SIMATIC ET 200B Distributed I/O Station Manual: 8 Analog Modules, pages 251 to 260

Pages 251 to 260 of 344, from SIMATIC ET 200B Distributed I/O Station Manual

The original document is the PDF (2.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Siemens ET 200B

Page 251

Analog Modules

Current Measuring Ranges

The two tables below show the representation of the digitized measuring values of the ET 200B-4AI for the measuring ranges: " 20 mA, 0 ... 20 mA and 4 ... 20 mA. Table 8-53

Representation of Digitized Measured Values of the ET 200B-4AI (Measuring Range: " 20 mA)

Measuring Range " 20 mA

Decimal

Hexadecimal w 23.5185

32767

7FFFH

23.518

32511

7EFFH

:

:

20.0007

27649

6C01H

20.000

27648

6C00H

15.000

20736

5100H

:

:

:

– 15.000

–20736

AF00H

– 20.000

–27648

9400H

– 20.0007

–27649

93FFH

:

:

:

– 23.5185

–32512

8100H v– 23.519

–32768

8000H

Units

:

Table 8-54

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Range Overflow

Overrange

Nominal range

Underrange

Underrun

Representation of Digitized Measured Values of the ET 200B-4AI (Measuring Ranges: 0 to 20 mA and 4 to 20 mA)

Measuring Range From 0 to 20 mA

Measuring Range From 4 to 20 mA w 23.5185

Units Decimal

Hexadecimal w 22.815

32767

7FFFH

23.518

22.814

32511

7EFFH

:

:

:

:

20.0007

20.0006

27649

6C01H

20.000

20.000

27648

6C00H

15.000

16.000

20736

5100H

:

:

:

:

0.000

4.000

0

0H

-0.0007

3.9995

–1

FFFFH

:

:

:

:

–3.5185

1.1852

–4864

ED00H v–3.5192 v1.1846

–32768

8000H

Range

Overflow

Overrange

Nominal range

Underrange

Underrun

8-71

8

Page 252

Analog Modules

8.5.6

Block Diagram, Terminal Assignment and Technical Data

Schematic Circuit Diagram

Simplified representation of potential for the ET 200B-4AI and TB8:

ET 200B-4AI PROFIBUS-DP

24 V 5V 5V V M

Logic P

4x MA x.1 x.2 x.4 Interface between electronics block and terminal block

X1 Analog TB8

Station number selection Connection PROFIBUSDP

8

N

PE

M

L+

Suppr. logic STOP/RUN switch

Coding panels

K+

0.3 0.4

1.3 1.4

2.3 2.4

3.3 3.4

MA L+ L+

K-

0.1 0.2

1.1 1.2

2.1 2.2

3.1 3.2

MA M M

Channel Channel 0 1

Channel 2

Channel Analog 24 V 3 ground supply

Figure 8-23 Block Diagram: ET 200B-4AI (6ES7 134-0HF10-0XB0) and TB8

8-72

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 253

Analog Modules

Terminal Assignment

The table below contains the terminal assignments of the TB8 for ET 200B-4AI: Table 8-55

Terminal Assignment of the TB8 for ET 200B-4AI (6ES7 134-0HF01-0XB0)

Terminal numbering TB8

Terminal

Assignment

K+

Unassigned

K–

Unassigned x.1

Measuring line (+)

x.2

Measuring line (–)

x.3

Unassigned x.4

Connection, resistance measurement

MA

Analog ground (MA)

MA

Analog ground (MA)

L+

Voltage supply, internal logic

L+

Voltage supply, internal logic

M

Voltage supply, internal logic

M

Voltage supply, internal logic

8 x = 0, 1, 2, 3

Note Certain additional settings must be made for the input circuit by means of the coding plugs of the TB8. The settings of the coding plugs are illustrated in Figures 8-17 to 8-22.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-73

Page 254

Analog Modules

Technical Data

The technical data of the ET 200B-4AI electronics block are listed in the table below.

Technical specifications Baud rates*

Inputs 9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud

Number of inputs

Galvanic isolation to inter- No nal electronics

Bus protocol

PROFIBUS-DP

Galvanic isolation to the SINEC L2-DP bus

Yes

Galvanic isolation to volt- Yes age supply of internal logic

Power losses

Typically 1.8 W

Measured value ranges Voltage sensors

Weight (EB and TB)

Approx. 550 g (19.25 oz.)

Dimensions (EB and TB: W x H x D)

160 x 130 x 60

Current sensors

Diagnostics functions, alarms Voltage monitoring

Green ”RUN” LED

Bus monitoring, SINEC L2-DP

Red ”BF” LED

Group diagnostics

Red ”DIA” LED, parameterizable

Alarms Limit-value alarm

Diagnostics alarm

Yes, parameterizable channels 0 and 2 Yes, parameterizable

Supply voltage for inputs and internal logic

8

4

Supply voltage (L+) Rated value Permissible range Value for t < 0.5 s

24 V DC 18.5 ... 30.2 V 35 V

Current consumption from L+ Logic 70 mA *

" 1.25 V " 2.5 V " 5V " 10 V 0 ... 20 mA 4 ... 20 mA " 20 mA

Connection of signal sensors For voltage measure- Possible ment (2-wire connection) For current measure- Possible ment (2-wire connection) For measuring trans- Possible, 2-wire- and ducer 4-wire measuring transducers Input resistance Voltage measurement Current measurement Measured value representation SIMATIC S5 w100 KW 125 W

Measuring principle

12-bit complement of twos or 11-bit amount with sign or 12-bit binary (selectable) Max. 14-bit complement of twos (depends on integration time) Successive approximation

Conversion time

Max. 100 ms

Cycle time of module

Approx. 5 ms

SIMATIC S7

In operation with the IM 308-B, the maximum possible baud rate is 1500 kbaud.

