Page 241
Analog Modules
8.5.2
Configuration Options
Type File
The information in this section applies to the type file SI8019BE.200. The type file contains the possible configurations. The configuration you choose depends on the wiring of the module.
Configuration
Table 8-38 shows the possible configurations of the ET 200B-4AI with COM ET 200 Windows or STEP 7. Table 8-38 lists only the slots for configuring the Input areas (slots 4 to 7). Slots 1 to 4 have the default value ”004”.
Table 8-38
Possible Configurations for the Input Areas of ET 200B-4AI Length1 (in words)
Meaning
4AI
4
A start address is assigned for the entire module, addresses for 4 words are reserved. (= module addressing)
4 x 1AI
4
3 x 1AI
3
A separate start address can be assigned for each channel. (= single-channel addressing)
2 x 1AI
2
1 x 1AI
1
Configuration
1
Terminals used Channel 0
Channel 1
Channel 2
Channel 3
0.1/0.2
1.1/1.2
2.1/2.2
3.0/3.1
8
Length of user data = Connection of measuring lines
Diagnostics
Diagnostics messages and diagnostics data (slave diagnostics) are returned only for the configured channels.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-61
Page 242
Analog Modules
8.5.3
Setting the Operating Mode
Setting the Operating Mode
You set the operating mode of the ET 200B-4AI electronics block by means of the coding plugs on the TB8 terminal block and by means of the COM ET 200 or STEP 7 parameterization software. Coding Plugs
The coding plugs of the TB8 enable you to set the input circuit of the TB8 for analog value measurement of each individual channel of the ET 200B-4AI in accordance with the measured-value sensor connected and the desired mode of measurement. The possible settings of the coding plugs are: ”A”, ”B”, ”C” and ”D”. For details of the relationships between the settings of the coding plugs and the mode of measurement and the measured-value sensors, see Section 8.5.1. Section 3.1 describes how to change the settings of the coding plugs.
Channel
Some parameters of the ET 200B-4AI listed on the following pages apply only to individual channels. Table 8-39 lists the assignment of TB8 terminals to channels. Table 8-39
8
8-62
Assignment of Terminals to Channels Channel
Terminals
Channel 0
Terminals 0.1/0.2
Channel 1
Terminals 1.1/1.2
Channel 2
Terminals 2.1/2.2
Channel 3
Terminals 3.1/3.2
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 243
Analog Modules
Parameters
Table 8-40 shows all the parameters for parameterizing the ET 200B-4AI with COM ET 200 Windows or STEP 7. You can set these parameters for the ET 200B-4AI if you use the type file SI8019BE.200.
Table 8-40
Parameters for ET 200B-4AI (6ES7 134-0HF01-0XB0) Parameter
Diagnostics alarm
Explanation
Value Range
Diagnostics alarm enable for module
Disable Enable
Limit-value alarm
Limit-value alarm enable for module
Disable Enable
Diagnostics enable for channel 0 Diagnostics enable for channel 1
Diagnostics messages enabled separately for each channel
Disable
Wire break monitoring enabled separately for each channel group for measuring range 4 ... 20 mA
Disable
You can set the measurement type and range separately for each channel
Channel not activated
Enable
Diagnostics enable for channel 2 Diagnostics enable for channel 3 Wire break monitoring enable for channel 0 Wire break monitoring enable for channel 1
Enable
Wire break monitoring enable for channel 2 Wire break monitoring enable for channel 3 Measurement type and range for channel 0
For voltage measurement:
10 V
2.5 V 1.25 V
For current measurement:
20 mA 0 ... 20 mA 4 ... 20 mA
Representation of measured values
Sets representation of the analog measured values for module
SIMATIC S5 SIMATIC S7
Measured value representation: S5
Sets data format for analog value representation, SIMATIC S5
Complement of twos Amount with sign Binary
Measuring type and range for channel 1 Measuring type and range for channel 2 Measuring type and range for channel 3
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8
8-63
Page 244
Analog Modules
Table 8-40
Parameters for ET 200B-4AI (6ES7 134-0HF01-0XB0), continued Parameter
Upper limit value for channel 0
Explanation
Value Range
Upper and lower limit values for each channel
0 *32768 ... 32767
Lower limit value for channel 0
0 *32768 ... 32767
Upper limit value for channel 2
0 *32768 ... 32767
Lower limit value for channel 2
0 *32768 ... 32767
:
Default
8
8-64
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 245
Analog Modules
8.5.4
Analog Value Representation, Operation with SIMATIC S5
Analog Value Representation, SIMATIC S7
If you operate the ET 200B-4AI with SIMATIC S5, you can utilize the analog value representation of SIMATIC S7 (higher measured-value resolution: max. 14 bits + sign). See Section 8.5.5 for the measured-value tables for analog value representation in SIMATIC S7.
