SIMATIC ET 200B Distributed I/O Station Manual: 8 Analog Modules, pages 221 to 230

Pages 221 to 230 of 344, from SIMATIC ET 200B Distributed I/O Station Manual

The original document is the PDF (2.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Siemens ET 200B

Page 221

Analog Modules

Measuring Range, Resistance Measurement Table 8-27

The table below shows the assignments of analog to digitized measured values for the resistance measuring ranges: 48 W, 150 W, 300 W and 600 W.

Representation of Digitized Measured Values of the ET 200B-4/8AI for Resistance Measurement

Measuring Range 48 Ω

Measuring Range 150 Ω

Measuring Range 300 Ω

Measuring Range 600 Ω u 56.4427 u 176.3835 u 352.767

56.4427

176.3835

:

Units Decimal Hexadecimal

Range u 705.5339

32767

7FFFH

Overflow

352.767

705.5339

32511

7EFFH

:

:

:

:

:

48.0174

150.0054

300.0109

600.0217

27649

6C01H

48.000

150.000

300.000

600.000

27648

6C00H

36.000

112.500

225.000

450.000

20736

5100H

:

:

:

:

:

:

0.000

0.000

0.000

0.000

0

0H

–32768

8000H

(Negative values physically impossible)

Overrange

Nominal range

Underrun

8

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-41

Page 222

Analog Modules

Measuring Range, Pt 100 Resistance Sensors

The table below shows the assignments of analog to digitized measured values for resistance sensors (Pt 100). Table 8-28

Representation of Digitized Measured Values of the ET 200B-4/8AI for Pt 100 Resistance Sensors

Temperature Range Standard Pt 100 850

Decimal

Hexadecimal

Range w1000.1

32767

7FFFH

Overflow

1000.0

10000

2710H

:

:

:

850.1

8501

2135H

850.0

8500

2134H

:

:

:

–200.0

–2000

F830H

–200.1

–2001

F82FH

:

8

Measuring Range, Ni 100 Resistance Sensors

:

:

–243.0

–2430

F682H v– 243.1

–32768

8000H

Nominal range

Underrange Underrun

The table below shows the assignments of analog to digitized measured values for resistance sensors (Ni 100). Table 8-29

Representation of Digitized Measured Values of the ET 200B-4/8AI for Ni 100 Resistance Sensors

Temperature Range Standard Ni 100 250

Decimal

Hexadecimal

Range w295.1

32767

7FFFH

Overflow

295.0

2950

0B86H

Overrange

:

:

:

250.1

2501

09C5H

250.0

2500

09C4H

:

:

:

–60.0

–600

FDA8H

–60.1

–601

FDA7H

:

8-42

Overrange

:

:

–105.0

–1050

FBE6H v– 105.1

–32768

8000H

Nominal range

Underrange

Underrun

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 223

Analog Modules

Measuring Range, Type E Thermocouples

The table below shows the assignments of analog to digitized measured values for Type E thermocouples. Table 8-30

Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization; Type E Thermocouples

Temperature Range in Type E

Decimal

Hexadecimal

Range w1200.1

32767

7FFFH

Overflow

1200.0

12000

2EE0H

:

:

:

1000.1

10001

2711H

1000.0

10000

2710H

:

:

–270.0

–2700

F574H v–270.1

–2701

F573H

:

Overrange

Nominal range Underrange

If wiring is incorrect or a sensor error in the negative range occurs, the analog-input module signals underrun when F0C4H is undershot and outputs 8000H.

Measuring Range, Type J Thermocouples

The table below shows the assignments of analog to digitized measured values for Type J thermocouples. Table 8-31

Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization; Type J Thermocouples

Temperature Range in Type J

Decimal

Hexadecimal

Range w1450.1

32767

7FFFH

Overflow

1450.0

14500

38A4H

:

:

1200.1

12001

2EE1H

1200.0

12000

2EE0H

:

:

–210.0

–2100

F7CCH v–210.1

–2101

F7CBH

:

:

Overrange

Nominal range Underrange

If wiring is incorrect or a sensor error in the negative range occurs, the analog-input module signals underrun when F3C1H is undershot and outputs 8000H.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-43

8

Page 224

Analog Modules

Measuring Range, Type K Thermocouples

The table below shows the assignments of analog to digitized measured values for Type K thermocouples. Table 8-32

Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization; Type K Thermocouples

Temperature Range in Type K

Decimal

Hexadecimal

Range w1622.1

32767

7FFFH

Overflow

1622.0

16220

3F5CH

:

:

:

1372.1

13721

3599H

1372.0

13720

3598H

:

:

–270.0

–2700

F574H v–270.1

–2701

F573H

:

Overrange

Nominal range Underrange

If wiring is incorrect or a sensor error in the negative range occurs, the analog-input module signals underrun when F0C4H is undershot and outputs 8000H.

