Page 261

Analog Modules

Two-Wire Connection of Loads (Current Output)

Two-wire connection of loads for current output is shown below:

Ä Ä Ä

A x.3 . x.1 .

C

A

A

TB8

K+

0.3 0.4

1.3 1.4

MA L+ L+

K–

0.1 0.2

1.1 1.2

MA M M x.2 . x.4 .

. Shield + 24V

RL

RL

Max. 75 V DC/60 V AC PE

Max. 75 V DC/ 60 V AC MA

Mexternal

Figure 8-27 2-Wire Connection of Loads for Current Output

8

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-81

Page 262

Analog Modules

8.6.2

Configuration Options

Type File

The information in this section applies to the type file SI8018BE.200. The type file contains the possible configurations. The configuration you choose depends on the wiring of the module.

Configuration

Table 8-56 shows the possible configurations of the ET 200B-4AO with COM ET 200 Windows or STEP 7. Table 8-56 lists only the slots for configuring the output areas (slots 4 to 7). Slots 1 to 3 have the default value ”004”.

8

Table 8-56

Possible Configurations for the Output Areas of ET 200B-4AO

Configuration

Terminals used Channel 0

Channel 1

Channel 2

Channel 3

0.1/ 0.2

1.1/ 1.2

2.1/ 2.2

3.0/ 3.1

0.3/ 0.4

1.3/ 1.4

2.3/ 2.4

Length1 (in words)

Meaning

3.3/ 3.4

4AO o o o o

4

A start address is assigned for the entire module, addresses for 4 are reserved. (= module addressing)

4 x 1AO o o o o

4

3 x 1AO o o o

2 x 1AO o o

1 x 1AO o

A separate start address can be assigned for each channel. (= single-channel addressing)

1 o

3 2 1

Length of user data = Connection of load = Connection of sensor lines for voltage measurement

Diagnostics

8-82

Diagnostics messages and diagnostics data (slave diagnostics) are returned only for the configured channels.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 263

Analog Modules

8.6.3

Setting the Operating Mode

Setting the Operating Mode

You set the operating mode of the ET 200B-4AO electronics block by means of the coding plugs on the TB8 terminal block and by means of the COM ET 200 or STEP 7 parameterization software. Coding Plugs

The coding plugs of the TB8 enable you to set the output circuit for analog value output of each individual channel of the ET 200B-4AO. The possible settings of the coding plugs are: ”A”, ”B”, ”C” and ”D”. For details of the relationships between the settings of the coding plugs and the output mode or load, see Section 8.6.1. Section 3.1 describes how to change the settings of the coding plugs.

Channel

Some parameters of the ET 200B-4AO listed on the following pages apply only to individual channels. Table 8-57 lists the assignment of TB8 terminals to channels. Table 8-57

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Assignment of Terminals to Channels Channel

Terminals

Channel 0

Terminals 0.1/0.2

Channel 1

Terminals 1.1/1.2

Channel 3

Terminals 2.1/2.2

Channel 4

Terminals 3.1/3.2

8

8-83

Page 264

Analog Modules

Parameters

Table 8-58 shows all the parameters for parameterizing the ET 200B-4AO with COM ET 200 Windows or STEP 7. You can set these parameters for the ET 200B-4AO if you use the type file SI8018BE.200.

Table 8-58

Parameters for ET 200B-4AO (6ES7 135-0HF01-0XB0) Parameter

Diagnostics alarm

Explanation

Explanation

Diagnostics alarm enable for module

Disable Enable

Diagnostics enable for channel 0 Diagnostics enable for channel 1

Diagnostics messages enabled separately for each channel

Disable Enable

Diagnostics enable for channel 2 Diagnostics enable for channel 3 Output value and range for channel 0

Type and range of output defined separately for each channel

Output value and range for channel 1

For voltage output:

" 10 V 0 ... 10 V

For current output:

" 20 mA 0 ... 20 mA 4 ... 20 mA

Representation of output values

Sets representation of the analog values for module

SIMATIC S5 SIMATIC S7

Type of dummy value for channel 0

Defines the dummy value output for each channel in the event of communication interruption

Parameterizable

Sets dummy value for each channel

0

Output value and range for channel 2 Output value and range for channel 3

8

Type of dummy value for channel 1

Last value

Type of dummy value for channel 2 Type of dummy value for channel 3 Dummy value for channel 0 Dummy value for channel 1

*32786 ... 32767

Dummy value for channel 2 Dummy value for channel 3 :

8-84

Default

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 265

Analog Modules

8.6.4

Analog Value Representation, Operation with SIMATIC S5

Analog Value Representation, SIMATIC S7

If you operate the ET 200B-4AO with SIMATIC S5, you can utilize the analog value representation of SIMATIC S7. See Section 8.6.5 for the measuredvalue tables for analog value representation in SIMATIC S7.

