Page 211

Analog Modules

Measuring Range, Ni 100 Resistance Sensors Table 8-16

Units

The table below shows the assignments of analog to digitized measured values for resistance sensors (Ni 100):

Representation of Digitized Measured Values of the ET 200B-4/8AI for Ni 100 Resistance Sensors (Complement of Twos) Resistance in W

Digitized Measured Value 15 14 13 12 11 10 9 8 7 6 5 4 3

X F OV 2 1

0

> 590

> 295

0 0 0 1 0 0 1 0 0 1 1 1 0 0 0

1

590

295

0 0 0 1 0 0 1 0 0 1 1 1 0 0 0

1

:

:

:

502

251

0 0 0 0 1 1 1 1 1 0 1 1 0 0 0

1

Range

Overflow Overrange1

500

289.2

250

0 0 0 0 1 1 1 1 1 0 1 0 0 0 0

0

498

288.1

249

0 0 0 0 1 1 1 1 1 0 0 1 0 0 0

0

400

240.7

200

0 0 0 0 1 1 0 0 1 0 0 0 0 0 0

0

200

161.8

100

0 0 0 0 0 1 1 0 0 1 0 0 0 0 0

0

2

100.5

1

0 0 0 0 0 0 0 0 0 0 0 1 0 0 0

0

0

100

0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0

–2

99.5

–1

1 1 1 1 1 1 1 1 1 1 1 1 0 0 0

0

–20

94.6

–10

1 1 1 1 1 1 1 1 0 1 1 0 0 0 0

0

–80

79.1

–40

1 1 1 1 1 1 0 1 1 0 0 0 0 0 0

0

–118

70

–59

1 1 1 1 1 1 0 0 0 1 0 1 0 0 0

0

–120

69.5

–60

1 1 1 1 1 1 0 0 0 1 0 0 0 0 0

0

–61

1 1 1 1 1 1 0 0 0 0 1 1 0 0 0

1

–122

1

Temperature in °C

Nominal range

8 Overrange1

:

:

:

–210

–105

1 1 1 1 1 0 0 1 0 1 1 1 0 0 0

1

< –210

< –105

1 1 1 1 1 0 0 1 0 1 1 1 0 0 0

1

Overflow

X

X

X X X X X X X X X X X X X 0 1

0

Wire break

In the overrange, any rise in the characteristic curve is retained when the linearized nominal range is exited.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-31

Page 212

Analog Modules

Measuring Range, Type E Thermocouples Table 8-17

Units

The table below shows the assignments of analog to digitized measured values for Type E thermocouples.

Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization; Type E Thermocouples (Nickel-Chrome/Copper-Nickel, to IEC 548, Part 1; Complement of Twos) Thermal e. m. f. in mV1

Temperature in °C

8

0

1001

0 0 0 1 1 1 1 1 0 1 0 0 1 0 0

1

1

Range

Overflow Overrange2

1000

76.358

1000

0 0 0 1 1 1 1 1 0 1 0 0 0 0 0

0

800

61.022

800

0 0 0 1 1 0 0 1 0 0 0 0 0 0 0

0

400

28.943

400

0 0 0 0 1 1 0 0 1 0 0 0 0 0 0

0

100

6.317

100

0 0 0 0 0 0 1 1 0 0 1 0 0 0 0

0

1

0.059

1

0 0 0 0 0 0 0 0 0 0 0 0 1 0 0

0

0

0

0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0

–1

–0.059

–1

1 1 1 1 1 1 1 1 1 1 1 1 1 0 0

0

–100

–5.237

–100

1 1 1 1 1 1 0 0 1 1 1 0 0 0 0

0

–200

–8.824

–200

1 1 1 1 1 0 0 1 1 1 0 0 0 0 0

0

–269

–9.833

–269

1 1 1 1 0 1 1 1 1 0 0 1 1 0 0

0

–270

–9.835

–270

1 1 1 1 0 1 1 1 1 0 0 1 0 0 0

0

–271

1 1 1 1 0 1 1 1 1 0 0 0 1 0 0

1

1 1 1 1 0 1 1 1 0 1 1 1 1 0 0

1

Overflow

X X X X X X X X X X X X X 0 1

0

Wire break

–271

–273 X 1 2

X F OV

15 14 13 12 11 10 9 8 7 6 5 4 2 1 3 0 0 1 0 0 1 0 1 1 0 0 0 0 0 0

> 1200

1001

Digitized Measured Value

X

Nominal range

Overrange2 for a reference temperature 0 °C In the overrange, any rise in the characteristic curve is retained when the linearized nominal range is exited.