Measuring Range, Type L Thermocouples

The table below shows the assignments of analog to digitized measured values for Type L thermocouples. Table 8-33

8

Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization; Type L Thermocouples

Temperature Range in Type L

Decimal

Hexadecimal

Range w1150.1

32767

7FFFH

Overflow

1150.0

11500

2CECH

:

:

900.1

9001

2329H

900.0

9000

2328H

:

:

–200.0

–2000

F830H v–200.1

–2001

F82FH

:

:

Overrange

Nominal range Underrange

If wiring is incorrect or a sensor error in the negative range occurs, the analog-input module signals underrun when F380H is undershot and outputs 8000H.

8-44

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 225

Analog Modules

Measuring Range, Type N Thermocouples

The table below shows the assignments of analog to digitized measured values for Type N thermocouples. Table 8-34

Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization; Type N Thermocouples

Temperature Range in Type N

Decimal

Hexadecimal

Range w1550.1

32767

7FFFH

Overflow

1550.0

15500

3C8CH

:

:

:

1300.1

13001

32C9H

1300.0

13000

32C8H

:

:

–270.0

–2700

F574H v–270.1

–2701

F573H

:

Overrange

Nominal range Underrange

If wiring is incorrect or a sensor error in the negative range occurs, the analog-input module signals underrun when F0C4H is undershot and outputs 8000H.

Measuring Range, Type T Thermocouples

The table below shows the assignments of analog to digitized measured values for Type T thermocouples. Table 8-35

Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization; Type T Thermocouples

Temperature Range in Type T

Decimal

Hexadecimal

Range w540.1

32767

7FFFH

Overflow

540.0

5400

1518H

:

:

400.1

4001

0FA1H

400.0

4000

0FA0H

:

:

270.0

–2700

F574H v–270.1

–2701

F573H

:

:

Overrange

Nominal range Underrange

If wiring is incorrect or a sensor error in the negative range occurs, the analog-input module signals underrun when F0C4H is undershot and outputs 8000H.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-45

8

Page 226

Analog Modules

Measuring Range, Type U Thermocouples

The table below shows the assignments of analog to digitized measured values for Type U thermocouples. Table 8-36

Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization; Type U Thermocouples

Temperature Range in Type U

Decimal

Hexadecimal

Range w850.1

32767

7FFFH

Overflow

850.0

8500

2134H

:

:

:

600.1

6001

1771H

600.0

6000

1770H

:

:

200.0

–2000

F830H v–200.1

–2001

F82FH

:

Overrange

Nominal range Underrange

If wiring is incorrect or a sensor error in the negative range occurs, the analog-input module signals underrun when F380H is undershot and outputs 8000H.

8

8-46

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 227

Analog Modules

8.4.6

Block Diagram, Terminal Assignment and Technical Data

Block Diagram

Simplified representation of potential for the ET 200B-4/8AI and TB8:

ET 200B-4/8AI PROFIBUS-DP

24 V 5V 5V –5 V M

Logic P

N

9x MA K+; x.1/x.3 K–; x.2/x.4 Interface between electronics block and terminal block

X1

M

L+

Station number selection

Analog TB8

Suppr. logic STOP/RUN switch

Coding panels Connection PROFIBUS -DP

PE

Compensating box

K+

0.3 0.4

1.3 1.4

2.3 2.4

3.3 3.4

MA L+ L+

K-

0.1 0.2

1.1 1.2

2.1 2.2

3.1 3.2

MA M M

8

Chnl. gp. 0: Chnl. gp. 1: Chnl. gp. 2: Chnl. gp. 3: Analog 24 V 0.1/0.2 1.1/1.2 2.1/2.2 3.1/3.2 ground supply 0.3/0.4 1.3/1.4 2.3/2.4 3.3/3.4

Figure 8-15 Block Diagram: ET 200B-4/8AI (6ES7 134-0KH01-0XB0) and TB8

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-47

Page 228

Analog Modules

Terminal Assignment

The table below contains the terminal assignments of the TB8 for ET 200B-4/8AI, depending on the sensor connected. Table 8-37

Terminal Assignment of the TB8 for ET 200B-4/8AI (6ES7 134-0KH01-0XB0)

Terminal numbering TB8

Terminal

Thermocouple

Resistance Thermometer

Voltage Sensor

Compensating box

Unassigned

Unassigned

K–

Compensating box

Unassigned

Unassigned x.1

Measuring line (+)

Constant current line IC+

Measuring line (+)

x.2

Measuring line (–)

Constant current line IC–

Measuring line (–)

x.3

Measuring line (+)

Measuring line (+)

Measuring line (+)

x.4

Measuring line (–)

Measuring line (–)

Measuring line (–)

K+

8

Assignment When the Following are Connected

MA

Analog ground (MA)

MA

Analog ground (MA)

L+

Voltage supply, internal logic

L+

Voltage supply, internal logic

M

Voltage supply, internal logic

M

Voltage supply, internal logic x = 0, 1, 2, 3

Note Certain additional settings must be made for the input circuit by means of the coding plugs of the TB8. The settings of the coding plugs are illustrated in Figures 8-6 to 8-14.