Analog Value Representation, SIMATIC S5

Analog values are represented in complements of twos with the ET 200B-4AO.

Table 8-59

The table below shows the analog value representation of the ET 200B-4AO:

Representation of an Analog Output Value as a Bit Pattern (6ES7 135-0HF01-0XB0) High Byte

Low Byte

Bit number

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Analog value representation

SI

210

29

28

27

26

25

24

23

22

21

20

X

X

X

X

Bits 0 ... 3 and 15 have no significance for the amount of the measured value. See Table 8-60 for a detailed description of these bits.

Supplementary Bits

Bits 0 ... 3 and 15 have the following meaning in the bit pattern of the analog output value: Table 8-60 Bit

Meaning

Signal Status

SI

Sign

0

“+” sign

1

“–” sign

X

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8

Description of the Bits (6ES7 135-0HF01-0XB0)

Irrelevant

–

Meaning of the Signal Status

–

8-85

Page 266

Analog Modules

Voltage and Current Output Ranges Table 8-61

Analog Output Signals of the ET 200B-4AO (Value Ranges: 10 V, 0 ... 10 V, 20 mA, 0 ... 20 mA, 4 ... 20 mA; Complement of Twos)

Units

Output Value in mV 0 ... 20 mA

1249 1204

8

The table below shows the assignments of analog to digitized output signals for the value ranges: 10 V, 0 ... 10 V, 20 mA, 0 ... 20 mA, 4 ... 20 mA.

4 ... 20 mA mA

0 ... 10 V

Digitized Output Value

15 14 13 12 11 10 9 8

23.52 23.52

:

7 6 5 4

0 1 0 0 1 1 1 0 0 0 0 1 23.52

11.758

Range

11.758

0 1 0 0 1 0 1 1 0 1 0 0

Overrange

:

:

:

:

:

:

1025

20.0195

20.016

20.2

10.0098

10.0098

0 1 0 0 0 0 0 0 0 0 0 1

1024

20.0

20.0

20.0

10.00

10.00

0 1 0 0 0 0 0 0 0 0 0 0

1023

19.98

19.98

19.98

9.99

9.990

0 0 1 1 1 1 1 1 1 1 1 1

512

10.0

12.0

10.0

5.00

5.000

0 0 1 0 0 0 0 0 0 0 0 0

256

5.0

8.00

5.0

2.50

2.500

0 0 0 1 0 0 0 0 0 0 0 0

1

0.0195

4.015

0.02

0.0098

0.0098

0

0.0

4.0

0.0

0.0

0.000

0 0 0 0 0 0 0 0 0 0 0 0 Nominal range 0 0 0 0 0 0 0 0 0 0 0 0

–1

0.0

3.984

–0.02

0.0

–0.0098

1 1 1 1 1 1 1 1 1 1 1 1

–256

0.0

0.0

–05.0

0.0

–2.500

1 1 1 1 0 0 0 0 0 0 0 0

–512

0.0

0.0

–10.0

0.0

–5.000

1 1 1 0 0 0 0 0 0 0 0 0

–1024

0.0

0.0

–20.00

0.0

–10.000

1 1 0 0 0 0 0 0 0 0 0 0

–1025

0.0

0.0

–20.02

0.0

–10.009

1 0 1 1 1 1 1 1 1 1 1 1

:

:

:

:

:

:

–1204

0.0

0.0

–23.52

0.0

–11.758

8-86

:

:

Overrange

1 0 1 1 0 1 0 0 1 1 0 0

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 267

Analog Modules

8.6.5

Analog Value Representation, Operation with SIMATIC S7

Analog Value Representation, SIMATIC S7

Table 8-62

Analog values are represented in complements of twos with the ET 200B-4AO for SIMATIC S7. The table below shows the analog value representation ET 200B-4AO:

Representation of an Analog Output Value as a Bit Pattern for SIMATIC S7 and ET 200B-4AO High Byte 13

12

11

Low Byte

Bit number

15

14

10

9

8

7

6

5

4

3

2

1

0

Analog value representation

SI

214 213 212 211 210

29

28

27

26

25

24

23

22

21

20

Bit 15 has no significance for the amount of the output value. It merely represents the sign.

