Page 201

Analog Modules

Configuration for Resistors/Thermal Resistors

Table 8-6 shows the possible configurations of the ET 200B-4/8AI with COM ET 200 Windows or STEP 7 for connecting thermal resistors and for resistance measurement. Table 8-6 lists only the slots for configuring the input areas (slots 4 to 7). Slots 1 to 3 have the default value ”004”.

Table 8-6

Configuration

Possible IDs for Configuring the Input Areas of ET 200B-4/8AI, with only Thermal resistors and Resistors Connected Length1 (in Channel group 0 Channel group 1 Channel group 2 Channel group 3 words) Chan- Chan- Chan- Chan- Chan- Chan- Chan- Channel 0 nel 1 nel 2 nel 3 nel 4 nel 5 nel 6 nel 7 Terminals used

0.1/0.2 8AI

0.3/0.4 o

1.1/1.2

1.3/1.4 o

2.1/2.2

2.3/2.4 o

3.0/3.1

Meaning

3.3/3.4 o

8

5 to 8 x 1AI

A start address is assigned for the entire module, addresses for 8 words are reserved. Input data only in the words for channels 0, 2, 4 and 6. (= module addressing) This configuration is rejected as errored.

Channel group 0 Channel group 1 Channel group 2 Channel group 3 Channel 0 0.1/0.2

0.3/0.4

Channel 1 1.1/1.2

1.3/1.4

Channel 2 2.1/2.2

4 x 1AI o o o

3 x 1AI o o o

2 x 1AI o o

1 x 1AI o

1 o

2.3/2.4

Channel 3 3.0/3.1 o

3.3/3.4 4

3

2

1

A separate start address can be assigned for each channel. Addresses are reserved for a maximum of 4 words. (= singlechannel addressing)

Length of user data = Connection of measuring lines = Connection of constant-current lines

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-21

8

Page 202

Analog Modules

Example

In this example voltage sensors and thermal resistors (Pt 100) are connected.

Table 8-7

Example for Configuring the Input Areas of ET 200B-4/8AI

Configuration

Terminals used

7

Chan. group 0

Chan. group 1

Chan- Channel 0 nel 1

Channel 2

Chan- Chan- Chan- Channel 3 nel 4 nel 5 nel 6

0.1/ 0.2

0.3/ 0.4

1.1/ 1.2

2.1/ 2.2

2.3/ 2.4

3.0/ 3.1

3.3/ 3.4

U measurement

U measurement

U measurement

U measurement

U measurement

U measurement

1AI

8

1 o

Chan. group 1

Chan. group 2

6 voltage sensors and one Pt 100 thermal resistor

Chan. group 3

Ch. 1

Ch. 2

Channel 3

Ch. 4

Ch. 5

0.1/ 0.2

1.1/ 1.2

1.3/ 1.4

2.1/ 2.2

3.0/ 3.1

3.3/ 3.4

U measurement

U measurement

0.3/ 0.4

Meaning

7

Channel 0

Pt 100

1AI

Pt 100

Chan. group 3 o Chan. group 0

4

1.3/ 1.4

Chan. group 2

Length1 (in words)

o

2.3/ 2.4

Pt 100

2 voltage sensors and two Pt 100 thermal resistors o

4

Length of user data = Connection of measuring lines = Connection of constant-current lines

Notes on Configuring

Bear the following in mind when configuring the modules:

If you connect resistance thermometers/resistors, the assignment defined in the configuration and the parameterization must match.

If you connect 4 resistance thermometers/resistors, the only possible configuration options are 8AI or 4

1AI.

If you use single-channel addressing and configure more channels than is possible for parameterization with resistance thermometers/resistors, an error message is displayed for the module.

If you connect resistance thermometers/resistors and configure with the 8AI ID, the channels not used by the resistance inputs you configure (channels 1, 3, 5 and 7) are also transmitted to the DP master. In the input area addresses that cannot be used for these channels are assigned.

If you connect resistance thermometers/resistors and use single-channel addressing, addresses are assigned only for the resistance inputs.

Diagnostics messages and diagnostics data (slave diagnostics) are returned only for the configured channels.

8-22

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 203

Analog Modules

8.4.3

Setting the Operating Mode

Setting the Operating Mode

You set the operating mode of the ET 200B-4/8AI electronics block by means of the coding plugs on the TB8 terminal block and by means of the COM ET 200 or STEP 7 parameterization software. Coding Plugs

The coding plugs of the TB8 enable you to set the input circuit of the TB8 for analog value measurement of each individual channel group of the ET 200B-4/8AI in accordance with the measured-value sensor connected and the desired mode of measurement. The possible settings of the coding plugs are: ”A”, ”B”, ”C” and ”D”. For details of the relationships between the settings of the coding plugs and the mode of measurement and the measured-value sensors, see Section 8.4.1. Section 3.1 describes how to change the settings of the coding plugs.

