Page 261
Analog Modules
Two-Wire Connection of Loads (Current Output)
Two-wire connection of loads for current output is shown below:
Ä Ä Ä
A x.3 . x.1 .
C
A
A
TB8
K+
0.3 0.4
1.3 1.4
MA L+ L+
K–
0.1 0.2
1.1 1.2
MA M M x.2 . x.4 .
. Shield + 24V
RL
RL
Max. 75 V DC/60 V AC PE
Max. 75 V DC/ 60 V AC MA
Mexternal
Figure 8-27 2-Wire Connection of Loads for Current Output
8
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-81
Page 262
Analog Modules
8.6.2
Configuration Options
Type File
The information in this section applies to the type file SI8018BE.200. The type file contains the possible configurations. The configuration you choose depends on the wiring of the module.
Configuration
Table 8-56 shows the possible configurations of the ET 200B-4AO with COM ET 200 Windows or STEP 7. Table 8-56 lists only the slots for configuring the output areas (slots 4 to 7). Slots 1 to 3 have the default value ”004”.
8
Table 8-56
Possible Configurations for the Output Areas of ET 200B-4AO
Configuration
Terminals used Channel 0
Channel 1
Channel 2
Channel 3
0.1/ 0.2
1.1/ 1.2
2.1/ 2.2
3.0/ 3.1
0.3/ 0.4
1.3/ 1.4
2.3/ 2.4
Length1 (in words)
Meaning
3.3/ 3.4
4AO o o o o
4
A start address is assigned for the entire module, addresses for 4 are reserved. (= module addressing)
4 x 1AO o o o o
4
3 x 1AO o o o
2 x 1AO o o
1 x 1AO o
A separate start address can be assigned for each channel. (= single-channel addressing)
1 o
3 2 1
Length of user data = Connection of load = Connection of sensor lines for voltage measurement
Diagnostics
8-82
Diagnostics messages and diagnostics data (slave diagnostics) are returned only for the configured channels.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 263
Analog Modules
8.6.3
Setting the Operating Mode
Setting the Operating Mode
You set the operating mode of the ET 200B-4AO electronics block by means of the coding plugs on the TB8 terminal block and by means of the COM ET 200 or STEP 7 parameterization software. Coding Plugs
The coding plugs of the TB8 enable you to set the output circuit for analog value output of each individual channel of the ET 200B-4AO. The possible settings of the coding plugs are: ”A”, ”B”, ”C” and ”D”. For details of the relationships between the settings of the coding plugs and the output mode or load, see Section 8.6.1. Section 3.1 describes how to change the settings of the coding plugs.
Channel
Some parameters of the ET 200B-4AO listed on the following pages apply only to individual channels. Table 8-57 lists the assignment of TB8 terminals to channels. Table 8-57
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Assignment of Terminals to Channels Channel
Terminals
Channel 0
Terminals 0.1/0.2
Channel 1
Terminals 1.1/1.2
Channel 3
Terminals 2.1/2.2
Channel 4
Terminals 3.1/3.2
8
8-83
Page 264
Analog Modules
Parameters
Table 8-58 shows all the parameters for parameterizing the ET 200B-4AO with COM ET 200 Windows or STEP 7. You can set these parameters for the ET 200B-4AO if you use the type file SI8018BE.200.
Table 8-58
Parameters for ET 200B-4AO (6ES7 135-0HF01-0XB0) Parameter
Diagnostics alarm
Explanation
Explanation
Diagnostics alarm enable for module
Disable Enable
Diagnostics enable for channel 0 Diagnostics enable for channel 1
Diagnostics messages enabled separately for each channel
Disable Enable
Diagnostics enable for channel 2 Diagnostics enable for channel 3 Output value and range for channel 0
Type and range of output defined separately for each channel
Output value and range for channel 1
For voltage output:
" 10 V 0 ... 10 V
For current output:
" 20 mA 0 ... 20 mA 4 ... 20 mA
Representation of output values
Sets representation of the analog values for module
SIMATIC S5 SIMATIC S7
Type of dummy value for channel 0
Defines the dummy value output for each channel in the event of communication interruption
Parameterizable
Sets dummy value for each channel
0
Output value and range for channel 2 Output value and range for channel 3
8
Type of dummy value for channel 1
Last value
Type of dummy value for channel 2 Type of dummy value for channel 3 Dummy value for channel 0 Dummy value for channel 1
*32786 ... 32767
Dummy value for channel 2 Dummy value for channel 3 :
8-84
Default
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 265
Analog Modules
8.6.4
Analog Value Representation, Operation with SIMATIC S5
Analog Value Representation, SIMATIC S7
If you operate the ET 200B-4AO with SIMATIC S5, you can utilize the analog value representation of SIMATIC S7. See Section 8.6.5 for the measuredvalue tables for analog value representation in SIMATIC S7.