Permissible potential difference Across inputs of a channel Inputs to MA (UCM) MA to PE or M

Max. " 10 V Max. " 1 V Max. 75 V DC/60 V AC

Error message in the event of Range overshoot Yes (nominal range) Wire break of signal- Only for measuring range sensor lines 4 ... 20 mA

8-74

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 255

Analog Modules

Inputs (continued) Noise suppression for f = n x (50/60 Hz " 1%) n = 1, 2, ... Common-mode inter- min. 70 dB ference (USS t1 V) Basic error limit Voltage ranges Current range

0.15 % 0.20 %

Working error limit (0 ... 60 °C) Voltage ranges Current range

0.32 % 0.41 %

Permissible input voltage (destruction limit)

Max. " 30 V (static) or " 75 V (pulse for max. 1ms and 1:20 sampling)

Permissible input current (destruction limit)

Max. 24 mA

Cable length Shielded

Max. 100 m

8

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-75

Page 256

Analog Modules

8.6

Electronics Block ET 200B-4AO (6ES7 135-0HF01-0XB0)

Characteristics

The ET 200B-4AO electronics block has the following characteristics:

4 inputs, floating to the supply voltage of the internal logic Output ranges: – Voltage output: 10 V, 0 ... 10 V – Current output: 20 mA, 0 ... 20 mA, 4 ... 20 mA

Supply voltage: 24 V DC Loads connectable in – 4-wire connection – 2-wire connection

Output range selection via COM ET 200 or STEP 7 or directly via parameterization telegram (see Chapter 4)

Dimensional Drawing

See Figure 8-4 for the precise dimensions.

8

Figure 8-24 Front Elevation: ET 200B-4AO (6ES7 135-0HF01-0XB0)

8-76

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 257

Analog Modules

List of Subsections

The following aspects of the ET 200B-4AO are described below: In Section you will find on Page

8.6.1

Connecting loads

8-78

8.6.2

Configuration options

8-82

8.6.3

Setting the operating mode

8-83

8.6.4

Analog-value representation, operation with SIMATIC S5

8-85

8.6.5

Analog-value representation, operation with SIMATIC S7

8-87

8.6.6

Block diagram, pin assignment and technical data

8-89

8

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-77

Page 258

Analog Modules

8.6.1

Connecting Loads

Possible Connections

There are two methods of connecting loads to the ET 200B-4AO:

4-wire connection of loads 2-wire connection of loads

On the Following Pages

The following pages contain a connection example for every connection possibility. Please note the following rules.

Rules

Please note the following rules when connecting loads to the ET 200B-4AO:

The output terminals x.2 (x = 0 to 3) have a fixed connection to analog ground (MA). If non-floating loads are connected to a common reference potential, please ensure minimum potential differences. Failure to do so can lead to undesired transient currents across the output module.

You are recommended to connect floating-ground loads which are floating with reference to each other. In such cases, connect analog ground (MA) with PE ( ) to enhance noise immunity.

The connection terminals of unused outputs are left open. You must short-circuit terminals “K+” and “K–”. For this purpose, set the coding plug to the “C” position.

8 !

Caution If the supply voltage is below the lower tolerance limit, the output analog values can deviate from the specified values.

Note Please note the explanation of shielding of analog lines in Sections 3.1 and 3.5.

8-78

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 259

Analog Modules

4-Wire Connection of Loads (Voltage Output)

The voltage on the load is re-adjusted via two high-resistance sensor lines per channel (S+, S– at terminals x.3 and x.4). In this way, voltage drops of up to 3 V per line can be re-adjusted. Please ensure that the sensor lines are connected directly to the load. 4-wire connection of loads for voltage output is shown below:

A x.3 x.1 .

x.2 x.4 .

.

.

Ä Ä Ä C

A

A

TB8

K+

0.3 0.4

1.3 1.4

MA L+ L+

K–

0.1 0.2

1.1 1.2

MA M M

. Shield + 24V S+

S–

. . . . RL

RL

Max. 75 V DC/60 V AC PE

Max. 75 V DC/ 60 V AC MA

Mexternal

8

Figure 8-25 4-Wire Connection of Loads for Voltage Output

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-79

Page 260

Analog Modules

2-Wire Connection of Loads (Voltage Output)

The sensor lines are not required for 2-wire connection. Two-wire connection is possible for voltage output if the line resistance of the signal lines is negligible compared to the load resistance. 2-wire connection of loads for voltage output is shown below:

B x.3 x.1 .

Ä Ä Ä x.2 . x.4 .

C

B

B

TB8

K+

0.3 0.4

1.3 1.4

MA L+ L+

K–

0.1 0.2

1.1 1.2

MA M M

. Shield + 24V

RL

RL Max. 75 V DC/ 60 V AC

Max. 75 V DC/60 V AC PE

MA

Mexternal

Figure 8-26 2-Wire Connection of Loads for Voltage Output

8

8-80

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c