8-48

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 229

Analog Modules

Technical Data

The technical data of the ET 200B-4/8AI electronics block are listed in the table below.

Technical specifications

Inputs

Baud rates*

9.6/19.2/93.75/187.5/50 0/1500/3000/6000/ 12000 kbaud

Bus protocol

PROFIBUS-DP

Galvanic isolation to the SINEC L2-DP bus

Yes

Power losses

Typically 2 W

Weight (EB and TB)

Approx. 550 g (19.25 oz.)

Dimensions (EB and TB: W x H x D)

160 x 130 x 60

Number of inputs

Galvanic isolation to internal No electronics Galvanic isolation to voltage supply of internal logic

Green ”RUN” LED

Bus monitoring, SINEC L2-DP

Red ”BF” LED

Group diagnostics

Red ”DIA” LED, parameterizable

Alarms Limit-value alarm

Diagnostics alarm End-of-cycle alarm

Yes, parameterizable channels 0 and 2 Yes, parameterizable Yes, parameterizable

Supply voltage for inputs and internal logic Supply voltage (L+) Rated value Permissible range Value for t < 0.5 s

24 V DC 18.5 ... 30.2 V 35 V

Current consumption from L+ Logic

80 mA

*

In operation with the IM 308-B, the maximum possible baud rate is 1500 kbaud.

Types E, J, K, L, N, T, U 48 W 150 W 300 W 600 W Resistance thermometers Pt 100, Ni 100 Voltage " 80 mV " 250 mV " 500 mV " 1000 mV

Permissible input voltage for 32 V voltage input (destruction limit) Characteristic-curve linearization for thermocouples for thermal resistors Linearization accuracy in nominal range for thermocouples

Types E, J, K, L, N, T, U Pt 100 (standard range) Ni 100 (standard range) "1°C

Connection of signal sensors For voltage measurement Possible For resistance measurement: Possible 2-wire connection Possible 4-wire connection Input resistance Measured value representation SIMATIC S5

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Yes

Measured value ranges Thermocouples Resistors

Diagnostics functions, alarms Voltage monitoring

8 voltage inputs or 4 inputs for resistance thermometers and resistors or 8 inputs for thermocouples w10 MW

SIMATIC S7

12-bit complement of twos or 11-bit amount with sign (selectable) Max. 14-bit complement of twos (depends on integration time)

Overrange

Approx. 17.5 %

8-49

8

Page 230

Analog Modules

Inputs (continued) Measuring principle

Inputs (continued) Crosstalk between inputs

Integrating

S At 50 Hz S At 60 Hz

Integration/conversion time/ resolution (per channel)

S Parameterizable S Integration time in ms S Basic conversion time

Yes 2.5

16.7

20

100

8

35

42

200 incl. integration time and offset measuring time in ms or Additional conversion 10 time for wire-break monitoring in ms

S Resolution in bits (incl. overrange)

9+ SI

S Noise suppression for in- 400

10

10

10

12+ 12+ SI SI

14+ SI

60

10

50 terference frequency f1 in Hz Permissible potential difference S Across inputs S Inputs to MA (UCM) S MA to PE or M

8

Max. "1 V Max. "1 V Max. 75 V DC/60 V AC

Error message in the event of S Range overshoot (over- Yes range) S Wire break of signal-sen- Yes, for Pt 100, Ni 100, sor lines R, " 80 mV, Type E, J, K, L, N, T, U thermocouples (parameterizable) Noise suppression for f=n (f1"1 %), (f1 = interference frequency) S Common-mode interfer- > 70 dB ence (USS t3 V)

50 dB 50 dB

Working error limit (over entire temperature range, in relation to input range)

S S S S S

80 mV

"1%

From 250 to 1000 mV

" 0.6 %

Thermocouples

" 10 K

Thermal resistors

"5K

Resistors

"1%

Basic error limit (working error limit at 25 _C, in relation to input range)

S S S S S

80 mV

" 0.6 %

From 250 to 1000 mV

" 0.4 %

Thermocouples

"7K

Thermal resistors

"3K

Resistors

" 0.6 %

Temperature error (in relation " 0.005 %/K to input range) Linearity error (in relation to " 0.05 % input range) Repeatability (in steady-state " 0.05 % condition at 25 _C, in relation to input range) Cable length S Shielded

Max. 100 m

S Series-mode interference > 40 dB (peak value of interference < rated value of input range)

8-50

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c