Analog Value Representation, SIMATIC S5
Analog values can be represented in three data formats with the ET 200B-4AI:
12-bit complement of twos representation (range: –2048 to +2047 units) 11-bit amount and 1-bit sign (range: –2048 to +2047 units) 12-bit binary number (range: 0 to 4095 units) The table below shows the analog value representation of the ET 200B-4AI:
Table 8-41
Representation of an Analog Input Value as a Bit Pattern (6ES7 134-0HF01-0XB0) High Byte
Bit number Analog value representation
Low Byte
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
SI
211
210
29
28
27
26
25
24
23
22
21
20
X
X
OV
Bits 0 to 2 and bit 15 have no significance for the amount of the measured value. See Table 8-42 for a detailed description of these bits.
Supplementary Bits
8
Bits 0 to 2 and bit 15 have the following meaning in the bit pattern of the analog input value: Table 8-42 Bit
Meaning
Signal Status
OV
Overflow bit
1
Overrange1
SI
Sign
0
“+” sign
1
“–” sign
X 1
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Description of the Bits (6ES7 134-0HF01-0XB0)
Irrelevant
–
Meaning of the Signal Status
–
In the event of overflow at one measuring point, the overflow bits of the other channels remain unaffected; this means the values of the other channels are correct and can be evaluated.
8-65
Page 246
Analog Modules
Voltage Measuring Ranges
The tables below show the assignments of analog to digitized measured values for the measuring ranges: 1.25 V, 2.5 V, 5 V, 10 V. The ET 200B-4AI module (6ES7 134-0HF01-0XB0) does not have an overrange.
Table 8-43
Representation of Digitized Measured Values of the ET 200B-4AI (6ES7 134-0HF01-0XB0; Measuring Ranges: 1.25 V, 2.5 V, 5 V, 10 V; Complement of Twos)
Units
Measured Value in V
X X OV
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
2047
1.2494
2.4988
4.9976
9.9951
0 0 1 1 1 1 1 1 1 1 1 1 1 0 0 1
2046
1.2488
2.4975
4.9951
9.9902
0 0 1 1 1 1 1 1 1 1 1 1 0 0 0 0
:
:
:
:
:
:
1
0.0006
0.0012
0.0024
0.0049
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0
0
0.0000
0.0000
0.0000
0.0000
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
–1
–0.0006
–0.0012
–0.0024
–0.0049 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0
:
:
:
:
–2047
–1.2494
–2.4988
–4.9976
–9.9951 1 1 0 0 0 0 0 0 0 0 0 0 1 0 0 0
–2048
–1.2500
–2.5000
–5.0000
–10.000 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 1
Table 8-44
8
Digitized Measured Value
:
:
Nomina l range
:
Representation of Digitized Measured Values of the ET 200B-4AI (6ES7 134-0HF01-0XB0; Measuring Ranges: 1.25 V, 2.5 V, 5 V, 10 V; Amount and Sign)
Units
Measured Value in V
SI
Digitized Measured Value
X X OV
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
2047
1.2494
2.4988
4.9976
9.9951
0
0 1 1 1 1 1 1 1 1 1 1 1 0 0 1
2046
1.2488
2.4975
4.9951
9.9902
0
0 1 1 1 1 1 1 1 1 1 1 0 0 0 0
:
:
:
:
:
1
0.0006
0.0012
0.0024
0.0049
0
0 0 0 0 0 0 0 0 0 0 0 1 0 0 0
0
0.0000
0.0000
0.0000
0.0000
0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
–1
–0.0006
–0.0012
–0.0024
–0.0049
1
0 0 0 0 0 0 0 0 0 0 0 1 0 0 0
:
:
:
:
:
–2047
–1.2494
–2.4988
–4.9976
–9.9951
1
0 1 1 1 1 1 1 1 1 1 1 1 0 0 0
–2048
–1.2500
–2.5000
–5.0000
–10.000
1
1 0 0 0 0 0 0 0 0 0 0 0 0 0 1
8-66
Range
Range
: Nominal range
:
