The text of a manual · part 26 of 41
SIMATIC ET 200B Distributed I/O Station Manual: 8 Analog Modules, pages 201 to 210
Pages 201 to 210 of 344, from SIMATIC ET 200B Distributed I/O Station Manual
The original document is the PDF (2.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens ET 200B
Page 201
Analog Modules
Configuration for Resistors/Thermal Resistors
Table 8-6 shows the possible configurations of the ET 200B-4/8AI with COM ET 200 Windows or STEP 7 for connecting thermal resistors and for resistance measurement. Table 8-6 lists only the slots for configuring the input areas (slots 4 to 7). Slots 1 to 3 have the default value ”004”.
Table 8-6
Configuration
Possible IDs for Configuring the Input Areas of ET 200B-4/8AI, with only Thermal resistors and Resistors Connected Length1 (in Channel group 0 Channel group 1 Channel group 2 Channel group 3 words) Chan- Chan- Chan- Chan- Chan- Chan- Chan- Channel 0 nel 1 nel 2 nel 3 nel 4 nel 5 nel 6 nel 7 Terminals used
0.1/0.2 8AI
0.3/0.4 o
1.1/1.2
1.3/1.4 o
2.1/2.2
2.3/2.4 o
3.0/3.1
Meaning
3.3/3.4 o
8
5 to 8 x 1AI
A start address is assigned for the entire module, addresses for 8 words are reserved. Input data only in the words for channels 0, 2, 4 and 6. (= module addressing) This configuration is rejected as errored.
Channel group 0 Channel group 1 Channel group 2 Channel group 3 Channel 0 0.1/0.2
0.3/0.4
Channel 1 1.1/1.2
1.3/1.4
Channel 2 2.1/2.2
4 x 1AI o o o
3 x 1AI o o o
2 x 1AI o o
1 x 1AI o
1 o
2.3/2.4
Channel 3 3.0/3.1 o
3.3/3.4 4
3
2
1
A separate start address can be assigned for each channel. Addresses are reserved for a maximum of 4 words. (= singlechannel addressing)
Length of user data = Connection of measuring lines = Connection of constant-current lines
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-21
8
Page 202
Analog Modules
Example
In this example voltage sensors and thermal resistors (Pt 100) are connected.
Table 8-7
Example for Configuring the Input Areas of ET 200B-4/8AI
Configuration
Terminals used
7
Chan. group 0
Chan. group 1
Chan- Channel 0 nel 1
Channel 2
Chan- Chan- Chan- Channel 3 nel 4 nel 5 nel 6
0.1/ 0.2
0.3/ 0.4
1.1/ 1.2
2.1/ 2.2
2.3/ 2.4
3.0/ 3.1
3.3/ 3.4
U measurement
U measurement
U measurement
U measurement
U measurement
U measurement
1AI
8
1 o
Chan. group 1
Chan. group 2
6 voltage sensors and one Pt 100 thermal resistor
Chan. group 3
Ch. 1
Ch. 2
Channel 3
Ch. 4
Ch. 5
0.1/ 0.2
1.1/ 1.2
1.3/ 1.4
2.1/ 2.2
3.0/ 3.1
3.3/ 3.4
U measurement
U measurement
0.3/ 0.4
Meaning
7
Channel 0
Pt 100
1AI
Pt 100
Chan. group 3 o Chan. group 0
4
1.3/ 1.4
Chan. group 2
Length1 (in words)
o
2.3/ 2.4
Pt 100
2 voltage sensors and two Pt 100 thermal resistors o
4
Length of user data = Connection of measuring lines = Connection of constant-current lines
Notes on Configuring
Bear the following in mind when configuring the modules:
If you connect resistance thermometers/resistors, the assignment defined in the configuration and the parameterization must match.
If you connect 4 resistance thermometers/resistors, the only possible configuration options are 8AI or 4
1AI.
If you use single-channel addressing and configure more channels than is possible for parameterization with resistance thermometers/resistors, an error message is displayed for the module.
If you connect resistance thermometers/resistors and configure with the 8AI ID, the channels not used by the resistance inputs you configure (channels 1, 3, 5 and 7) are also transmitted to the DP master. In the input area addresses that cannot be used for these channels are assigned.
If you connect resistance thermometers/resistors and use single-channel addressing, addresses are assigned only for the resistance inputs.
Diagnostics messages and diagnostics data (slave diagnostics) are returned only for the configured channels.
8-22
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 203
Analog Modules
8.4.3
Setting the Operating Mode
Setting the Operating Mode
You set the operating mode of the ET 200B-4/8AI electronics block by means of the coding plugs on the TB8 terminal block and by means of the COM ET 200 or STEP 7 parameterization software. Coding Plugs
The coding plugs of the TB8 enable you to set the input circuit of the TB8 for analog value measurement of each individual channel group of the ET 200B-4/8AI in accordance with the measured-value sensor connected and the desired mode of measurement. The possible settings of the coding plugs are: ”A”, ”B”, ”C” and ”D”. For details of the relationships between the settings of the coding plugs and the mode of measurement and the measured-value sensors, see Section 8.4.1. Section 3.1 describes how to change the settings of the coding plugs.
