Analog Modules
Current Measuring Ranges
The two tables below show the representation of the digitized measuring values of the ET 200B-4AI for the measuring ranges: " 20 mA, 0 ... 20 mA and 4 ... 20 mA. Table 8-53
Representation of Digitized Measured Values of the ET 200B-4AI (Measuring Range: " 20 mA)
Measuring Range " 20 mA
Decimal
Hexadecimal w 23.5185
32767
7FFFH
23.518
32511
7EFFH
:
:
20.0007
27649
6C01H
20.000
27648
6C00H
15.000
20736
5100H
:
:
:
– 15.000
–20736
AF00H
– 20.000
–27648
9400H
– 20.0007
–27649
93FFH
:
:
:
– 23.5185
–32512
8100H v– 23.519
–32768
8000H
Units
:
Table 8-54
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Range Overflow
Overrange
Nominal range
Underrange
Underrun
Representation of Digitized Measured Values of the ET 200B-4AI (Measuring Ranges: 0 to 20 mA and 4 to 20 mA)
Measuring Range From 0 to 20 mA
Measuring Range From 4 to 20 mA w 23.5185
Units Decimal
Hexadecimal w 22.815
32767
7FFFH
23.518
22.814
32511
7EFFH
:
:
:
:
20.0007
20.0006
27649
6C01H
20.000
20.000
27648
6C00H
15.000
16.000
20736
5100H
:
:
:
:
0.000
4.000
0
0H
-0.0007
3.9995
–1
FFFFH
:
:
:
:
–3.5185
1.1852
–4864
ED00H v–3.5192 v1.1846
–32768
8000H
Range
Overflow
Overrange
Nominal range
Underrange
Underrun
8-71
8
Page 252
Analog Modules
8.5.6
Block Diagram, Terminal Assignment and Technical Data
Schematic Circuit Diagram
Simplified representation of potential for the ET 200B-4AI and TB8:
ET 200B-4AI PROFIBUS-DP
24 V 5V 5V V M
Logic P
4x MA x.1 x.2 x.4 Interface between electronics block and terminal block
X1 Analog TB8
Station number selection Connection PROFIBUSDP
8
N
PE
M
L+
Suppr. logic STOP/RUN switch
Coding panels
K+
0.3 0.4
1.3 1.4
2.3 2.4
3.3 3.4
MA L+ L+
K-
0.1 0.2
1.1 1.2
2.1 2.2
3.1 3.2
MA M M
Channel Channel 0 1
Channel 2
Channel Analog 24 V 3 ground supply
Figure 8-23 Block Diagram: ET 200B-4AI (6ES7 134-0HF10-0XB0) and TB8
8-72
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 253
Analog Modules
Terminal Assignment
The table below contains the terminal assignments of the TB8 for ET 200B-4AI: Table 8-55
Terminal Assignment of the TB8 for ET 200B-4AI (6ES7 134-0HF01-0XB0)
Terminal numbering TB8
Terminal
Assignment
K+
Unassigned
K–
Unassigned x.1
Measuring line (+)
x.2
Measuring line (–)
x.3
Unassigned x.4
Connection, resistance measurement
MA
Analog ground (MA)
MA
Analog ground (MA)
L+
Voltage supply, internal logic
L+
Voltage supply, internal logic
M
Voltage supply, internal logic
M
Voltage supply, internal logic
8 x = 0, 1, 2, 3
Note Certain additional settings must be made for the input circuit by means of the coding plugs of the TB8. The settings of the coding plugs are illustrated in Figures 8-17 to 8-22.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-73
Page 254
Analog Modules
Technical Data
The technical data of the ET 200B-4AI electronics block are listed in the table below.
Technical specifications Baud rates*
Inputs 9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud
Number of inputs
Galvanic isolation to inter- No nal electronics
Bus protocol
PROFIBUS-DP
Galvanic isolation to the SINEC L2-DP bus
Yes
Galvanic isolation to volt- Yes age supply of internal logic
Power losses
Typically 1.8 W
Measured value ranges Voltage sensors
Weight (EB and TB)
Approx. 550 g (19.25 oz.)
Dimensions (EB and TB: W x H x D)
160 x 130 x 60
Current sensors
Diagnostics functions, alarms Voltage monitoring
Green ”RUN” LED
Bus monitoring, SINEC L2-DP
Red ”BF” LED
Group diagnostics
Red ”DIA” LED, parameterizable
Alarms Limit-value alarm
Diagnostics alarm
Yes, parameterizable channels 0 and 2 Yes, parameterizable
Supply voltage for inputs and internal logic
8
4
Supply voltage (L+) Rated value Permissible range Value for t < 0.5 s
24 V DC 18.5 ... 30.2 V 35 V
Current consumption from L+ Logic 70 mA *
" 1.25 V " 2.5 V " 5V " 10 V 0 ... 20 mA 4 ... 20 mA " 20 mA
Connection of signal sensors For voltage measure- Possible ment (2-wire connection) For current measure- Possible ment (2-wire connection) For measuring trans- Possible, 2-wire- and ducer 4-wire measuring transducers Input resistance Voltage measurement Current measurement Measured value representation SIMATIC S5 w100 KW 125 W
Measuring principle
12-bit complement of twos or 11-bit amount with sign or 12-bit binary (selectable) Max. 14-bit complement of twos (depends on integration time) Successive approximation
Conversion time
Max. 100 ms
Cycle time of module
Approx. 5 ms
SIMATIC S7
In operation with the IM 308-B, the maximum possible baud rate is 1500 kbaud.
