SIMATIC ET 200B Distributed I/O Station Manual: 8 Analog Modules, pages 231 to 240

Pages 231 to 240 of 344, from SIMATIC ET 200B Distributed I/O Station Manual

The original document is the PDF (2.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Siemens ET 200B

Page 231

Analog Modules

8.5

Electronics Block ET 200B-4AI (6ES7 134-0HF01-0XB0)

Characteristics

The ET 200B-4AI electronics block has the following characteristics:

4 inputs, floating to the supply voltage of the internal logic Measuring ranges: – Voltage: 1.25 V, 2.5 V, 5 V, 10 V, – Current: 0 to 20 mA, 4 to 20 mA, mA

Measuring principle: successive approximation Supply voltage: 24 V DC Connectable sensors – Voltage sensors (2-wire connection) – Current sensors (2-wire connection)

Measured-value range selection via COM ET 200 or STEP 7 or directly via parameterization telegram (see Chapter 4)

Dimensional Drawing

See Figure 8-4 for the precise dimensions.

8

Figure 8-16 Front Elevation: ET 200B-4AI (6ES7 134-0HF01-0XB0)

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-51

Page 232

Analog Modules

List of Subsections

The following aspects of the ET 200B-4AI are described below: In Section you will find on Page

8.5.1

Connecting transducers

8-53

8.5.2

Configuration options

8-61

8.5.3

Setting the operating mode

8-62

8.5.4

Analog-value representation, operation with SIMATIC S5

8-65

8.5.5

Analog-value representation, operation with SIMATIC S7

8-70

8.5.6

Schematic circuit diagram, terminal assignment and technical data

8-72

8

8-52

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 233

Analog Modules

8.5.1

Connecting Transducers

Possible Connections

You can connect the following to the ET 200B-4AI:

Up to 4 voltage sensors (2-wire connection) Up to 4 current sensors (2-wire connection) Mixed configurations with different types of sensor are possible. 2-wire measuring transducers and 4-wire measuring transducers require a separate voltage supply (see Figures 8-21 and 8-22).

Input Circuit

There are two ways of measuring analog signals from current/voltage sensors:

Floating-ground measurement Ground-referenced measurement You set the input circuit for floating-ground or ground-referenced measurement by means of the coding plugs on the TB8 (one coding plug per channel).

Floating-Ground Measurement

In the case of floating-ground measurement (differential measurement), each signal line has its own signal reference conductor. Differential measurement is required in the following cases:

If the sensors are connected to different potentials and

8

If the different signal sources are physically apart. Note The maximum permissible common mode voltage (VCM) of the differential inputs to analog ground (MA) is + 1 V. The maximum permissible voltage difference between MA and PE must not exceed 75 V DC/60 V AC. Avoid ground loops!

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-53

Page 234

Analog Modules

GroundReferenced Measurement

In the case of ground-referenced measurement, all signal reference conductors in the TB8 are connected to a common reference point (analog ground MA). To avoid ground loops, galvanically isolated and ungrounded signal sources (thermocouples, voltage sources) are required. Note Connect MA to PE( ) to enhance noise immunity in the case of ground-referenced measurement.

On the Following Pages

The following pages contain a connection example for every connection possibility and measuring principle. Please note the following rules.

Rules

Please note the following rules when connecting measured-value sensors to the ET 200B-4AI:

The permissible potential difference at the differential input (x.1<–>x.2, x = 0 to 3) must not exceed +10 V.

The maximum permissible common mode voltage (VCM) between the differential inputs (x.1<–>x.2, x=0 to 3) and analog ground MA is +1 V.

The maximum permissible isolation voltage between analog ground (MA) and PE ( ) or between the reference potential of the supply voltage (M) is 75 V DC/60 V AC.

8

You must short-circuit the connection terminals of unused voltage inputs and connect them to MA (coding plug at position “D” for voltage sensors; position “C” implements the connection to MA for current sensors).

You must short-circuit terminals “K+” and “K–”. For this purpose, set the coding plug to the “C” position. Note Please note the explanation of shielding of analog lines in Sections 3.1 and 3.5.

8-54

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 235

Analog Modules

Connecting Voltage Sensors

Voltage sensors for the following measured value ranges can be connected: " 1.25 V, " 2.5 V, " 5 V, " 10 V Figures 8-17 and 8-18 show the two methods of connecting voltage sensors.

