Page 221
Analog Modules
Measuring Range, Resistance Measurement Table 8-27
The table below shows the assignments of analog to digitized measured values for the resistance measuring ranges: 48 W, 150 W, 300 W and 600 W.
Representation of Digitized Measured Values of the ET 200B-4/8AI for Resistance Measurement
Measuring Range 48 Ω
Measuring Range 150 Ω
Measuring Range 300 Ω
Measuring Range 600 Ω u 56.4427 u 176.3835 u 352.767
56.4427
176.3835
:
Units Decimal Hexadecimal
Range u 705.5339
32767
7FFFH
Overflow
352.767
705.5339
32511
7EFFH
:
:
:
:
:
48.0174
150.0054
300.0109
600.0217
27649
6C01H
48.000
150.000
300.000
600.000
27648
6C00H
36.000
112.500
225.000
450.000
20736
5100H
:
:
:
:
:
:
0.000
0.000
0.000
0.000
0
0H
–32768
8000H
(Negative values physically impossible)
Overrange
Nominal range
Underrun
8
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-41
Page 222
Analog Modules
Measuring Range, Pt 100 Resistance Sensors
The table below shows the assignments of analog to digitized measured values for resistance sensors (Pt 100). Table 8-28
Representation of Digitized Measured Values of the ET 200B-4/8AI for Pt 100 Resistance Sensors
Temperature Range Standard Pt 100 850
Decimal
Hexadecimal
Range w1000.1
32767
7FFFH
Overflow
1000.0
10000
2710H
:
:
:
850.1
8501
2135H
850.0
8500
2134H
:
:
:
–200.0
–2000
F830H
–200.1
–2001
F82FH
:
8
Measuring Range, Ni 100 Resistance Sensors
:
:
–243.0
–2430
F682H v– 243.1
–32768
8000H
Nominal range
Underrange Underrun
The table below shows the assignments of analog to digitized measured values for resistance sensors (Ni 100). Table 8-29
Representation of Digitized Measured Values of the ET 200B-4/8AI for Ni 100 Resistance Sensors
Temperature Range Standard Ni 100 250
Decimal
Hexadecimal
Range w295.1
32767
7FFFH
Overflow
295.0
2950
0B86H
Overrange
:
:
:
250.1
2501
09C5H
250.0
2500
09C4H
:
:
:
–60.0
–600
FDA8H
–60.1
–601
FDA7H
:
8-42
Overrange
:
:
–105.0
–1050
FBE6H v– 105.1
–32768
8000H
Nominal range
Underrange
Underrun
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 223
Analog Modules
Measuring Range, Type E Thermocouples
The table below shows the assignments of analog to digitized measured values for Type E thermocouples. Table 8-30
Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization; Type E Thermocouples
Temperature Range in Type E
Decimal
Hexadecimal
Range w1200.1
32767
7FFFH
Overflow
1200.0
12000
2EE0H
:
:
:
1000.1
10001
2711H
1000.0
10000
2710H
:
:
–270.0
–2700
F574H v–270.1
–2701
F573H
:
Overrange
Nominal range Underrange
If wiring is incorrect or a sensor error in the negative range occurs, the analog-input module signals underrun when F0C4H is undershot and outputs 8000H.
Measuring Range, Type J Thermocouples
The table below shows the assignments of analog to digitized measured values for Type J thermocouples. Table 8-31
Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization; Type J Thermocouples
Temperature Range in Type J
Decimal
Hexadecimal
Range w1450.1
32767
7FFFH
Overflow
1450.0
14500
38A4H
:
:
1200.1
12001
2EE1H
1200.0
12000
2EE0H
:
:
–210.0
–2100
F7CCH v–210.1
–2101
F7CBH
:
:
Overrange
Nominal range Underrange
If wiring is incorrect or a sensor error in the negative range occurs, the analog-input module signals underrun when F3C1H is undershot and outputs 8000H.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-43
8
Page 224
Analog Modules
Measuring Range, Type K Thermocouples
The table below shows the assignments of analog to digitized measured values for Type K thermocouples. Table 8-32
Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization; Type K Thermocouples
Temperature Range in Type K
Decimal
Hexadecimal
Range w1622.1
32767
7FFFH
Overflow
1622.0
16220
3F5CH
:
:
:
1372.1
13721
3599H
1372.0
13720
3598H
:
:
–270.0
–2700
F574H v–270.1
–2701
F573H
:
Overrange
Nominal range Underrange
If wiring is incorrect or a sensor error in the negative range occurs, the analog-input module signals underrun when F0C4H is undershot and outputs 8000H.