Channel Group

Some parameters of the ET 200B-4/8AI listed on the following pages apply only to individual channel groups. Table 8-8 lists the assignment of TB8 terminals to channel groups. Table 8-8

Assignment of Terminals to Channel Groups Channel Group

Channel group 0

8

Terminals Terminals 0.1/0.2 Terminals 0.3/0.4

Channel group 1

Terminals 1.1/1.2 Terminals 1.3/1.4

Channel group 2

Terminals 2.1/2.2 Terminals 2.3/2.4

Channel group 3

Terminals 3.1/3.2 Terminals 3.3/3.4

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-23

Page 204

Analog Modules

Parameters

Table 8-9 shows all the parameters for parameterizing the ET 200B-4/8AI with COM ET 200 Windows or STEP 7. You can set these parameters for the ET 200B-4/8AI if you use the type file SI801ABE.200.

Table 8-9

Parameters for ET 200B-4/8AI (6ES7 134-0KH01-0XB0) Parameter

Diagnostics alarm

Explanation

Value Range

Diagnostics-alarm enable for module

Disable Enable

End-of-cycle alarm

End-of-cycle alarm enable for module

Disable Enable

Limit-value alarm

Limit-value alarm enable for module

Disable Enable

Diagnostics enable for channel group 0 Diagnostics messages enabled separately for each channel group Diagnostics enable for channel group 1

Disable Enable

Diagnostics enable for channel group 2 Diagnostics enable for channel group 3 Wire break monitoring enable for channel group 0 Wire break monitoring enable for channel group 1

8

Wire break monitoring enabled separately for each channel group: only for resistance thermometers (Pt 100, Ni 100), thermocouples, resistors and voltage sensors 80 mV

Disable

Enter an optimum integration time for the A/D converter to help suppress noise voltage.

2.5 ms 16.7 ms 20 ms 100 ms

Enable

Wire break monitoring enable for channel group 2 Wire break monitoring enable for channel group 3 Integration time for channel group 0 Integration time for channel group 1 Integration time for channel group 2 Integration time for channel group 3

8-24

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 205

Analog Modules

Table 8-9

Parameters for ET 200B-4/8AI (6ES7 134-0KH01-0XB0), continued Parameter

Explanation

Value Range

Measurement type and range for channel group 0

You can set the measurement type and range separately for each channel group

Channel not activated

For voltage measurement:

Measurement type and range for channel group 1

Measurement type and range for channel group 2

Measurement type and range for channel group 3

"1V " 0.5 V " 0.25 V " 80 mV

For resistance thermometer with linearization:

Pt 100 standard range Ni 100 standard range

For thermocouple with external reference junction:

Type N with linearization Type E with linearization Type J with linearization Type L with linearization Type T with linearization Type K with linearization Type U with linearization

For resistance measurement:

48 ohms 150 ohms 300 ohms 600 ohms

Representation of measured values

Sets representation of the measured values for module

SIMATIC S5 SIMATIC S7

Measured value representation: S5

Sets data format for analog value representation, SIMATIC S5

Complement of twos Amount with sign

Upper limit value for channel 0

Upper and lower limit values for each channel

0 *32768 ... 32767

Lower limit value for channel 0

0 *32768 ... 32767

Upper limit value for channel 2 (channel 1*)

0 *32768 ... 32767

Lower limit value for channel 2 (channel 1*)

0 *32768 ... 32767

: *

8

Default

For the ET 200B-4/8AI, only the combination of single channel addressing and parameterization of channel group 0 for resistance measurement (Pt 100, Ni 100, R) requires parameterization of the ”Upper/lower limit values” for channel 1. In all other cases (i.e. module addressing and single channel addressingand parameterization of channel group 0 for other than resistance measurement (Pt 100, Ni 100, R), you parameterize ”Upper/lower limit values” for channel 2.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

8-25

Page 206

Analog Modules

8.4.4

Analog Value Representation, Operation with SIMATIC S5

Analog Value Representation, SIMATIC S7

If you operate the ET 200B-4/8AI with SIMATIC S5, you can utilize the analog value representation of SIMATIC S7 (higher measured-value resolution: max. 14 bits + sign). See Section 8.4.5 for the measured-value tables for analog value representation in SIMATIC S7.

Analog Value Representation, SIMATIC S5

Analog values can be represented in two data formats with the ET 200B-4/8AI for SIMATIC S5:

12-bit complement of twos representation (range: –2048 to +2047 units) 11-bit amount and 1-bit sign (range: –2048 to +2047 units) The Table below shows the analog value representation of the ET 200B-4AI:

Table 8-10

Representation of an Analog Input Value as a Bit Pattern (6ES7 134-0KH01-0XB0) High Byte

Low Byte

Bit number

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Analog value representation

SI

211 210

29

28

27

26

25

24

23

22

21

20

X

F s

Bits 0 to 2 and bit 15 have no significance for the amount of the measured value. See Table 8-11 for a detailed description of these bits.

