Page 211
Analog Modules
Measuring Range, Ni 100 Resistance Sensors Table 8-16
Units
The table below shows the assignments of analog to digitized measured values for resistance sensors (Ni 100):
Representation of Digitized Measured Values of the ET 200B-4/8AI for Ni 100 Resistance Sensors (Complement of Twos) Resistance in W
Digitized Measured Value 15 14 13 12 11 10 9 8 7 6 5 4 3
X F OV 2 1
0
> 590
> 295
0 0 0 1 0 0 1 0 0 1 1 1 0 0 0
1
590
295
0 0 0 1 0 0 1 0 0 1 1 1 0 0 0
1
:
:
:
502
251
0 0 0 0 1 1 1 1 1 0 1 1 0 0 0
1
Range
Overflow Overrange1
500
289.2
250
0 0 0 0 1 1 1 1 1 0 1 0 0 0 0
0
498
288.1
249
0 0 0 0 1 1 1 1 1 0 0 1 0 0 0
0
400
240.7
200
0 0 0 0 1 1 0 0 1 0 0 0 0 0 0
0
200
161.8
100
0 0 0 0 0 1 1 0 0 1 0 0 0 0 0
0
2
100.5
1
0 0 0 0 0 0 0 0 0 0 0 1 0 0 0
0
0
100
0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0
–2
99.5
–1
1 1 1 1 1 1 1 1 1 1 1 1 0 0 0
0
–20
94.6
–10
1 1 1 1 1 1 1 1 0 1 1 0 0 0 0
0
–80
79.1
–40
1 1 1 1 1 1 0 1 1 0 0 0 0 0 0
0
–118
70
–59
1 1 1 1 1 1 0 0 0 1 0 1 0 0 0
0
–120
69.5
–60
1 1 1 1 1 1 0 0 0 1 0 0 0 0 0
0
–61
1 1 1 1 1 1 0 0 0 0 1 1 0 0 0
1
–122
1
Temperature in °C
Nominal range
8 Overrange1
:
:
:
–210
–105
1 1 1 1 1 0 0 1 0 1 1 1 0 0 0
1
< –210
< –105
1 1 1 1 1 0 0 1 0 1 1 1 0 0 0
1
Overflow
X
X
X X X X X X X X X X X X X 0 1
0
Wire break
In the overrange, any rise in the characteristic curve is retained when the linearized nominal range is exited.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-31
Page 212
Analog Modules
Measuring Range, Type E Thermocouples Table 8-17
Units
The table below shows the assignments of analog to digitized measured values for Type E thermocouples.
Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization; Type E Thermocouples (Nickel-Chrome/Copper-Nickel, to IEC 548, Part 1; Complement of Twos) Thermal e. m. f. in mV1
Temperature in °C
8
0
1001
0 0 0 1 1 1 1 1 0 1 0 0 1 0 0
1
1
Range
Overflow Overrange2
1000
76.358
1000
0 0 0 1 1 1 1 1 0 1 0 0 0 0 0
0
800
61.022
800
0 0 0 1 1 0 0 1 0 0 0 0 0 0 0
0
400
28.943
400
0 0 0 0 1 1 0 0 1 0 0 0 0 0 0
0
100
6.317
100
0 0 0 0 0 0 1 1 0 0 1 0 0 0 0
0
1
0.059
1
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0
0
0
0
0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0
–1
–0.059
–1
1 1 1 1 1 1 1 1 1 1 1 1 1 0 0
0
–100
–5.237
–100
1 1 1 1 1 1 0 0 1 1 1 0 0 0 0
0
–200
–8.824
–200
1 1 1 1 1 0 0 1 1 1 0 0 0 0 0
0
–269
–9.833
–269
1 1 1 1 0 1 1 1 1 0 0 1 1 0 0
0
–270
–9.835
–270
1 1 1 1 0 1 1 1 1 0 0 1 0 0 0
0
–271
1 1 1 1 0 1 1 1 1 0 0 0 1 0 0
1
1 1 1 1 0 1 1 1 0 1 1 1 1 0 0
1
Overflow
X X X X X X X X X X X X X 0 1
0
Wire break
–271
–273 X 1 2
X F OV
15 14 13 12 11 10 9 8 7 6 5 4 2 1 3 0 0 1 0 0 1 0 1 1 0 0 0 0 0 0
> 1200
1001
Digitized Measured Value
X
Nominal range
Overrange2 for a reference temperature 0 °C In the overrange, any rise in the characteristic curve is retained when the linearized nominal range is exited.
