitoring SINEC L2-DP

Red “BF” LED

Group diagnostics

Red “DIA” LED, parameterizable

Diagnostics alarm Yes, parameterizable Supply voltage for outputs and internal logic Supply voltage (L+) Rated value Permissible range Value for t < 0.5s

24 V DC 18.5 to 30.2 V 35 V

Current consumption from L+ Logic Max. 200 mA Outputs Number of outputs

4

Galvanic isolation to inter- No nal electronic circuits

Connection type Load resistance Voltage output Load impedance for current output Capacitive load Inductive load

11-bit complement of twos

Overrange

Approx. 17.5 %

Conversion time

Approx. 1 ms

Settling time For resistive load For capacitive load For inductive load Permissible potential difference MA to PE or M

0.1 ms 3.3 ms 0.5 ms

Max. 75 V DC/60 V AC

Crosstalk between outputs 40 dB Working error limit (over entire temperature range in relation to output range) Voltage 0.5 % Current

Basic error limit (working error limit at 25°C (77 °F) in relation to output range) Voltage 0.2 % Current 0.3 % Temperature error (in rela- 0.02 %/K tion to output range) Linearity error (in relation to output range)

8

0.05 %

Repeatability (in 0.05 % state condition at 25°C (77 °F), in relation to output range) Output ripple (in relation to output range)

0.05 %

Voltage output Short-circuit protection Short-circuit current

Yes, max. 1 output simultaneously Max. 25 mA

10 V, 0 to 10 V 20 mA, 0 to 20 mA, 4 to 20 mA

Current output Idle voltage

Max. 18 V

2- or 4-wire connection

Cable length Shielded

Max. 100 m (328 ft.)

Galvanic isolation to volt- Yes age supply of internal logic Output ranges Voltage range Current ranges

Data input format

Min. 3.3 kW Max. 300 W

*

In operation with the IM 308-B, the maximum possible baud rate is 1500 kbaud.

Max. 1 mF Max. 1 mH

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-91

Page 272

Analog Modules

8

8-92

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c