8-32

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 213

Analog Modules

Measuring Range, Type J Thermocouples Table 8-18

Units

The table below shows the assignments of analog to digitized measured values for Type J thermocouples.

Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization: Type J Thermocouple (Iron/Copper-Nickel (Constantan), to IEC 584) (Complement of Twos) Thermal e. m. f. in mV1

Temperature in °C

Digitized Measured Value 15 14 13 12 11 10 9 8

1485

7 6

5 4 3

X F OV 2 1

0

0 0 1 0 1 1 1 0 0 1 1 0 1 0 0

1

Range

Overflow Overrange2

1201

1201

0 0 1 0 0 1 0 1 1 0 0 0 1 0 0

1

1200

69.536

1200

0 0 1 0 0 1 0 1 1 0 0 0 0 0 0

0

1000

57.942

1000

0 0 0 1 1 1 1 1 0 1 0 0 0 0 0

0

500

27.388

500

0 0 0 0 1 1 1 1 1 0 1 0 0 0 0

0

100

5.268

100

0 0 0 0 0 0 1 1 0 0 1 0 0 0 0

0

1

0.05

1

0 0 0 0 0 0 0 0 0 0 0 0 1 0 0

0

0

0

0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0

–1

–0.05

–1

1 1 1 1 1 1 1 1 1 1 1 1 1 0 0

0

–100

–4.632

–100

1 1 1 1 1 1 0 0 1 1 1 0 0 0 0

0

–150

–6.499

–150

1 1 1 1 1 0 1 1 0 1 0 1 0 0 0

0

–199

–7.868

–199

1 1 1 1 1 0 0 1 1 1 0 0 1 0 0

0

–200

–7.890

–200

1 1 1 1 1 0 0 1 1 1 0 0 0 0 0

0

–201

1 1 1 1 1 0 0 1 1 0 1 1 1 0 0

1

Overrange2

1 1 1 1 0 1 1 1 0 1 1 1 1 0 0

1

Overflow

X X X X X X X X X X X X X 0 1

0

Wire break

–201

–273 X 1 2

X

Nominal range

For a reference temperature of 0 °C (32 °F) In the overrange, any rise in the characteristic curve is retained when the linearized nominal range is exited.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-33

8

Page 214

Analog Modules

Measuring Range, Type K Thermocouples Table 8-19

Units

The table below shows the assignments of analog to digitized measured values for Type K thermocouples.

Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization: Type K Thermocouples (Nickel-Chrome/Nickel-Aluminum, to IEC 584) (Complement of Twos) Thermal e. m. f. in mV1