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 247
Analog Modules
Table 8-45
Representation of Digitized Measured Values of the ET 200B-4AI (6ES7 134-0HF01-0XB0; Measuring Ranges: 1.25 V, 2.5 V, 5 V, 10 V; Binary)
Units
Measured Value in V
Digitized Measured Value
X X OV
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
4095
1.2494
2.4988
4.9976
9.9951
0 1 1 1 1 1 1 1 1 1 1 1 1 0 0 1
4094
1.2488
2.4975
4.9951
9.9902
0 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0
:
:
:
:
:
:
2049
0.0006
0.0012
0.0024
0.0049
0 1 0 0 0 0 0 0 0 0 0 0 1 0 0 0
2048
0.0000
0.0000
0.0000
0.0000
0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0
2047
–0.0006
–0.0012
–0.0024
–0.0049
0 0 1 1 1 1 1 1 1 1 1 1 1 0 0 0
:
:
:
:
:
:
1
–1.2494
–2.4988
–4.9976
–9.9951
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0
0
–1.2500
–2.5000
–5.0000
–10.000
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1
Current Measuring Ranges
Range
Nomin al range
:
The tables below show the assignments of analog to digitized measured values for the measuring ranges: 0 ... 20 mA, 4 ... 20 mA, 20 mA. The ET 200B-4AI module (6ES7 134-0HF01-0XB0) does not have an overrange. Table 8-46
Units
Representation of Digitized Measured Values of the ET 200B-4AI (6ES7 134-0HF01-0XB0; Measuring Range: 20 mA; Complement of Twos) Measured Value in mA
Digitized Measured Value
X X OV
Range mA 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
2047
19.9902
0 0 1 1 1 1 1 1 1 1 1 1 1 0 0 1
2046
19.9804
0 0 1 1 1 1 1 1 1 1 1 1 0 0 0 0
:
:
:
1
0.00976
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0
0
0.0000
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
–1
–0.00976
1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0
:
:
:
–2047
–19.9902
1 1 0 0 0 0 0 0 0 0 0 0 1 0 0 0
–2048
–20.0000
1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 1
Nomina l range
8-67
8
Page 248
Analog Modules
Table 8-47
Units
Representation of Digitized Measured Values of the ET 200B-4AI (6ES7 134-0HF01-0XB0; Measuring Range: 20 mA; Amount and Sign) Measured Value in mA
SI mA
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
2047
19.9902
0
0 1 1 1 1 1 1 1 1 1 1 1 0 0 1
2046
19.9804
0
0 1 1 1 1 1 1 1 1 1 1 0 0 0 0
:
:
1
0.00976
0
0 0 0 0 0 0 0 0 0 0 0 1 0 0 0
0
0.0000
0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
–1
–0.00976
1
0 0 0 0 0 0 0 0 0 0 0 1 0 0 0
:
:
–2047
–19.9902
1
0 1 1 1 1 1 1 1 1 1 1 1 0 0 0
–2048
–20.0000
1
1 0 0 0 0 0 0 0 0 0 0 0 0 0 1
Table 8-48
Units
8
Digitized Measured Value
X X OV
Range
: Nominal range
:
Representation of Digitized Measured Values of the ET 200B-4AI (6ES7 134-0HF01-0XB0; Measuring Range: 20 mA; Binary) Measured Value in mA
Digitized Measured Value
X X OV
Range mA 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
8-68
4095
19.9902
0 1 1 1 1 1 1 1 1 1 1 1 1 0 0 1
4094
19.9804
0 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0
:
:
:
2049
0.00976
0 1 0 0 0 0 0 0 0 0 0 0 1 0 0 0
2048
0.0000
0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0
2047
–0.00976
0 0 1 1 1 1 1 1 1 1 1 1 1 0 0 0
:
:
:
1
–19.9902
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0
0
–20.0000
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1
Nomina l range
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 249