8-32
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 213
Analog Modules
Measuring Range, Type J Thermocouples Table 8-18
Units
The table below shows the assignments of analog to digitized measured values for Type J thermocouples.
Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization: Type J Thermocouple (Iron/Copper-Nickel (Constantan), to IEC 584) (Complement of Twos) Thermal e. m. f. in mV1
Temperature in °C
Digitized Measured Value 15 14 13 12 11 10 9 8
1485
7 6
5 4 3
X F OV 2 1
0
0 0 1 0 1 1 1 0 0 1 1 0 1 0 0
1
Range
Overflow Overrange2
1201
1201
0 0 1 0 0 1 0 1 1 0 0 0 1 0 0
1
1200
69.536
1200
0 0 1 0 0 1 0 1 1 0 0 0 0 0 0
0
1000
57.942
1000
0 0 0 1 1 1 1 1 0 1 0 0 0 0 0
0
500
27.388
500
0 0 0 0 1 1 1 1 1 0 1 0 0 0 0
0
100
5.268
100
0 0 0 0 0 0 1 1 0 0 1 0 0 0 0
0
1
0.05
1
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0
0
0
0
0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0
–1
–0.05
–1
1 1 1 1 1 1 1 1 1 1 1 1 1 0 0
0
–100
–4.632
–100
1 1 1 1 1 1 0 0 1 1 1 0 0 0 0
0
–150
–6.499
–150
1 1 1 1 1 0 1 1 0 1 0 1 0 0 0
0
–199
–7.868
–199
1 1 1 1 1 0 0 1 1 1 0 0 1 0 0
0
–200
–7.890
–200
1 1 1 1 1 0 0 1 1 1 0 0 0 0 0
0
–201
1 1 1 1 1 0 0 1 1 0 1 1 1 0 0
1
Overrange2
1 1 1 1 0 1 1 1 0 1 1 1 1 0 0
1
Overflow
X X X X X X X X X X X X X 0 1
0
Wire break
–201
–273 X 1 2
X
Nominal range
For a reference temperature of 0 °C (32 °F) In the overrange, any rise in the characteristic curve is retained when the linearized nominal range is exited.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-33
8
Page 214
Analog Modules
Measuring Range, Type K Thermocouples Table 8-19
Units
The table below shows the assignments of analog to digitized measured values for Type K thermocouples.
Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization: Type K Thermocouples (Nickel-Chrome/Nickel-Aluminum, to IEC 584) (Complement of Twos) Thermal e. m. f. in mV1
Temperature in °C
Digitized Measured Value 15 14 13 12 11 10 9 8
> 2359
7 6
5 4 3
X F OV 2 1
0
0 1 0 0 1 0 0 1 1 0 1 1 1 0 0
1
Range
Overflow Overrange2
1370
8
1370
0 0 1 0 1 0 1 0 1 1 0 1 0 0 0
1
1369
54.773
1369
0 0 1 0 1 0 1 0 1 1 0 0 1 0 0
0
1000
41.269
1000
0 0 0 1 1 1 1 1 0 1 0 0 0 0 0
0
500
20.640
500
0 0 0 0 1 1 1 1 1 0 1 0 0 0 0
0
150
6.137
150
0 0 0 0 0 1 0 0 1 0 1 1 0 0 0
0
100
4.095
100
0 0 0 0 0 0 1 1 0 0 1 0 0 0 0
0
1
0.039
1
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0
0
0
0
0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0
–1
–0.039
–1
1 1 1 1 1 1 1 1 1 1 1 1 1 0 0
0
–100
–3.553
–100
1 1 1 1 1 1 0 0 1 1 1 0 0 0 0
0
–101
–3.584
–101
1 1 1 1 1 1 0 0 1 1 0 1 1 0 0
0
Accuracy
–150
–4.912
–150
1 1 1 1 1 0 1 1 0 1 0 1 0 0 0
0 v2K
–200
–5.891
–200
1 1 1 1 1 0 0 1 1 1 0 0 0 0 0
0
–201
1 1 1 1 1 0 0 1 1 0 1 1 1 0 0
1
Overrange2
1 1 1 1 0 1 1 1 0 1 1 1 1 0 0
1
Overflow
X X X X X X X X X X X X X 0 1
0
Wire break
–201
–273 X 1 2
X
Nominal range
For a reference temperature of 0 °C (32 °F) In the overrange, any rise in the characteristic curve is retained when the linearized nominal range is exited.