Channel Group
Some parameters of the ET 200B-4/8AI listed on the following pages apply only to individual channel groups. Table 8-8 lists the assignment of TB8 terminals to channel groups. Table 8-8
Assignment of Terminals to Channel Groups Channel Group
Channel group 0
8
Terminals Terminals 0.1/0.2 Terminals 0.3/0.4
Channel group 1
Terminals 1.1/1.2 Terminals 1.3/1.4
Channel group 2
Terminals 2.1/2.2 Terminals 2.3/2.4
Channel group 3
Terminals 3.1/3.2 Terminals 3.3/3.4
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-23
Page 204
Analog Modules
Parameters
Table 8-9 shows all the parameters for parameterizing the ET 200B-4/8AI with COM ET 200 Windows or STEP 7. You can set these parameters for the ET 200B-4/8AI if you use the type file SI801ABE.200.
Table 8-9
Parameters for ET 200B-4/8AI (6ES7 134-0KH01-0XB0) Parameter
Diagnostics alarm
Explanation
Value Range
Diagnostics-alarm enable for module
Disable Enable
End-of-cycle alarm
End-of-cycle alarm enable for module
Disable Enable
Limit-value alarm
Limit-value alarm enable for module
Disable Enable
Diagnostics enable for channel group 0 Diagnostics messages enabled separately for each channel group Diagnostics enable for channel group 1
Disable Enable
Diagnostics enable for channel group 2 Diagnostics enable for channel group 3 Wire break monitoring enable for channel group 0 Wire break monitoring enable for channel group 1
8
Wire break monitoring enabled separately for each channel group: only for resistance thermometers (Pt 100, Ni 100), thermocouples, resistors and voltage sensors 80 mV
Disable
Enter an optimum integration time for the A/D converter to help suppress noise voltage.
2.5 ms 16.7 ms 20 ms 100 ms
Enable
Wire break monitoring enable for channel group 2 Wire break monitoring enable for channel group 3 Integration time for channel group 0 Integration time for channel group 1 Integration time for channel group 2 Integration time for channel group 3
8-24
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 205
Analog Modules
Table 8-9
Parameters for ET 200B-4/8AI (6ES7 134-0KH01-0XB0), continued Parameter
Explanation
Value Range
Measurement type and range for channel group 0
You can set the measurement type and range separately for each channel group
Channel not activated
For voltage measurement:
Measurement type and range for channel group 1
Measurement type and range for channel group 2
Measurement type and range for channel group 3
"1V " 0.5 V " 0.25 V " 80 mV
For resistance thermometer with linearization:
Pt 100 standard range Ni 100 standard range
For thermocouple with external reference junction:
Type N with linearization Type E with linearization Type J with linearization Type L with linearization Type T with linearization Type K with linearization Type U with linearization
For resistance measurement:
48 ohms 150 ohms 300 ohms 600 ohms
Representation of measured values
Sets representation of the measured values for module
SIMATIC S5 SIMATIC S7
Measured value representation: S5
Sets data format for analog value representation, SIMATIC S5
Complement of twos Amount with sign
Upper limit value for channel 0
Upper and lower limit values for each channel
0 *32768 ... 32767
Lower limit value for channel 0
0 *32768 ... 32767
Upper limit value for channel 2 (channel 1*)
0 *32768 ... 32767
Lower limit value for channel 2 (channel 1*)
0 *32768 ... 32767
: *
8
Default
For the ET 200B-4/8AI, only the combination of single channel addressing and parameterization of channel group 0 for resistance measurement (Pt 100, Ni 100, R) requires parameterization of the ”Upper/lower limit values” for channel 1. In all other cases (i.e. module addressing and single channel addressingand parameterization of channel group 0 for other than resistance measurement (Pt 100, Ni 100, R), you parameterize ”Upper/lower limit values” for channel 2.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-25
Page 206
Analog Modules
8.4.4
Analog Value Representation, Operation with SIMATIC S5
Analog Value Representation, SIMATIC S7
If you operate the ET 200B-4/8AI with SIMATIC S5, you can utilize the analog value representation of SIMATIC S7 (higher measured-value resolution: max. 14 bits + sign). See Section 8.4.5 for the measured-value tables for analog value representation in SIMATIC S7.