Analog Modules
Table 8-49
Units
Representation of Digitized Measured Values of the ET 200B-4AI (6ES7 134-0HF01-0XB0; Measuring Range: 0 ... 20 mA) Measured Value in mA
Digitized Measured Value1
X X OV
Range
0 to 20 mA 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
1
4095
19.9951
0 1 1 1 1 1 1 1 1 1 1 1 1 0 0 1
4094
19.9902
0 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0
:
:
:
1
0.00488
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0
0
0.00000
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1
Nomina l range
Same representation for two’s complement, amount and sign, and binary
Table 8-50
Units
Representation of Digitized Measured Values of the ET 200B-4AI (6ES7 134-0HF01-0XB0; Measuring Range: 4 ... 20 mA) Measured Value in mA
Digitized Measured Value1
X X OV
Range
4 to 20 mA 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
1
Note
2559
19.992
0 1 0 0 1 1 1 1 1 1 1 1 1 0 0 1
2048
16.000
0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0
512
4.000
0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0
511
3.992
0 0 0 0 1 1 1 1 1 1 1 1 1 0 0 0
384
3.000
0 0 0 0 1 1 0 0 0 0 0 0 0 0 0 0
383
2.992
0 0 0 0 1 0 1 1 1 1 1 1 1 0 0 0
0
0.000
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1
Nominal range
Same representation for two’s complement, amount and sign, and binary
The measuring range 4 to 20 mA is resolved to 2048 units in the interval 512 to 2560. For a representation in the range 0 to 2048 units, 512 units must be subtracted per software.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-69
8
Page 250
Analog Modules
8.5.5
Analog Value Representation, Operation with SIMATIC S7
Analog Value Representation, SIMATIC S7
Table 8-51
If you operate the ET 200B-4AI with SIMATIC S7 the analog values are represented in complements of twos. The table below shows the analog value representation of the ET 200B-4AI:
Representation of an Analog Input Value as a Bit Pattern for SIMATIC S7 and ET 200B-4AI High Byte 13
12
11
Low Byte
Bit Number
15
14
10
9
8
7
6
5
4
3
2
1
0
Analog Value Representation
SI
214 213 212 211 210
29
28
27
26
25
24
23
22
21
20
Bit 15 has no significance for the amount of the measured value. It merely represents the sign.
Voltage Measuring Ranges
Table 8-52
8
The table below shows the representation of the digitized measuring values of the ET 200B-4AI for the measuring ranges: " 1.25 V, " 2.5 V, " 5 V and " 10 V.
Representation of Digitized Measured Values of the ET 200B-4AI (Measuring Ranges: " 1.25 V, " 2.5 V, " 5 V and " 10 V)
Measuring Range " 1.25 V
Measuring Range " 2.5V
Measuring Range "5V
Measuring Range " 10 V w 1.4699 w 2.9398 w 5.8796
1.46986
2.9397
Units Decimal
Hexadecimal w 11.759
32767
7FFFH
5.8794
11.7589
32511
7EFFH
:
:
:
:
:
1.25005
2.5001
5.0002
10.0004
27649
6C01H
1.25
2.50
5.00
10.00
27648
6C00H
0.9375
1.875
3.75
7.50
20736
5100H
:
:
:
:
:
:
– 0.9375
– 1.875
– 3.75
– 7.50
–20736
AF00H
– 1.25
– 2.50
– 5.00
– 10.00
–27648
9400H
– 1.25005
– 2.5001
– 5.0002
– 10.0004
–27649
93FFH
:
:
:
:
:
:
– 1.4699
– 2.9398
– 5.8796
– 11.759
–32512
8100H v– 1.47 v– 2.94 v– 5.88 v– 11.76
–32768
8000H
:
8-70
Range
Overflow
Overrange
Nominal range
Underrange
Underrun
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c