Permissible potential difference Across inputs of a channel Inputs to MA (UCM) MA to PE or M
Max. " 10 V Max. " 1 V Max. 75 V DC/60 V AC
Error message in the event of Range overshoot Yes (nominal range) Wire break of signal- Only for measuring range sensor lines 4 ... 20 mA
8-74
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 255
Analog Modules
Inputs (continued) Noise suppression for f = n x (50/60 Hz " 1%) n = 1, 2, ... Common-mode inter- min. 70 dB ference (USS t1 V) Basic error limit Voltage ranges Current range
0.15 % 0.20 %
Working error limit (0 ... 60 °C) Voltage ranges Current range
0.32 % 0.41 %
Permissible input voltage (destruction limit)
Max. " 30 V (static) or " 75 V (pulse for max. 1ms and 1:20 sampling)
Permissible input current (destruction limit)
Max. 24 mA
Cable length Shielded
Max. 100 m
8
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-75
Page 256
Analog Modules
8.6
Electronics Block ET 200B-4AO (6ES7 135-0HF01-0XB0)
Characteristics
The ET 200B-4AO electronics block has the following characteristics:
4 inputs, floating to the supply voltage of the internal logic Output ranges: – Voltage output: 10 V, 0 ... 10 V – Current output: 20 mA, 0 ... 20 mA, 4 ... 20 mA
Supply voltage: 24 V DC Loads connectable in – 4-wire connection – 2-wire connection
Output range selection via COM ET 200 or STEP 7 or directly via parameterization telegram (see Chapter 4)
Dimensional Drawing
See Figure 8-4 for the precise dimensions.
8
Figure 8-24 Front Elevation: ET 200B-4AO (6ES7 135-0HF01-0XB0)
8-76
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 257
Analog Modules
List of Subsections
The following aspects of the ET 200B-4AO are described below: In Section you will find on Page
8.6.1
Connecting loads
8-78
8.6.2
Configuration options
8-82
8.6.3
Setting the operating mode
8-83
8.6.4
Analog-value representation, operation with SIMATIC S5
8-85
8.6.5
Analog-value representation, operation with SIMATIC S7
8-87
8.6.6
Block diagram, pin assignment and technical data
8-89
8
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-77
Page 258
Analog Modules
8.6.1
Connecting Loads
Possible Connections
There are two methods of connecting loads to the ET 200B-4AO:
4-wire connection of loads 2-wire connection of loads
On the Following Pages
The following pages contain a connection example for every connection possibility. Please note the following rules.
Rules
Please note the following rules when connecting loads to the ET 200B-4AO:
The output terminals x.2 (x = 0 to 3) have a fixed connection to analog ground (MA). If non-floating loads are connected to a common reference potential, please ensure minimum potential differences. Failure to do so can lead to undesired transient currents across the output module.
You are recommended to connect floating-ground loads which are floating with reference to each other. In such cases, connect analog ground (MA) with PE ( ) to enhance noise immunity.
The connection terminals of unused outputs are left open. You must short-circuit terminals “K+” and “K–”. For this purpose, set the coding plug to the “C” position.
8 !
Caution If the supply voltage is below the lower tolerance limit, the output analog values can deviate from the specified values.
Note Please note the explanation of shielding of analog lines in Sections 3.1 and 3.5.
8-78
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 259
Analog Modules
4-Wire Connection of Loads (Voltage Output)
The voltage on the load is re-adjusted via two high-resistance sensor lines per channel (S+, S– at terminals x.3 and x.4). In this way, voltage drops of up to 3 V per line can be re-adjusted. Please ensure that the sensor lines are connected directly to the load. 4-wire connection of loads for voltage output is shown below:
A x.3 x.1 .
x.2 x.4 .
.
.
Ä Ä Ä C
A
A
TB8
K+
0.3 0.4
1.3 1.4
MA L+ L+
K–
0.1 0.2
1.1 1.2
MA M M
. Shield + 24V S+
S–
. . . . RL
RL
Max. 75 V DC/60 V AC PE
Max. 75 V DC/ 60 V AC MA
Mexternal
8
Figure 8-25 4-Wire Connection of Loads for Voltage Output
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-79
Page 260
Analog Modules
2-Wire Connection of Loads (Voltage Output)
The sensor lines are not required for 2-wire connection. Two-wire connection is possible for voltage output if the line resistance of the signal lines is negligible compared to the load resistance. 2-wire connection of loads for voltage output is shown below:
B x.3 x.1 .
Ä Ä Ä x.2 . x.4 .
C
B
B
TB8
K+
0.3 0.4
1.3 1.4
MA L+ L+
K–
0.1 0.2
1.1 1.2
MA M M
. Shield + 24V
RL
RL Max. 75 V DC/ 60 V AC
Max. 75 V DC/60 V AC PE
MA
Mexternal
Figure 8-26 2-Wire Connection of Loads for Voltage Output
8
8-80
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c