Analog Value Representation, SIMATIC S5
Analog values are represented in complements of twos with the ET 200B-4AO.
Table 8-59
The table below shows the analog value representation of the ET 200B-4AO:
Representation of an Analog Output Value as a Bit Pattern (6ES7 135-0HF01-0XB0) High Byte
Low Byte
Bit number
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Analog value representation
SI
210
29
28
27
26
25
24
23
22
21
20
X
X
X
X
Bits 0 ... 3 and 15 have no significance for the amount of the measured value. See Table 8-60 for a detailed description of these bits.
Supplementary Bits
Bits 0 ... 3 and 15 have the following meaning in the bit pattern of the analog output value: Table 8-60 Bit
Meaning
Signal Status
SI
Sign
0
“+” sign
1
“–” sign
X
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8
Description of the Bits (6ES7 135-0HF01-0XB0)
Irrelevant
–
Meaning of the Signal Status
–
8-85
Page 266
Analog Modules
Voltage and Current Output Ranges Table 8-61
Analog Output Signals of the ET 200B-4AO (Value Ranges: 10 V, 0 ... 10 V, 20 mA, 0 ... 20 mA, 4 ... 20 mA; Complement of Twos)
Units
Output Value in mV 0 ... 20 mA
1249 1204
8
The table below shows the assignments of analog to digitized output signals for the value ranges: 10 V, 0 ... 10 V, 20 mA, 0 ... 20 mA, 4 ... 20 mA.
4 ... 20 mA mA
0 ... 10 V
Digitized Output Value
15 14 13 12 11 10 9 8
23.52 23.52
:
7 6 5 4
0 1 0 0 1 1 1 0 0 0 0 1 23.52
11.758
Range
11.758
0 1 0 0 1 0 1 1 0 1 0 0
Overrange
:
:
:
:
:
:
1025
20.0195
20.016
20.2
10.0098
10.0098
0 1 0 0 0 0 0 0 0 0 0 1
1024
20.0
20.0
20.0
10.00
10.00
0 1 0 0 0 0 0 0 0 0 0 0
1023
19.98
19.98
19.98
9.99
9.990
0 0 1 1 1 1 1 1 1 1 1 1
512
10.0
12.0
10.0
5.00
5.000
0 0 1 0 0 0 0 0 0 0 0 0
256
5.0
8.00
5.0
2.50
2.500
0 0 0 1 0 0 0 0 0 0 0 0
1
0.0195
4.015
0.02
0.0098
0.0098
0
0.0
4.0
0.0
0.0
0.000
0 0 0 0 0 0 0 0 0 0 0 0 Nominal range 0 0 0 0 0 0 0 0 0 0 0 0
–1
0.0
3.984
–0.02
0.0
–0.0098
1 1 1 1 1 1 1 1 1 1 1 1
–256
0.0
0.0
–05.0
0.0
–2.500
1 1 1 1 0 0 0 0 0 0 0 0
–512
0.0
0.0
–10.0
0.0
–5.000
1 1 1 0 0 0 0 0 0 0 0 0
–1024
0.0
0.0
–20.00
0.0
–10.000
1 1 0 0 0 0 0 0 0 0 0 0
–1025
0.0
0.0
–20.02
0.0
–10.009
1 0 1 1 1 1 1 1 1 1 1 1
:
:
:
:
:
:
–1204
0.0
0.0
–23.52
0.0
–11.758
8-86
:
:
Overrange
1 0 1 1 0 1 0 0 1 1 0 0
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 267
Analog Modules
8.6.5
Analog Value Representation, Operation with SIMATIC S7
Analog Value Representation, SIMATIC S7
Table 8-62
Analog values are represented in complements of twos with the ET 200B-4AO for SIMATIC S7. The table below shows the analog value representation ET 200B-4AO:
Representation of an Analog Output Value as a Bit Pattern for SIMATIC S7 and ET 200B-4AO High Byte 13
12
11
Low Byte
Bit number
15
14
10
9
8
7
6
5
4
3
2
1
0
Analog value representation
SI
214 213 212 211 210
29
28
27
26
25
24
23
22
21
20
Bit 15 has no significance for the amount of the output value. It merely represents the sign.