Analog Value Representation, SIMATIC S5
Analog values can be represented in two data formats with the ET 200B-4/8AI for SIMATIC S5:
12-bit complement of twos representation (range: –2048 to +2047 units) 11-bit amount and 1-bit sign (range: –2048 to +2047 units) The Table below shows the analog value representation of the ET 200B-4AI:
Table 8-10
Representation of an Analog Input Value as a Bit Pattern (6ES7 134-0KH01-0XB0) High Byte
Low Byte
Bit number
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Analog value representation
SI
211 210
29
28
27
26
25
24
23
22
21
20
X
F s
Bits 0 to 2 and bit 15 have no significance for the amount of the measured value. See Table 8-11 for a detailed description of these bits.
8
Supplementary Bits
Bits 0 to 2 and bit 15 have the following meaning in the bit pattern of the analog input value: Table 8-11
Bit
Meaning
Signal Status
Meaning of the Signal Status
OV
Overflow bit
1
Overrange1
F
Fault bit
1
Wire break; the measured value read in is not valid2
SI
Sign
0
“+” sign
1
“–” sign
–
–
X 1
2
8-26
Description of the Bits (6ES7 134-0KH01-0XB0)
Irrelevant
In the event of an overflow at one measuring point, the overflow bits of the other channels remain unaffected; this means that the values of the other channels are correct and can be evaluated. When the ET 200B-4/8AI signals a wire break (fault bit F = 1), the overflow bit OV is also set.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 207
Analog Modules
Voltage Measuring Ranges
Table 8-12
The two tables below show the assignments of analog to digitized measured values for the measuring ranges: 80 mV, 250 mV, 500 mV and 1000 mV.
Representation of Digitized Measured Values of the ET 200B-4/8AI (6ES7 134-0KH01-0XB0; Measuring Ranges: 80 mV, 250 mV, 500 mV and 1000 mV; Complement of Twos)
Units
Measured Value in mV
Digitized Measured Value
X F O V
Range mV mV mV mV
> 2409
94.10
294.07
588.13
1176.26 0 1 0 0 1 0 1 1 0 1 0 0 1 0 0 1
Overflow
2408
94.06
293.95
587.89
1175.78
0 1 0 0 1 0 1 1 0 1 0 0 0 0 0 0
Overrange
:
:
:
:
:
:
2049
80.04
250.12
500.24
1000.48
0 1 0 0 0 0 0 0 0 0 0 0 1 0 0 0
2048
80.00
250.0
500.0
1000.0
0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0
1024
40.00
125.00
250.00
500.00
0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0
1
0.039
0.12
0.24
0.48
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0
0
0.00
0.00
0.00
0.00
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
–1
–0.039
–0.12
–0.24
–0.48
1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0
–1024
–40.00 –125.00
–250.00
–500.00
1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0
–2048
–80.00
–250.0
–500.0
–1000.0
1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0
–2049
–80.04 –250.12
–500.24
–1000.48 1 0 1 1 1 1 1 1 1 1 1 1 1 0 0 0
:
:
:
:
:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Overrange
:
–2408
–94.06 –293.95
587.89
–1175.78 1 0 1 1 0 1 0 0 1 1 0 0 0 0 0 0
< –2409
–94.10 –294.07
–588.13
–1176.26 1 0 1 1 0 1 0 0 1 0 1 1 1 0 0 1
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Nominal range
8 Overflow
8-27
Page 208
Analog Modules
Table 8-13
Representation of Digitized Measured Values of the ET 200B-4/8AI (6ES7 134-0KH01-0XB0; Measuring Ranges: " 80 mV, " 250 mV, " 500 mV and " 1000 mV; Amount and Sign)
Units
Measured Value in mV
SI
Digitized Measured Value
X F OV
Range
"80 mV
"250 mV
"500 mV
"1000 mV
15
14 13 12 11 10 9 8 7 6 5 4 3 2 1
0
> 2409
94.10
294.07
588.13
1176.26
0
1 0 0 1 0 1 1 0 1 0 0 1 0 0
1
Overflow
2408
94.06
293.95
587.89
1175.78
0
1 0 0 1 0 1 1 0 1 0 0 0 0 0
0
Overrange
Range
:
:
:
:
:
2049
80.04
250.12
500.24
1000.48
0
1 0 0 0 0 0 0 0 0 0 0 1 0 0
0
2048
80.00
250.0
500.0
1000.0
0
1 0 0 0 0 0 0 0 0 0 0 0 0 0
0
1024
40.00
125.00
250.00
500.00
0
0 1 0 0 0 0 0 0 0 0 0 0 0 0
0
1
0.039
0.12
0.24
0.48
0
0 0 0 0 0 0 0 0 0 0 0 1 0 0
0
0
0.00
0.00
0.00
0.00
0
0 0 0 0 0 0 0 0 0 0 0 0 0 0
0
–1
–0.039
–0.12
–0.24
–0.48
1
0 0 0 0 0 0 0 0 0 0 0 1 0 0
0
–1024
–40.00 –125.00
–250.00
–500.00
1
0 1 0 0 0 0 0 0 0 0 0 0 0 0
0
–2048
–80.00
–250.0
–500.0
–1000.0
1
1 0 0 0 0 0 0 0 0 0 0 0 0 0
0
–2049
–80.04 –250.12
–500.24
–1000.48
1
1 0 0 0 0 0 0 0 0 0 0 1 0 0
0
:
:
:
:
:
:
–2408
–94.06 –293.95
587.89
–1175.78
1
1 0 0 1 0 1 1 0 1 0 0 0 0 0
: 0
< –2409
–94.10 –294.07
–588.13
–1176.26
1
1 0 0 1 0 1 1 0 1 0 0 1 0 0
1
Nominal range
Overrange
Overflow
8 Note Bit 15 of the digitized measured value indicates the sign. The following applies: SI = 0 ³ positive value; SI = 1 ³ negative value.
