The text of a manual · part 25 of 41
SIMATIC ET 200B Distributed I/O Station Manual: 8 Analog Modules, pages 191 to 200
Pages 191 to 200 of 344, from SIMATIC ET 200B Distributed I/O Station Manual
The original document is the PDF (2.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens ET 200B
Page 191
Analog Modules
Floating-Ground Measurement
  . . . . .
The figure below illustrates the connection of thermocouples of the same type with one compensating box for the entire module (floating-ground measurement):
Ä ÄÄ Ä
A x.3 x.1 V x.2 x.4 MA
A
 Â. . V
A K+ í K–
MA
A
A
TB8
K+
0.3 0.4
1.3 1.4
MA L+ L+
K–
0.1 0.2
1.1 1.2
MA M M
.
. Shield + 24V Comp. box
. .
. .
Thermal link
UCM v"1V Max. 75 V DC/60 V AC PE Figure 8-6
Max. 75 V DC/ 60 V AC MA
Mexternal
Connection of Thermocouples with one Compensating Box (FloatingGround Measurement)
Note The maximum permissible common mode voltage (VCM v + 1V) must not be exceeded at any of the differential inputs with reference to MA.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-11
8
Page 192
Analog Modules
Floating-Ground Measurement
 Â
The figure below illustrates the connection of thermocouples of different types with one compensating box per channel (floating-ground measurement):
A x.3 . x.1 . V
Ä Ä Ä x.2 . x.4 . M.A
C
ÂÂ ÂÂ . . V
C
K+ K–
MA
A
A
TB8
K+
0.3 0.4
1.3 1.4
MA L+ L+
K–
0.1 0.2
1.1 1.2
MA M M
.
. Shield + 24V Comp. box
Comp. box
Thermal link
UCM v"1V Max. 75 V DC/60 V AC PE
8
Figure 8-7
Max. 75 V DC/ 60 V AC MA
Mexternal
Connection of Thermocouples with one Compensating Box per Channel (Floating-Ground Measurement)
Note The maximum permissible common mode voltage (VCM v + 1V) must not be exceeded at any of the differential inputs with reference to MA
8-12
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 193
Analog Modules
GroundReferenced Measurement
The figure below illustrates the connection of thermocouples of the same type with one compensating box for the entire module (ground-referenced measurement):
Ä ÄÄ Ä
C x.2 x.4 M . .A x.3 . x.1 .
D
V
V
C
C
TB8
K+
0.3 0.4
1.3 1.4
MA L+ L+
K–
0.1 0.2
1.1 1.2
MA M M
D K+ .
. MA
í K–
.
. Shield + 24V Comp. box
. .
. .
Thermal link
Max. 75 V DC/60 V AC PE Figure 8-8
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Max. 75 V DC/ 60 V AC MA
Mexternal
Connection of Thermocouples with one Compensating Box (Ground-Referenced Measurement)
8
8-13
Page 194
Analog Modules
Connection of Resistance Thermometers/ Resistors (2-Wire Connection)
If resistance thermometers or resistors are connected, resistance can be measured by means of a 2-wire connection. The resistance thermometer/resistor receives a constant current supply via terminals x.1 and x.2. Voltage drops on the measuring lines may falsify the results. This type of measurement is useful if the measuring lines are short and thick or when the requirements for measuring accuracy are low. Figures 8-9 and 8-10 show the two methods of connecting resistance thermometers and resistors in a 2-wire connection, taking a Pt 100 by way of example. A maximum of 4 resistance thermometers (Pt 100, Ni 100) or resistors can be connected.
Floating-Ground Measurement
The connection of resistance thermometers (Pt 100) with 2-wire connections (floating-ground measurement) is shown below:
Ä Ä Ä
B x.2 . x.4 .
x.3 . x.1 .
B
B
TB8
K+
0.3 0.4
1.3 1.4
MA L+ L+
K–
0.1 0.2
1.1 1.2
MA M M
C
í
. Shield 8
+ 24V
Pt 100
Pt 100 VCM v"1V
Max. 75 V DC/60 V AC PE Figure 8-9
Max. 75 V DC/ 60 V AC MA
Mexternal
Connection of Resistance Thermometers (Pt 100) with 2-Wire Connections (Floating-Ground Measurement)
Note The maximum permissible common mode voltage (VCM v "1V) must not be exceeded at any of the differential inputs with reference to MA.
8-14
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 195
Analog Modules
GroundReferenced Measurement
In the case of ground-referenced measurement, you must connect terminal x.4 externally with analog ground (MA). The connection of resistance thermometers (Pt 100) with 2-wire connections (ground-referenced measurement) is shown below:
B
Ä Ä Ä x.2 x.4 .
x.3 x.1 . í
B
B
TB8
K+
0.3 0.4
1.3 1.4
MA L+ L+
K–
0.1 0.2
1.1 1.2
MA M M
C
. Ext. connection . Shield + 24V
Pt 100
Pt 100
Max. 75 V DC/60 V AC PE
Max. 75 V DC/ 60 V AC MA
Mexternal
Figure 8-10 Connection of Resistance Thermometers (Pt 100) with 2-Wire Connections (Ground-Referenced Measurement)
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-15
8
Page 196
Analog Modules
Connection of Resistance Thermometers (4-Wire Connection)
If resistance thermometers or resistors are connected, resistance can be measured by means of a 4-wire connection. A constant current Ic is fed to the resistance thermometer via terminals x.1 and x.2. The voltage generated at the resistance thermometer is measured via x.3/x.4. This means that voltage drops on the “constant current lines” do not corrupt the result of the measurement. The measurement inputs have a high resistance so that only a negligible voltage drop occurs on the measuring lines. Figures 8-11 and 8-12 show the two methods of connecting resistance thermometers and resistors in a 4-wire connection, taking a Pt 100 by way of example.