Voltage Output Ranges Table 8-63
The table below shows the assignments of analog to digitized output signals for the value ranges: " 10 V, 0 ... 10 V.
Representation of Digitized Measured Values of the ET 200B-4AO (Output Ranges: 0 to 10 V and " 10 V)
Output Range 0 to 10 V
Output Range " 10 V
Units Decimal
Hexadecimal
0
0 w32512 w7F00H
11.7589
11.7589
32511
7EFFH
:
:
:
:
10.0004
10.0004
27649
6C01H
10.0000
10.0000
27648
6C00H
:
:
:
:
0
0
0
0H
:
:
– 6912
E500H
– 6913
E4FFH
:
:
– 10.0000
– 27648
9400H
10.0004
– 27649
93FFH
:
:
:
– 11.7593
– 32512
8100H
0 v– 32513 v80FFH
0 :
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Range
8
Overflow
Overrange
Nominal range
Underrange
Underrun
8-87
Page 268
Analog Modules
Current Output Ranges Table 8-64
Output Range " 20 mA
Representation of Digitized Measured Values of the ET 200B-4AO (Output Ranges: " 20 mA, 0 to 20 mA and 4 to 20 mA) Output Range 0 to 20 mA
Output Range 4 to 20 mA
Range
Units Decimal
Hexadecimal
0
0
0 w32512 w7F00H
23.518
23.518
22.81
32511
7EFFH
:
:
:
:
:
20.0007
20.0007
20.006
27649
6C01H
20.000
20.000
20.000
27648
6C00H
:
:
:
:
0
4.000
0
0H
0
:
:
:
0
– 6912
E500H
0
– 6913
E4FFH
:
:
– 27648
9400H
– 27649
93FFH
:
:
:
– 23.519
– 32512
8100H
0 v– 32513 v80FFH
0
:
– 20.000
8
The table below shows the assignments of analog to digitized output signals for the value ranges: " 20 mA, 0 ... 20 mA, 4 ... 20 mA.
8-88
Overflow
Overrange
Nominal range
Underrange
Underrun
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 269
Analog Modules
8.6.6
Block Diagram, Terminal Assignment and Technical Data
Block Diagram
Simplified representation of potential for the ET 200B-4AO and TB8:
ET 200B-4AO PROFIBUS-DP
24 V 5V 5V V M
Logic N
P
4x MA x.1 x.2 x.3 x.4 Interface between electronics block and terminal block
X1 Analog TB8
Station number selection
M
L+
Suppr. logic STOP/RUN switch
Coding panels
Connection PROFIBUS-DP K+
0.3 0.4
1.3 1.4
2.3 2.4
3.3 3.4
MA L+ L+
K-
0.1 0.2
1.1 1.2
2.1 2.2
3.1 3.2
MA M M
Channel 0
Channel 1
PE
Channel Channel 2 3
8
Analog 24 V ground supply
Figure 8-28 Block Diagram: ET 200B-4AO (6ES7 135-0HF01-0XB0) and TB8
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-89
Page 270
Analog Modules
Terminal Assignment
The table below contains the terminal assignments of the TB8 for ET 200B-4AO, depending on the circuit type used. Table 8-65
Terminal Assignment of the TB8 for ET 200B-4AO (6ES7 135-0HF01-0XB0)
Terminal numbering TB8
Terminal
8
4-Wire Connection
2-Wire Connection
K+
Unassigned
K–
Unassigned x.1
Analog output “voltage” (+)
Analog output “current or voltage” (+)
x.2
Analog output “voltage”” (–)
Analog output “current or voltage” (–)
x.3
Sensor line (S+)
connected to x.1 x.4
Sensor line (S–)
connected to x.2
MA
Analog ground (MA)
MA
Analog ground (MA)
L+
Voltage supply for internal logic
L+
Voltage supply for internal logic
M
Voltage supply for internal logic
M
Voltage supply for internal logic x = 0, 1, 2, 3
Note You must make additional settings for the input circuits of the TB8 via coding plugs. See Figures 8-25 and 8-27 for the necessary settings of the coding plugs.
8-90