8-28
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 209
Analog Modules
2Measuring Ranges: Resistance Measurement Table 8-14
The table below shows the assignments of analog to digitized measured values for the resistance measuring ranges: 48 W, 150 W, 300 W and 600 W.
Representation of Digitized Measured Values of the ET 200B-4/8AI for Resistance Measurement (Complement of Twos) Resistance in W
Units
Digitized Measured Value 15 14 13 12 11 10 9 8 7 6 5 4 3
X F OV
48
150
300
600
2 1
0 w 2409
56.46
176.44
352.88
705.76 0 1 0 0 1 0 1 1 0 1 0 0 1 0 0
1
2408
56.44
176.37
352.73
705.47 0 1 0 0 1 0 1 1 0 1 0 0 0 0 0
0
:
:
:
:
2049
48.02
150.07
300.14
600.29 0 1 0 0 0 0 0 0 0 0 0 0 1 0 0
0
2048
48
150
300
600
0 1 0 0 0 0 0 0 0 0 0 0 0 0 0
0
1536
36
112.5
225
450
0 0 1 1 0 0 0 0 0 0 0 0 0 0 0
0
1024
24
75
150
300
0 0 1 0 0 0 0 0 0 0 0 0 0 0 0
0
512
12
37.5
75
150
0 0 0 1 0 0 0 0 0 0 0 0 0 0 0
0
1
0.023
0.072
0.144
0.288
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0
0
0
0
0
0
0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0
(Negative values physically impossible)
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
1
0 : X
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
:
:
Overflow Overrange
Nominal range
Overflow
: X X X X X X X X X X X X X 0 1
Range
0
Wire break
8-29
8
Page 210
Analog Modules
Measuring Range, Pt 100 Resistance Thermometers Table 8-15
Units
1
Representation of Digitized Measured Values of the ET 200B-4/8AI for Resistance Thermometers (Complement of Twos) Resistance in W
Temperature in °C
> 400
Digitized Measured Value
X F OV
15 14 13 12 11 10 9 8 7 6 5 4 3
2 1
0
> 883
0 0 1 1 0 1 1 1 0 0 1 1 0 0 0
1
1766
883
0 0 1 1 0 1 1 1 0 0 1 1 0 0 0
1
:
:
:
1702
851
0 0 1 1 0 1 0 1 0 0 1 1 0 0 0
1
> 1766
8
The table below shows the assignments of analog to digitized measured values for resistance thermometers (Pt 100):
Range
Overflow Overrange1
1700
390.26
850
0 0 1 1 0 1 0 1 0 0 1 0 0 0 0
0
1400
345.13
700
0 0 1 0 1 0 1 1 1 1 0 0 0 0 0
0
1000
280.90
500
0 0 0 1 1 1 1 1 0 1 0 0 0 0 0
0
600
212.02
300
0 0 0 1 0 0 1 0 1 1 0 0 0 0 0
0
300
157.31
150
0 0 0 0 1 0 0 1 0 1 1 0 0 0 0
0
200
138.50
100
0 0 0 0 0 1 1 0 0 1 0 0 0 0 0
0
2
100.39
1
0 0 0 0 0 0 0 0 0 0 0 1 0 0 0
0
–0
100.00
0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0
–40
92.16
–20
1 1 1 1 1 1 1 0 1 1 0 0 0 0 0
0
–80
84.27
–40
1 1 1 1 1 1 0 1 1 0 0 0 0 0 0
0
–200
60.25
–100
1 1 1 1 1 0 0 1 1 1 0 0 0 0 0
0
–202
–101
1 1 1 1 1 0 0 1 1 0 1 1 0 0 0
1
:
:
:
–494
–247
1 1 1 1 0 0 0 0 1 0 0 1 0 0 0
1
< –494
< –247
1 1 1 1 0 0 0 0 1 0 0 1 0 0 0
1
Nominal range
Overrange1
Overflow
In the overrange, any rise in the characteristic curve is retained when the linearized nominal range is exited.
8-30
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c