8-34
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 215
Analog Modules
Measuring Range, Type L Thermocouples Table 8-20
Units
The table below shows the assignments of analog to digitized measured values for Type L thermocouples.
Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization: Type L Thermocouples (Iron/Copper-Nickel (Constantan), to DIN 43710) (Complement of Twos) Thermal e. m. f. in mV1
Temperature in °C
Digitized Measured Value 15 14 13 12 11 10 9 8
1361
7 6
5 4 3
X F OV 2 1
0
0 0 1 0 1 0 1 0 1 0 0 0 1 0 0
1
Range
Overflow Overrange2
901
901
0 0 0 1 1 1 0 0 0 0 1 0 1 0 0
1
900
53.14
900
0 0 0 1 1 1 0 0 0 0 1 0 0 0 0
0
500
27.85
500
0 0 0 0 1 1 1 1 1 0 1 0 0 0 0
0
250
13.75
250
0 0 0 0 0 1 1 1 1 1 0 1 0 0 0
0
100
+5.37
100
0 0 0 0 0 0 1 1 0 0 1 0 0 0 0
0
1
0.05
1
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0
0
0
0
0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0
–1
–0.05
–1
1 1 1 1 1 1 1 1 1 1 1 1 1 0 0
0
–100
–4.75
–100
1 1 1 1 1 1 0 0 1 1 1 0 0 0 0
0
–150
–6.60
–150
1 1 1 1 1 0 1 1 0 1 0 1 0 0 0
0
–190
–7.86
–190
1 1 1 1 1 0 1 0 0 0 0 1 0 0 0
0
–199
–8.12
–199
1 1 1 1 1 0 0 1 1 1 0 0 1 0 0
0
–200
1 1 1 1 1 0 0 1 1 1 0 0 0 0 0
1
Overrange2
1 1 1 1 0 1 1 1 0 1 1 1 1 0 0
1
Overflow
X X X X X X X X X X X X X 0 1
0
Wire break
–200
–273 X 1 2
X
Nominal range
For a reference temperature of 0 °C (32 °F) In the overrange, any rise in the characteristic curve is retained when the linearized nominal range is exited.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-35
8
Page 216
Analog Modules
Measuring Range, Type N Thermocouples Table 8-21
Units
The table below shows the assignments of analog to digitized measured values for Type N thermocouples.
Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization; Type N Thermocouples (Nickel-Chrome-Silicium/Nickel-Silicium, to IEC 548-1; Complement of Twos) Thermal e. m. f. in mV1
Temperature in °C
8
0
1301
0 0 1 0 1 0 0 0 1 0 1 0 1 0 0
1
1
Range
Overflow Overrange2
1300
47.502
1300
0 0 1 0 1 0 0 0 1 0 1 0 0 0 0
0
1000
36.248
1000
0 0 0 1 1 1 1 1 0 1 0 0 0 0 0
0
500
16.744
500
0 0 0 0 1 1 1 1 1 0 1 0 0 0 0
0
100
2.774
100
0 0 0 0 0 0 1 1 0 0 1 0 0 0 0
0
1
0.026
1
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0
0
0
0
0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0
–1
–0.026
–1
1 1 1 1 1 1 1 1 1 1 1 1 1 0 0
0
–100
–2.407
–100
1 1 1 1 1 1 0 0 1 1 1 0 0 0 0
0
–250
–4.313
–250
1 1 1 1 1 0 0 0 0 0 1 1 0 0 0
0
–269
–4.345
–269
1 1 1 1 0 1 1 1 1 0 0 1 1 0 0
0
–270
–4.345
–270
1 1 1 1 0 1 1 1 1 0 0 1 0 0 0
0
–271
1 1 1 1 0 1 1 1 1 0 0 0 1 0 0
1
1 1 1 1 0 1 1 1 0 1 1 1 1 0 0
1
Overflow
X X X X X X X X X X X X X 0 1
0
Wire break
–271
–273 X 1 2
X F OV
15 14 13 12 11 10 9 8 7 6 5 4 2 1 3 0 0 1 1 0 0 0 0 0 1 1 1 0 0 0
> 1550
1301
Digitized Measured Value
X
Nominal range
Overrange2 for a reference temperature 0 °C In the overrange, any rise in the characteristic curve is retained when the linearized nominal range is exited.