Floating-Ground Measurement
The connection of resistance thermometers (Pt 100) with 4-wire connections (floating-ground measurement) is shown below:
Ä Ä Ä
A x.2 . x.4 . MA x.3 . x.1 .
.
.
í
C
A
A
TB8
K+
0.3 0.4
1.3 1.4
MA L+ L+
K–
0.1 0.2
1.1 1.2
MA M M
.
. Shield
8
IC
+ 24V IC
. . . . Pt 100
Pt 100 UCM v"1V
Max. 75 V DC/60 V AC PE
Max. 75 V DC/ 60 V AC MA
Mexternal
Figure 8-11 Connection of Resistance Thermometers (Pt 100) with 4-Wire Connections (Floating-Ground Measurement)
Note The maximum permissible common mode voltage (VCM v "1V) must not be exceeded at any of the differential inputs with reference to MA.
8-16
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 197
Analog Modules
GroundReferenced Measurement
The connection of resistance thermometers (Pt 100) with 4-wire connections (ground-referenced measurement) is shown below:
Ä Ä Ä
D x.2 . x.4 . MA x.3 . x.1 .
.
.
í
C
D
D
TB8
K+
0.3 0.4
1.3 1.4
MA L+ L+
K–
0.1 0.2
1.1 1.2
MA M M
.
. Shield IC
+ 24V IC
. . . . Pt 100
Pt 100
Max. DC 75V/AC 60V PE
Max. DC 75V/ AC 60V MA
Mexternal
Figure 8-12 Connection of Resistance Thermometers (Pt 100) with 4-Wire Connections (Ground-Referenced Measurement)
8
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-17
Page 198
Analog Modules
Connection of Voltage Sensors
The channels can also be used to connect voltage sensors (" 80 mV, " 250 mV, " 500 mV, " 1000 mV). Two voltage sensors per channel group can be connected. Figures 8-13 and 8-14 show the two methods of connecting voltage sensors.
Floating-Ground Measurement
Two-wire connection of voltage sensors (floating-ground measurement) is shown below:
Ä Ä Ä Ä Ä Ä
A x.3 . x.1 . V x.2 . x.4 . M.A V
C
A
A
TB8
K+
0.3 0.4
1.3 1.4
MA L+ L+
K–
0.1 0.2
1.1 1.2
MA M M
. Shield + 24V + +
U U
–
+
–
+
U U
– – VCMv"1V
8
Max. 75 V DC/60 V AC PE
Max. 75 V DC/ 60 V AC MA
Mexternal
Figure 8-13 2-Wire Connection of Voltage Sensors to ET 200B-4/8AI (Floating-Ground Measurement)
Note The maximum permissible common mode voltage (VCM v "1V) must not be exceeded at any of the differential inputs with reference to MA.
8-18
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 199
Analog Modules
GroundReferenced Measurement x.3 . x.1 . V
Two-wire connection of voltage sensors (ground-referenced measurement) is shown below:
Ä Ä Ä
C x.2 x.4 M . . .A
C
C
C
TB8
K+
0.3 0.4
1.3 1.4
MA L+ L+
K–
0.1 0.2
1.1 1.2
MA M M
V
. Shield + 24V + +
U U
–
+
–
+
U U
– –
Max. 75 V DC/60 V AC PE
Max. 75 V DC/ 60 V AC MA
Mexternal
Figure 8-14 2-Wire Connection of Voltage Sensors to ET 200B-4/8AI (Ground-Referenced Measurement)
8
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-19
Page 200
Analog Modules
8.4.2
Configuration Options
Type File
The information in this section applies to the type file SI801ABE.200. The type file contains the possible configurations. The configuration you choose depends on the wiring of the module.
Configuration for Voltage Sensors, Thermocouples
Table 8-5 shows the possible configurations of the ET 200B-4/8AI with COM ET 200 Windows or STEP 7 for connecting voltage sensors and thermocouples. Table 8-5 lists only the slots for configuring the input areas (slots 4 to 11). Slots 1 to 3 have the default value ”004”.
Table 8-5
Configuration
Possible Configurations for the Input Areas of ET 200B-4/8AI, with only Voltage Sensors and Thermocouples Connected Length1 (in Channel group 0 Channel group 1 Channel group 2 Channel group 3 words) Chan- Chan- Chan- Chan- Chan- Chan- Chan- Channel 0 nel 1 nel 2 nel 3 nel 4 nel 5 nel 6 nel 7 Terminals used
0.1/0.2
0.3/0.4
1.1/1.2
1.3/1.4
2.1/2.2
2.3/2.4
3.0/3.1
Meaning
3.3/3.4
8AI
8
A start address is assigned for the entire module, addresses for8words arereserved. (= module addressing)
8 x 1AI
8
7 x 1AI
7
6 x 1AI
6
5 x 1AI
5
4 x 1AI
4
A separate start address can be assigned for each channel. (= singlechannel addressing)
3 x 1AI
3
2 x 1AI
2
1 x 1AI
1
8
1
Length of user data;
= Connection of measuring lines
Note If you connect voltage sensors/thermocouples and resistors/thermal resistors to the same module, you have a mixed configuration as shown in Tables 8-5 and 8-6 (see example below).
8-20
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c