Measuring Range, Type L Thermocouples
The table below shows the assignments of analog to digitized measured values for Type L thermocouples. Table 8-33
8
Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization; Type L Thermocouples
Temperature Range in Type L
Decimal
Hexadecimal
Range w1150.1
32767
7FFFH
Overflow
1150.0
11500
2CECH
:
:
900.1
9001
2329H
900.0
9000
2328H
:
:
–200.0
–2000
F830H v–200.1
–2001
F82FH
:
:
Overrange
Nominal range Underrange
If wiring is incorrect or a sensor error in the negative range occurs, the analog-input module signals underrun when F380H is undershot and outputs 8000H.
8-44
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 225
Analog Modules
Measuring Range, Type N Thermocouples
The table below shows the assignments of analog to digitized measured values for Type N thermocouples. Table 8-34
Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization; Type N Thermocouples
Temperature Range in Type N
Decimal
Hexadecimal
Range w1550.1
32767
7FFFH
Overflow
1550.0
15500
3C8CH
:
:
:
1300.1
13001
32C9H
1300.0
13000
32C8H
:
:
–270.0
–2700
F574H v–270.1
–2701
F573H
:
Overrange
Nominal range Underrange
If wiring is incorrect or a sensor error in the negative range occurs, the analog-input module signals underrun when F0C4H is undershot and outputs 8000H.
Measuring Range, Type T Thermocouples
The table below shows the assignments of analog to digitized measured values for Type T thermocouples. Table 8-35
Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization; Type T Thermocouples
Temperature Range in Type T
Decimal
Hexadecimal
Range w540.1
32767
7FFFH
Overflow
540.0
5400
1518H
:
:
400.1
4001
0FA1H
400.0
4000
0FA0H
:
:
270.0
–2700
F574H v–270.1
–2701
F573H
:
:
Overrange
Nominal range Underrange
If wiring is incorrect or a sensor error in the negative range occurs, the analog-input module signals underrun when F0C4H is undershot and outputs 8000H.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-45
8
Page 226
Analog Modules
Measuring Range, Type U Thermocouples
The table below shows the assignments of analog to digitized measured values for Type U thermocouples. Table 8-36
Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization; Type U Thermocouples
Temperature Range in Type U
Decimal
Hexadecimal
Range w850.1
32767
7FFFH
Overflow
850.0
8500
2134H
:
:
:
600.1
6001
1771H
600.0
6000
1770H
:
:
200.0
–2000
F830H v–200.1
–2001
F82FH
:
Overrange
Nominal range Underrange
If wiring is incorrect or a sensor error in the negative range occurs, the analog-input module signals underrun when F380H is undershot and outputs 8000H.
8
8-46
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 227
Analog Modules
8.4.6
Block Diagram, Terminal Assignment and Technical Data
Block Diagram
Simplified representation of potential for the ET 200B-4/8AI and TB8:
ET 200B-4/8AI PROFIBUS-DP
24 V 5V 5V –5 V M
Logic P
N
9x MA K+; x.1/x.3 K–; x.2/x.4 Interface between electronics block and terminal block
X1
M
L+
Station number selection
Analog TB8
Suppr. logic STOP/RUN switch
Coding panels Connection PROFIBUS -DP
PE
Compensating box
K+
0.3 0.4
1.3 1.4
2.3 2.4
3.3 3.4
MA L+ L+
K-
0.1 0.2
1.1 1.2
2.1 2.2
3.1 3.2
MA M M
8
Chnl. gp. 0: Chnl. gp. 1: Chnl. gp. 2: Chnl. gp. 3: Analog 24 V 0.1/0.2 1.1/1.2 2.1/2.2 3.1/3.2 ground supply 0.3/0.4 1.3/1.4 2.3/2.4 3.3/3.4
Figure 8-15 Block Diagram: ET 200B-4/8AI (6ES7 134-0KH01-0XB0) and TB8
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-47
Page 228
Analog Modules
Terminal Assignment
The table below contains the terminal assignments of the TB8 for ET 200B-4/8AI, depending on the sensor connected. Table 8-37
Terminal Assignment of the TB8 for ET 200B-4/8AI (6ES7 134-0KH01-0XB0)
Terminal numbering TB8
Terminal
Thermocouple
Resistance Thermometer
Voltage Sensor
Compensating box
Unassigned
Unassigned
K–
Compensating box
Unassigned
Unassigned x.1
Measuring line (+)
Constant current line IC+
Measuring line (+)
x.2
Measuring line (–)
Constant current line IC–
Measuring line (–)
x.3
Measuring line (+)
Measuring line (+)
Measuring line (+)
x.4
Measuring line (–)
Measuring line (–)
Measuring line (–)
K+
8
Assignment When the Following are Connected
MA
Analog ground (MA)
MA
Analog ground (MA)
L+
Voltage supply, internal logic
L+
Voltage supply, internal logic
M
Voltage supply, internal logic
M
Voltage supply, internal logic x = 0, 1, 2, 3
Note Certain additional settings must be made for the input circuit by means of the coding plugs of the TB8. The settings of the coding plugs are illustrated in Figures 8-6 to 8-14.