Temperature in °C

Digitized Measured Value 15 14 13 12 11 10 9 8

> 2359

7 6

5 4 3

X F OV 2 1

0

0 1 0 0 1 0 0 1 1 0 1 1 1 0 0

1

Range

Overflow Overrange2

1370

8

1370

0 0 1 0 1 0 1 0 1 1 0 1 0 0 0

1

1369

54.773

1369

0 0 1 0 1 0 1 0 1 1 0 0 1 0 0

0

1000

41.269

1000

0 0 0 1 1 1 1 1 0 1 0 0 0 0 0

0

500

20.640

500

0 0 0 0 1 1 1 1 1 0 1 0 0 0 0

0

150

6.137

150

0 0 0 0 0 1 0 0 1 0 1 1 0 0 0

0

100

4.095

100

0 0 0 0 0 0 1 1 0 0 1 0 0 0 0

0

1

0.039

1

0 0 0 0 0 0 0 0 0 0 0 0 1 0 0

0

0

0

0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0

–1

–0.039

–1

1 1 1 1 1 1 1 1 1 1 1 1 1 0 0

0

–100

–3.553

–100

1 1 1 1 1 1 0 0 1 1 1 0 0 0 0

0

–101

–3.584

–101

1 1 1 1 1 1 0 0 1 1 0 1 1 0 0

0

Accuracy

–150

–4.912

–150

1 1 1 1 1 0 1 1 0 1 0 1 0 0 0

0 v2K

–200

–5.891

–200

1 1 1 1 1 0 0 1 1 1 0 0 0 0 0

0

–201

1 1 1 1 1 0 0 1 1 0 1 1 1 0 0

1

Overrange2

1 1 1 1 0 1 1 1 0 1 1 1 1 0 0

1

Overflow

X X X X X X X X X X X X X 0 1

0

Wire break

–201

–273 X 1 2

X

Nominal range

For a reference temperature of 0 °C (32 °F) In the overrange, any rise in the characteristic curve is retained when the linearized nominal range is exited.

8-34

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 215

Analog Modules

Measuring Range, Type L Thermocouples Table 8-20

Units

The table below shows the assignments of analog to digitized measured values for Type L thermocouples.

Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization: Type L Thermocouples (Iron/Copper-Nickel (Constantan), to DIN 43710) (Complement of Twos) Thermal e. m. f. in mV1

Temperature in °C

Digitized Measured Value 15 14 13 12 11 10 9 8

1361

7 6

5 4 3

X F OV 2 1

0

0 0 1 0 1 0 1 0 1 0 0 0 1 0 0

1

Range

Overflow Overrange2

901

901

0 0 0 1 1 1 0 0 0 0 1 0 1 0 0

1

900

53.14

900

0 0 0 1 1 1 0 0 0 0 1 0 0 0 0

0

500

27.85

500

0 0 0 0 1 1 1 1 1 0 1 0 0 0 0

0

250

13.75

250

0 0 0 0 0 1 1 1 1 1 0 1 0 0 0

0

100

+5.37

100

0 0 0 0 0 0 1 1 0 0 1 0 0 0 0

0

1

0.05

1

0 0 0 0 0 0 0 0 0 0 0 0 1 0 0

0

0

0

0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0

–1

–0.05

–1

1 1 1 1 1 1 1 1 1 1 1 1 1 0 0

0

–100

–4.75

–100

1 1 1 1 1 1 0 0 1 1 1 0 0 0 0

0

–150

–6.60

–150

1 1 1 1 1 0 1 1 0 1 0 1 0 0 0

0

–190

–7.86

–190

1 1 1 1 1 0 1 0 0 0 0 1 0 0 0

0

–199

–8.12

–199

1 1 1 1 1 0 0 1 1 1 0 0 1 0 0

0

–200

1 1 1 1 1 0 0 1 1 1 0 0 0 0 0

1

Overrange2

1 1 1 1 0 1 1 1 0 1 1 1 1 0 0

1

Overflow

X X X X X X X X X X X X X 0 1

0

Wire break

–200

–273 X 1 2

X

Nominal range

For a reference temperature of 0 °C (32 °F) In the overrange, any rise in the characteristic curve is retained when the linearized nominal range is exited.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-35

8

Page 216

Analog Modules

Measuring Range, Type N Thermocouples Table 8-21

Units

The table below shows the assignments of analog to digitized measured values for Type N thermocouples.

Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization; Type N Thermocouples (Nickel-Chrome-Silicium/Nickel-Silicium, to IEC 548-1; Complement of Twos) Thermal e. m. f. in mV1