8

Supplementary Bits

Bits 0 to 2 and bit 15 have the following meaning in the bit pattern of the analog input value: Table 8-11

Bit

Meaning

Signal Status

Meaning of the Signal Status

OV

Overflow bit

1

Overrange1

F

Fault bit

1

Wire break; the measured value read in is not valid2

SI

Sign

0

“+” sign

1

“–” sign

–

–

X 1

2

8-26

Description of the Bits (6ES7 134-0KH01-0XB0)

Irrelevant

In the event of an overflow at one measuring point, the overflow bits of the other channels remain unaffected; this means that the values of the other channels are correct and can be evaluated. When the ET 200B-4/8AI signals a wire break (fault bit F = 1), the overflow bit OV is also set.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 207

Analog Modules

Voltage Measuring Ranges

Table 8-12

The two tables below show the assignments of analog to digitized measured values for the measuring ranges: 80 mV, 250 mV, 500 mV and 1000 mV.

Representation of Digitized Measured Values of the ET 200B-4/8AI (6ES7 134-0KH01-0XB0; Measuring Ranges: 80 mV, 250 mV, 500 mV and 1000 mV; Complement of Twos)

Units

Measured Value in mV

Digitized Measured Value

X F O V

Range mV mV mV mV

> 2409

94.10

294.07

588.13

1176.26 0 1 0 0 1 0 1 1 0 1 0 0 1 0 0 1

Overflow

2408

94.06

293.95

587.89

1175.78

0 1 0 0 1 0 1 1 0 1 0 0 0 0 0 0

Overrange

:

:

:

:

:

:

2049

80.04

250.12

500.24

1000.48

0 1 0 0 0 0 0 0 0 0 0 0 1 0 0 0

2048

80.00

250.0

500.0

1000.0

0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0

1024

40.00

125.00

250.00

500.00

0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0

1

0.039

0.12

0.24

0.48

0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0

0

0.00

0.00

0.00

0.00

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

–1

–0.039

–0.12

–0.24

–0.48

1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0

–1024

–40.00 –125.00

–250.00

–500.00

1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0

–2048

–80.00

–250.0

–500.0

–1000.0

1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0

–2049

–80.04 –250.12

–500.24

–1000.48 1 0 1 1 1 1 1 1 1 1 1 1 1 0 0 0

:

:

:

:

:

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Overrange

:

–2408

–94.06 –293.95

587.89

–1175.78 1 0 1 1 0 1 0 0 1 1 0 0 0 0 0 0

< –2409

–94.10 –294.07

–588.13

–1176.26 1 0 1 1 0 1 0 0 1 0 1 1 1 0 0 1

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Nominal range

8 Overflow

8-27

Page 208

Analog Modules

Table 8-13

Representation of Digitized Measured Values of the ET 200B-4/8AI (6ES7 134-0KH01-0XB0; Measuring Ranges: " 80 mV, " 250 mV, " 500 mV and " 1000 mV; Amount and Sign)

Units

Measured Value in mV

SI

Digitized Measured Value

X F OV

Range

"80 mV

"250 mV

"500 mV

"1000 mV

15

14 13 12 11 10 9 8 7 6 5 4 3 2 1

0

> 2409

94.10

294.07

588.13

1176.26

0

1 0 0 1 0 1 1 0 1 0 0 1 0 0

1

Overflow

2408

94.06

293.95

587.89

1175.78

0

1 0 0 1 0 1 1 0 1 0 0 0 0 0

0

Overrange

Range

:

:

:

:

:

2049

80.04

250.12

500.24

1000.48

0

1 0 0 0 0 0 0 0 0 0 0 1 0 0

0

2048

80.00

250.0

500.0

1000.0

0

1 0 0 0 0 0 0 0 0 0 0 0 0 0

0

1024

40.00

125.00

250.00

500.00

0

0 1 0 0 0 0 0 0 0 0 0 0 0 0

0

1

0.039

0.12

0.24

0.48

0

0 0 0 0 0 0 0 0 0 0 0 1 0 0

0

0

0.00

0.00

0.00

0.00

0

0 0 0 0 0 0 0 0 0 0 0 0 0 0

0

–1

–0.039

–0.12

–0.24

–0.48

1

0 0 0 0 0 0 0 0 0 0 0 1 0 0

0

–1024

–40.00 –125.00

–250.00

–500.00

1

0 1 0 0 0 0 0 0 0 0 0 0 0 0

0

–2048

–80.00

–250.0

–500.0

–1000.0

1

1 0 0 0 0 0 0 0 0 0 0 0 0 0

0

–2049

–80.04 –250.12

–500.24

–1000.48

1

1 0 0 0 0 0 0 0 0 0 0 1 0 0

0

:

:

:

:

:

:

–2408

–94.06 –293.95

587.89

–1175.78

1

1 0 0 1 0 1 1 0 1 0 0 0 0 0

: 0

< –2409

–94.10 –294.07

–588.13

–1176.26

1

1 0 0 1 0 1 1 0 1 0 0 1 0 0

1

Nominal range

Overrange

Overflow

8 Note Bit 15 of the digitized measured value indicates the sign. The following applies: SI = 0 ³ positive value; SI = 1 ³ negative value.

8-28

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 209

Analog Modules

2Measuring Ranges: Resistance Measurement Table 8-14

The table below shows the assignments of analog to digitized measured values for the resistance measuring ranges: 48 W, 150 W, 300 W and 600 W.

Representation of Digitized Measured Values of the ET 200B-4/8AI for Resistance Measurement (Complement of Twos) Resistance in W

Units

Digitized Measured Value 15 14 13 12 11 10 9 8 7 6 5 4 3

X F OV

48

150

300

600

2 1

0 w 2409

56.46

176.44

352.88

705.76 0 1 0 0 1 0 1 1 0 1 0 0 1 0 0

1

2408

56.44

176.37

352.73

705.47 0 1 0 0 1 0 1 1 0 1 0 0 0 0 0

0

:

:

:

:

2049

48.02

150.07

300.14

600.29 0 1 0 0 0 0 0 0 0 0 0 0 1 0 0

0

2048

48

150

300

600

0 1 0 0 0 0 0 0 0 0 0 0 0 0 0

0

1536

36

112.5

225

450

0 0 1 1 0 0 0 0 0 0 0 0 0 0 0

0

1024

24

75

150

300

0 0 1 0 0 0 0 0 0 0 0 0 0 0 0

0

512

12

37.5

75

150

0 0 0 1 0 0 0 0 0 0 0 0 0 0 0

0

1

0.023

0.072

0.144

0.288

0 0 0 0 0 0 0 0 0 0 0 0 1 0 0

0

0

0

0

0

0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0

(Negative values physically impossible)

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

1

0 : X

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

:

:

Overflow Overrange

Nominal range

Overflow

: X X X X X X X X X X X X X 0 1

Range

0

Wire break

8-29

8

Page 210

Analog Modules

Measuring Range, Pt 100 Resistance Thermometers Table 8-15

Units

1

Representation of Digitized Measured Values of the ET 200B-4/8AI for Resistance Thermometers (Complement of Twos) Resistance in W

Temperature in °C

> 400

Digitized Measured Value

X F OV

15 14 13 12 11 10 9 8 7 6 5 4 3

2 1

0

> 883

0 0 1 1 0 1 1 1 0 0 1 1 0 0 0

1

1766

883

0 0 1 1 0 1 1 1 0 0 1 1 0 0 0

1

:

:

:

1702

851

0 0 1 1 0 1 0 1 0 0 1 1 0 0 0

1

> 1766

8

The table below shows the assignments of analog to digitized measured values for resistance thermometers (Pt 100):

Range

Overflow Overrange1

1700

390.26

850

0 0 1 1 0 1 0 1 0 0 1 0 0 0 0

0

1400

345.13

700

0 0 1 0 1 0 1 1 1 1 0 0 0 0 0

0

1000

280.90

500

0 0 0 1 1 1 1 1 0 1 0 0 0 0 0

0

600

212.02

300

0 0 0 1 0 0 1 0 1 1 0 0 0 0 0

0

300

157.31

150

0 0 0 0 1 0 0 1 0 1 1 0 0 0 0

0

200

138.50

100

0 0 0 0 0 1 1 0 0 1 0 0 0 0 0

0

2

100.39

1

0 0 0 0 0 0 0 0 0 0 0 1 0 0 0

0

–0

100.00

0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0

–40

92.16

–20

1 1 1 1 1 1 1 0 1 1 0 0 0 0 0

0

–80

84.27

–40

1 1 1 1 1 1 0 1 1 0 0 0 0 0 0

0

–200

60.25

–100

1 1 1 1 1 0 0 1 1 1 0 0 0 0 0

0

–202

–101

1 1 1 1 1 0 0 1 1 0 1 1 0 0 0

1

:

:

:

–494

–247

1 1 1 1 0 0 0 0 1 0 0 1 0 0 0

1

< –494

< –247

1 1 1 1 0 0 0 0 1 0 0 1 0 0 0

1

Nominal range

Overrange1

Overflow

In the overrange, any rise in the characteristic curve is retained when the linearized nominal range is exited.

8-30

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c