8-48
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 229
Analog Modules
Technical Data
The technical data of the ET 200B-4/8AI electronics block are listed in the table below.
Technical specifications
Inputs
Baud rates*
9.6/19.2/93.75/187.5/50 0/1500/3000/6000/ 12000 kbaud
Bus protocol
PROFIBUS-DP
Galvanic isolation to the SINEC L2-DP bus
Yes
Power losses
Typically 2 W
Weight (EB and TB)
Approx. 550 g (19.25 oz.)
Dimensions (EB and TB: W x H x D)
160 x 130 x 60
Number of inputs
Galvanic isolation to internal No electronics Galvanic isolation to voltage supply of internal logic
Green ”RUN” LED
Bus monitoring, SINEC L2-DP
Red ”BF” LED
Group diagnostics
Red ”DIA” LED, parameterizable
Alarms Limit-value alarm
Diagnostics alarm End-of-cycle alarm
Yes, parameterizable channels 0 and 2 Yes, parameterizable Yes, parameterizable
Supply voltage for inputs and internal logic Supply voltage (L+) Rated value Permissible range Value for t < 0.5 s
24 V DC 18.5 ... 30.2 V 35 V
Current consumption from L+ Logic
80 mA
*
In operation with the IM 308-B, the maximum possible baud rate is 1500 kbaud.
Types E, J, K, L, N, T, U 48 W 150 W 300 W 600 W Resistance thermometers Pt 100, Ni 100 Voltage " 80 mV " 250 mV " 500 mV " 1000 mV
Permissible input voltage for 32 V voltage input (destruction limit) Characteristic-curve linearization for thermocouples for thermal resistors Linearization accuracy in nominal range for thermocouples
Types E, J, K, L, N, T, U Pt 100 (standard range) Ni 100 (standard range) "1°C
Connection of signal sensors For voltage measurement Possible For resistance measurement: Possible 2-wire connection Possible 4-wire connection Input resistance Measured value representation SIMATIC S5
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Yes
Measured value ranges Thermocouples Resistors
Diagnostics functions, alarms Voltage monitoring
8 voltage inputs or 4 inputs for resistance thermometers and resistors or 8 inputs for thermocouples w10 MW
SIMATIC S7
12-bit complement of twos or 11-bit amount with sign (selectable) Max. 14-bit complement of twos (depends on integration time)
Overrange
Approx. 17.5 %
8-49
8
Page 230
Analog Modules
Inputs (continued) Measuring principle
Inputs (continued) Crosstalk between inputs
Integrating
S At 50 Hz S At 60 Hz
Integration/conversion time/ resolution (per channel)
S Parameterizable S Integration time in ms S Basic conversion time
Yes 2.5
16.7
20
100
8
35
42
200 incl. integration time and offset measuring time in ms or Additional conversion 10 time for wire-break monitoring in ms
S Resolution in bits (incl. overrange)
9+ SI
S Noise suppression for in- 400
10
10
10
12+ 12+ SI SI
14+ SI
60
10
50 terference frequency f1 in Hz Permissible potential difference S Across inputs S Inputs to MA (UCM) S MA to PE or M
8
Max. "1 V Max. "1 V Max. 75 V DC/60 V AC
Error message in the event of S Range overshoot (over- Yes range) S Wire break of signal-sen- Yes, for Pt 100, Ni 100, sor lines R, " 80 mV, Type E, J, K, L, N, T, U thermocouples (parameterizable) Noise suppression for f=n (f1"1 %), (f1 = interference frequency) S Common-mode interfer- > 70 dB ence (USS t3 V)
50 dB 50 dB
Working error limit (over entire temperature range, in relation to input range)
S S S S S
80 mV
"1%
From 250 to 1000 mV
" 0.6 %
Thermocouples
" 10 K
Thermal resistors
"5K
Resistors
"1%
Basic error limit (working error limit at 25 _C, in relation to input range)
S S S S S
80 mV
" 0.6 %
From 250 to 1000 mV
" 0.4 %
Thermocouples
"7K
Thermal resistors
"3K
Resistors
" 0.6 %
Temperature error (in relation " 0.005 %/K to input range) Linearity error (in relation to " 0.05 % input range) Repeatability (in steady-state " 0.05 % condition at 25 _C, in relation to input range) Cable length S Shielded
Max. 100 m
S Series-mode interference > 40 dB (peak value of interference < rated value of input range)
8-50