8-36
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 217
Analog Modules
Measuring Range, Type T Thermocouples Table 8-22
Units
The table below shows the assignments of analog to digitized measured values for Type T thermocouples.
Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization; Type T Thermocouples (Copper/Copper-Nickel, to IEC 548, Part 1; Complement of Twos) Thermal e. m. f. in mV1
Temperature in °C
15 14 13 12 11 10 9 8
0
0 0 0 1 0 0 0 0 1 1 1 0 0 0 0
1
401
0 0 0 0 1 1 0 0 1 0 0 0 1 0 0
1
Range
Overflow Overrange2
400
20.869
400
0 0 0 0 1 1 0 0 1 0 0 0 0 0 0
0
399
20.807
399
0 0 0 0 1 1 0 0 0 1 1 1 1 0 0
0
200
9.286
200
0 0 0 0 0 1 1 0 0 1 0 0 0 0 0
0
100
4.277
100
0 0 0 0 0 0 1 1 0 0 1 0 0 0 0
0
1
0.039
1
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0
0
0
0
0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0
–1
–0.039
–1
1 1 1 1 1 1 1 1 1 1 1 1 1 0 0
0
–100
–3.378
–100
1 1 1 1 1 1 0 0 1 1 1 0 0 0 0
0
–200
–5.603
–200
1 1 1 1 1 0 0 1 1 1 0 0 0 0 0
0
–269
–6.256
–269
1 1 1 1 0 1 1 1 1 0 0 1 1 0 0
0
–270
–6.258
–270
1 1 1 1 0 1 1 1 1 0 0 1 0 0 0
0
–271
1 1 1 1 0 1 1 1 1 0 0 0 1 0 0
1
1 1 1 1 0 1 1 1 0 1 1 1 1 0 0
1
Overflow
X X X X X X X X X X X X X 0 1
0
Wire break
–271
–273 X 1 2
7 6
X F OV
5 4 3 2 1
> 540
401
Digitized Measured Value
X
Nominal range
Overrange2 for a reference temperature 0 °C In the overrange, any rise in the characteristic curve is retained when the linearized nominal range is exited.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-37
8
Page 218
Analog Modules
Measuring Range, Type U Thermocouples Table 8-23
Units
The table below shows the assignments of analog to digitized measured values for Type U thermocouples.
Representation of Digitized Measured Values of the ET 200B-4/8AI with Linearization; Type U Thermocouples (Copper/Copper-Nickel, to DIN 43710; Complement of Twos) Thermal e. m. f. in mV1
Temperature in °C
8
0
601
0 0 0 1 0 0 1 0 1 1 0 0 1 0 0
1
1
Range
Overflow Overrange2
600
34.31
600
0 0 0 1 0 0 1 0 1 1 0 0 0 0 0
0
599
34.24
599
0 0 0 1 0 0 1 0 1 0 1 1 1 0 0
0
300
14.90
300
0 0 0 0 1 0 0 1 0 1 1 0 0 0 0
0
100
4.25
100
0 0 0 0 0 0 1 1 0 0 1 0 0 0 0
0
1
0.04
1
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0
0
0
0
0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0
–1
–0.04
–1
1 1 1 1 1 1 1 1 1 1 1 1 1 0 0
0
–100
–3.4
–100
1 1 1 1 1 1 0 0 1 1 1 0 0 0 0
0
–150
–4.69
–150
1 1 1 1 1 0 1 1 0 1 0 1 0 0 0
0
–199
–5.68
–199
1 1 1 1 1 0 0 1 1 1 0 0 1 0 0
0
–200
–5.70
–200
1 1 1 1 1 0 0 1 1 1 0 0 0 0 0
0
–201
1 1 1 1 1 0 0 1 1 0 1 1 1 0 0
1
1 1 1 1 0 1 1 1 0 1 1 1 1 0 0
1
Overflow
X X X X X X X X X X X X X 0 1
0
Wire break
–201
–273 X 1 2
X F OV
15 14 13 12 11 10 9 8 7 6 5 4 2 1 3 0 0 0 1 1 0 1 0 1 0 0 1 0 0 0
> 850
601
Digitized Measured Value
X
Nominal range
Overrange2 for a reference temperature 0 °C In the overrange, any rise in the characteristic curve is retained when the linearized nominal range is exited.