Voltage Output Ranges Table 8-63

The table below shows the assignments of analog to digitized output signals for the value ranges: " 10 V, 0 ... 10 V.

Representation of Digitized Measured Values of the ET 200B-4AO (Output Ranges: 0 to 10 V and " 10 V)

Output Range 0 to 10 V

Output Range " 10 V

Units Decimal

Hexadecimal

0

0 w32512 w7F00H

11.7589

11.7589

32511

7EFFH

:

:

:

:

10.0004

10.0004

27649

6C01H

10.0000

10.0000

27648

6C00H

:

:

:

:

0

0

0

0H

:

:

– 6912

E500H

– 6913

E4FFH

:

:

– 10.0000

– 27648

9400H

10.0004

– 27649

93FFH

:

:

:

– 11.7593

– 32512

8100H

0 v– 32513 v80FFH

0 :

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Range

8

Overflow

Overrange

Nominal range

Underrange

Underrun

8-87

Page 268

Analog Modules

Current Output Ranges Table 8-64

Output Range " 20 mA

Representation of Digitized Measured Values of the ET 200B-4AO (Output Ranges: " 20 mA, 0 to 20 mA and 4 to 20 mA) Output Range 0 to 20 mA

Output Range 4 to 20 mA

Range

Units Decimal

Hexadecimal

0

0

0 w32512 w7F00H

23.518

23.518

22.81

32511

7EFFH

:

:

:

:

:

20.0007

20.0007

20.006

27649

6C01H

20.000

20.000

20.000

27648

6C00H

:

:

:

:

0

4.000

0

0H

0

:

:

:

0

– 6912

E500H

0

– 6913

E4FFH

:

:

– 27648

9400H

– 27649

93FFH

:

:

:

– 23.519

– 32512

8100H

0 v– 32513 v80FFH

0

:

– 20.000

8

The table below shows the assignments of analog to digitized output signals for the value ranges: " 20 mA, 0 ... 20 mA, 4 ... 20 mA.

8-88

Overflow

Overrange

Nominal range

Underrange

Underrun

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 269

Analog Modules

8.6.6

Block Diagram, Terminal Assignment and Technical Data

Block Diagram

Simplified representation of potential for the ET 200B-4AO and TB8:

ET 200B-4AO PROFIBUS-DP

24 V 5V 5V V M

Logic N

P

4x MA x.1 x.2 x.3 x.4 Interface between electronics block and terminal block

X1 Analog TB8

Station number selection

M

L+

Suppr. logic STOP/RUN switch

Coding panels

Connection PROFIBUS-DP K+

0.3 0.4

1.3 1.4

2.3 2.4

3.3 3.4

MA L+ L+

K-

0.1 0.2

1.1 1.2

2.1 2.2

3.1 3.2

MA M M

Channel 0

Channel 1

PE

Channel Channel 2 3

8

Analog 24 V ground supply

Figure 8-28 Block Diagram: ET 200B-4AO (6ES7 135-0HF01-0XB0) and TB8

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-89

Page 270

Analog Modules

Terminal Assignment

The table below contains the terminal assignments of the TB8 for ET 200B-4AO, depending on the circuit type used. Table 8-65

Terminal Assignment of the TB8 for ET 200B-4AO (6ES7 135-0HF01-0XB0)

Terminal numbering TB8

Terminal

8

4-Wire Connection

2-Wire Connection

K+

Unassigned

K–

Unassigned x.1

Analog output “voltage” (+)

Analog output “current or voltage” (+)

x.2

Analog output “voltage”” (–)

Analog output “current or voltage” (–)

x.3

Sensor line (S+)

connected to x.1 x.4

Sensor line (S–)

connected to x.2

MA

Analog ground (MA)

MA

Analog ground (MA)

L+

Voltage supply for internal logic

L+

Voltage supply for internal logic

M

Voltage supply for internal logic

M

Voltage supply for internal logic x = 0, 1, 2, 3

Note You must make additional settings for the input circuits of the TB8 via coding plugs. See Figures 8-25 and 8-27 for the necessary settings of the coding plugs.

8-90

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c