Temperature in °C

8

0

1301

0 0 1 0 1 0 0 0 1 0 1 0 1 0 0

1

1

Range

Overflow Overrange2

1300

47.502

1300

0 0 1 0 1 0 0 0 1 0 1 0 0 0 0

0

1000

36.248

1000

0 0 0 1 1 1 1 1 0 1 0 0 0 0 0

0

500

16.744

500

0 0 0 0 1 1 1 1 1 0 1 0 0 0 0

0

100

2.774

100

0 0 0 0 0 0 1 1 0 0 1 0 0 0 0

0

1

0.026

1

0 0 0 0 0 0 0 0 0 0 0 0 1 0 0

0

0

0

0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0

–1

–0.026

–1

1 1 1 1 1 1 1 1 1 1 1 1 1 0 0

0

–100

–2.407

–100

1 1 1 1 1 1 0 0 1 1 1 0 0 0 0

0

–250

–4.313

–250

1 1 1 1 1 0 0 0 0 0 1 1 0 0 0

0

–269

–4.345

–269

1 1 1 1 0 1 1 1 1 0 0 1 1 0 0

0

–270

–4.345

–270

1 1 1 1 0 1 1 1 1 0 0 1 0 0 0

0

–271

1 1 1 1 0 1 1 1 1 0 0 0 1 0 0

1

1 1 1 1 0 1 1 1 0 1 1 1 1 0 0

1

Overflow

X X X X X X X X X X X X X 0 1

0

Wire break

–271

–273 X 1 2

X F OV

15 14 13 12 11 10 9 8 7 6 5 4 2 1 3 0 0 1 1 0 0 0 0 0 1 1 1 0 0 0

> 1550

1301

Digitized Measured Value

X

Nominal range

Overrange2 for a reference temperature 0 °C In the overrange, any rise in the characteristic curve is retained when the linearized nominal range is exited.

8-36

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 217

Analog Modules

Measuring Range, Type T Thermocouples Table 8-22

Units

The table below shows the assignments of analog to digitized measured values for Type T thermocouples.

Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization; Type T Thermocouples (Copper/Copper-Nickel, to IEC 548, Part 1; Complement of Twos) Thermal e. m. f. in mV1

Temperature in °C

15 14 13 12 11 10 9 8

0

0 0 0 1 0 0 0 0 1 1 1 0 0 0 0

1

401

0 0 0 0 1 1 0 0 1 0 0 0 1 0 0

1

Range

Overflow Overrange2

400

20.869

400

0 0 0 0 1 1 0 0 1 0 0 0 0 0 0

0

399

20.807

399

0 0 0 0 1 1 0 0 0 1 1 1 1 0 0

0

200

9.286

200

0 0 0 0 0 1 1 0 0 1 0 0 0 0 0

0

100

4.277

100

0 0 0 0 0 0 1 1 0 0 1 0 0 0 0

0

1

0.039

1

0 0 0 0 0 0 0 0 0 0 0 0 1 0 0

0

0

0

0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0

–1

–0.039

–1

1 1 1 1 1 1 1 1 1 1 1 1 1 0 0

0

–100

–3.378

–100

1 1 1 1 1 1 0 0 1 1 1 0 0 0 0

0

–200

–5.603

–200

1 1 1 1 1 0 0 1 1 1 0 0 0 0 0

0

–269

–6.256

–269

1 1 1 1 0 1 1 1 1 0 0 1 1 0 0

0

–270

–6.258

–270

1 1 1 1 0 1 1 1 1 0 0 1 0 0 0

0

–271

1 1 1 1 0 1 1 1 1 0 0 0 1 0 0

1

1 1 1 1 0 1 1 1 0 1 1 1 1 0 0

1

Overflow

X X X X X X X X X X X X X 0 1

0

Wire break

–271

–273 X 1 2

7 6

X F OV

5 4 3 2 1

> 540

401

Digitized Measured Value

X

Nominal range

Overrange2 for a reference temperature 0 °C In the overrange, any rise in the characteristic curve is retained when the linearized nominal range is exited.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-37

8

Page 218

Analog Modules

Measuring Range, Type U Thermocouples Table 8-23

Units

The table below shows the assignments of analog to digitized measured values for Type U thermocouples.

Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization; Type U Thermocouples (Copper/Copper-Nickel, to DIN 43710; Complement of Twos) Thermal e. m. f. in mV1