8-38
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 219
Analog Modules
8.4.5
Analog Value Representation, Operation with SIMATIC S7
Analog Value Representation, SIMATIC S7
Table 8-24
If you operate the ET 200B-4/8AI with SIMATIC S7 the analog values are represented in complements of twos. The table below shows the analog value representation of the ET 200B-4/8AI:
Representation of an Analog Input Value as a Bit Pattern for SIMATIC S7 and ET 200B-4/8AI High Byte 13
12
11
Low Byte
Bit Number
15
14
10
9
8
7
6
5
4
3
2
1
0
Analog Value Representation
SI
214 213 212 211 210
29
28
27
26
25
24
23
22
21
20
Bit 15 has no significance for the amount of the measured value. It merely represents the sign.
Resolution
The resolution for the measured value depends directly on the integration time selected for the ET 200B-4/8A. In other words, the longer the integration time for an analog input channel, the higher is the resolution of the measured value. If the resolution of an analog module is less than 15 bits, the analog value entry is left-aligned. The unused lower-value places are padded with ”0”. Table 8-25 lists the possible resolutions of the ET 200B-4/8AI as a function of integration time. The ”x” characters indicate the bits that are of no significance for the measured value.
Table 8-25
Possible Resolutions of Analog Values: ET 200B-4/8AI
Integration Time
Analog Value Resolution in Bits
High Byte
Low Byte
2.5 ms
9 (+SI)
SI 0 0 0 0 0 0 0
0 1 x x x x x x
16.7 ms, 20 ms
12 (+SI)
SI 0 0 0 0 0 0 0
0 0 0 0 1 x x x
100 ms
14 (+SI)
SI 0 0 0 0 0 0 0
0 0 0 0 0 0 1 x
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-39
8
Page 220
Analog Modules
Voltage Measuring Ranges
Table 8-26
Measuring Range " 80 mV
The table below shows the representation of the digitized measuring values of the ET 200B-4/8AI for the measuring ranges: " 80 mV, " 250 mV, " 500 mV and " 1000 mV.
Representation of Digitized Measured Values of the ET 200B-4/8AI (Measuring Ranges: " 80 mV, " 250 mV, " 500 mV and " 1000 mV) Measuring Range " 250 mV
Measuring Range " 500 mV
Measuring Range " 1 V
Units Decimal Hexadecimal w 94.074 w 293.98 w 587.96 w 1.17592
32767
7FFFH
94.071
293.97
587.94
1.17588
32511
7EFFH
:
:
:
:
:
80.003
250.01
500.02
1.00004
27649
6C01H
80.000
250.00
500.00
1.000
27648
6C00H
60.000
187.50
375.00
0.750
20736
5100H
:
:
:
:
– 60.000
– 187.50
– 375.00
– 0.750
–20736
AF00H
– 80.000
– 250.00
– 500.00
–1.000
–27648
9400H
– 80.003
– 250.01
– 500.02
– 1.00004
–27649
93FFH
:
:
:
:
:
:
– 94.074
– 293.98
– 587.96
– 1.17592
–32512
8100H v– 94.077 v– 293.99 v– 587.98 v– 1.17596
–32768
8000H
:
:
:
Range Overflow
Overrange
Nominal range
Underrange
Underrun
8
8-40
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c