Floating-Ground Measurement

Â

Figure 8-17 shows the 2-wire connection of voltage sensors (floating-ground measurement):

Ä Ä Ä

A x.3 x.1

. .

x.2 x.4 . M. A

A

A

TB8

K+

0.3 0.4

1.3 1.4

MA L+ L+

K–

0.1 0.2

1.1 1.2

MA M M

C

V

. Shield + 24V +

U

–

+

U

–

VCM v"1V Max. 75 V DC/60 V AC PE

Max. 75 V DC/ 60 V AC MA

8

Mexternal

Figure 8-17 Two-Wire Connection of Voltage Sensors to ET 200B-4AI (Floating-Ground Measurement)

Note The maximum permissible common mode voltage (VCM v "1 V) must not be exceeded at any of the differential inputs with reference to MA.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-55

Page 236

Analog Modules

GroundReferenced Measurement

The 2-wire connection of voltage sensors (ground-referenced measurement) is shown below:

Ä Ä Ä

D x.3 x.1 x.2 . M. A . x.4

. .

D

D

TB8

K+

0.3 0.4

1.3 1.4

MA L+ L+

K–

0.1 0.2

1.1 1.2

MA M M

C

V

. Shield + 24V +

U

–

+

U

–

Max. 75 V DC/60 V AC PE

Max. 75 V DC/ 60 V AC MA

Mexternal

Figure 8-18 Two-Wire Connection of Voltage Sensors to ET 200B-4AI (Ground-Referenced Measurement)

8

8-56

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 237

Analog Modules

Connecting Current Sensors

Current sensors for the following measured value ranges can be connected: 0 to 20 mA, 4 to 20 mA, " 20 mA Figures 8-19 and 8-20 show the two methods of connecting current sensors.

Floating-Ground Measurement

Â

The 2-wire connection of current sensors (floating-ground measurement) is shown below:

Ä Ä Ä

B x.3 x.1 .

x.2 x.4 . M. A

B

B

TB8

K+

0.3 0.4

1.3 1.4

MA L+ L+

K–

0.1 0.2

1.1 1.2

MA M M

C mA

. Shield + 24V + mA

–

+ mA –

VCM v"1V Max. 75 V DC/60 V AC PE

Max. 75 V DC/ 60 V AC MA

8

Mexternal

Figure 8-19 Two-Wire Connection of Current Sensors (Floating-Ground Measurement)

Note The maximum permissible common mode voltage (VCM v " 1 V) must not be exceeded at any of the differential inputs with reference to MA.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-57

Page 238

Analog Modules

GroundReferenced Measurement

The 2-wire connection of current sensors (ground-referenced measurement) is shown below:

Ä Ä Ä

C x.3 . x.1 .

x.2 . x.4 . M. A

C

C

TB8

K+

0.3 0.4

1.3 1.4

MA L+ L+

K–

0.1 0.2

1.1 1.2

MA M M

C mA

. Shield + 24V + mA

– mA + –

Max. 75 V DC/60 V AC PE

Max. 75 V DC/ 60 V AC MA

Mexternal

Figure 8-20 Two-Wire Connection of Current Sensors (Ground-Referenced Measurement)

8

8-58

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 239

Analog Modules

Connecting 2-Wire and 4-Wire Measuring Transducers

The 2-wire and 4 -wire measuring transducers receive a separate supply voltage.

2-Wire Measuring Transducers

The figure below shows how to connect the 2-wire measuring transducer as a current sensor:

Â

2-wire measuring transducer converts the incoming measured variable into a current. 4-wire measuring transducers can be used to measure current and voltage.

Ä Ä Ä

B x.2 x.4 . M. A x.3 x.1 .

B

B

TB8

K+

0.3 0.4

1.3 1.4

MA L+ L+

K–

0.1 0.2

1.1 1.2

MA M M

C mA

. Shield M L+

.

.

+ – Meas. transd.

+ 24V

+ – Meas. transd. UCM v"1V

Max. 75 V DC/60 V AC PE

Max. 75 V DC/ 60 V AC MA

8

Mexternal

Figure 8-21 Connection of 2-Wire Measuring Transducer as Current Sensor

Note The maximum permissible common mode voltage of the differential inputs to analog ground MA is (UCM v "1V). Avoid ground loops!

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-59

Page 240

Analog Modules

4-Wire Measuring Transducer

 Â. . . . .

The figure below shows how to connect the 4-wire measuring transducer as a current sensor or voltage sensor:

Ä Ä Ä

B x.2 x.4 MA x.3 x.1

B

B

TB8

K+

0.3 0.4

1.3 1.4

MA L+ L+

K–

0.1 0.2

1.1 1.2

MA M M

C mA

. Shield M L+

. . +Meas. – +Meas. – transd.

+ 24V transd.

UCM v"1V Max. 75 V DC/60 V AC PE

Max. 75 V DC/ 60 V AC MA

Mexternal

Figure 8-22 Connection of 4-Wire Measuring Transducer as Current Sensor or Voltage Sensor

8

Note The maximum permissible common mode voltage of the differential inputs to analog ground MA is (UCM v "1V).

8-60

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c