Temperature in °C

8

0

601

0 0 0 1 0 0 1 0 1 1 0 0 1 0 0

1

1

Range

Overflow Overrange2

600

34.31

600

0 0 0 1 0 0 1 0 1 1 0 0 0 0 0

0

599

34.24

599

0 0 0 1 0 0 1 0 1 0 1 1 1 0 0

0

300

14.90

300

0 0 0 0 1 0 0 1 0 1 1 0 0 0 0

0

100

4.25

100

0 0 0 0 0 0 1 1 0 0 1 0 0 0 0

0

1

0.04

1

0 0 0 0 0 0 0 0 0 0 0 0 1 0 0

0

0

0

0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0

–1

–0.04

–1

1 1 1 1 1 1 1 1 1 1 1 1 1 0 0

0

–100

–3.4

–100

1 1 1 1 1 1 0 0 1 1 1 0 0 0 0

0

–150

–4.69

–150

1 1 1 1 1 0 1 1 0 1 0 1 0 0 0

0

–199

–5.68

–199

1 1 1 1 1 0 0 1 1 1 0 0 1 0 0

0

–200

–5.70

–200

1 1 1 1 1 0 0 1 1 1 0 0 0 0 0

0

–201

1 1 1 1 1 0 0 1 1 0 1 1 1 0 0

1

1 1 1 1 0 1 1 1 0 1 1 1 1 0 0

1

Overflow

X X X X X X X X X X X X X 0 1

0

Wire break

–201

–273 X 1 2

X F OV

15 14 13 12 11 10 9 8 7 6 5 4 2 1 3 0 0 0 1 1 0 1 0 1 0 0 1 0 0 0

> 850

601

Digitized Measured Value

X

Nominal range

Overrange2 for a reference temperature 0 °C In the overrange, any rise in the characteristic curve is retained when the linearized nominal range is exited.

8-38

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 219

Analog Modules

8.4.5

Analog Value Representation, Operation with SIMATIC S7

Analog Value Representation, SIMATIC S7

Table 8-24

If you operate the ET 200B-4/8AI with SIMATIC S7 the analog values are represented in complements of twos. The table below shows the analog value representation of the ET 200B-4/8AI:

Representation of an Analog Input Value as a Bit Pattern for SIMATIC S7 and ET 200B-4/8AI High Byte 13

12

11

Low Byte

Bit Number

15

14

10

9

8

7

6

5

4

3

2

1

0

Analog Value Representation

SI

214 213 212 211 210

29

28

27

26

25

24

23

22

21

20

Bit 15 has no significance for the amount of the measured value. It merely represents the sign.

Resolution

The resolution for the measured value depends directly on the integration time selected for the ET 200B-4/8A. In other words, the longer the integration time for an analog input channel, the higher is the resolution of the measured value. If the resolution of an analog module is less than 15 bits, the analog value entry is left-aligned. The unused lower-value places are padded with ”0”. Table 8-25 lists the possible resolutions of the ET 200B-4/8AI as a function of integration time. The ”x” characters indicate the bits that are of no significance for the measured value.

Table 8-25

Possible Resolutions of Analog Values: ET 200B-4/8AI

Integration Time

Analog Value Resolution in Bits

High Byte

Low Byte

2.5 ms

9 (+SI)

SI 0 0 0 0 0 0 0

0 1 x x x x x x

16.7 ms, 20 ms

12 (+SI)

SI 0 0 0 0 0 0 0

0 0 0 0 1 x x x

100 ms

14 (+SI)

SI 0 0 0 0 0 0 0

0 0 0 0 0 0 1 x

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-39

8

Page 220

Analog Modules

Voltage Measuring Ranges

Table 8-26

Measuring Range " 80 mV

The table below shows the representation of the digitized measuring values of the ET 200B-4/8AI for the measuring ranges: " 80 mV, " 250 mV, " 500 mV and " 1000 mV.

Representation of Digitized Measured Values of the ET 200B-4/8AI (Measuring Ranges: " 80 mV, " 250 mV, " 500 mV and " 1000 mV) Measuring Range " 250 mV

Measuring Range " 500 mV

Measuring Range " 1 V

Units Decimal Hexadecimal w 94.074 w 293.98 w 587.96 w 1.17592

32767

7FFFH

94.071

293.97

587.94

1.17588

32511

7EFFH

:

:

:

:

:

80.003

250.01

500.02

1.00004

27649

6C01H

80.000

250.00

500.00

1.000

27648

6C00H

60.000

187.50

375.00

0.750

20736

5100H

:

:

:

:

– 60.000

– 187.50

– 375.00

– 0.750

–20736

AF00H

– 80.000

– 250.00

– 500.00

–1.000

–27648

9400H

– 80.003

– 250.01

– 500.02

– 1.00004

–27649

93FFH

:

:

:

:

:

:

– 94.074

– 293.98

– 587.96

– 1.17592

–32512

8100H v– 94.077 v– 293.99 v– 587.98 v– 1.17596

–32768

8000H

:

:

:

Range Overflow

Overrange

Nominal range

Underrange

Underrun

8