Page 181
8
Analog Modules
Introduction
There are a number of analog modules for connecting measured-value sensors and loads/actuators.
In this Chapter
This chapter contains the technical data for the analog modules. The technical data for each analog module is accompanied by details of the measured-value sensors and loads that can be connected, information on analog-value display for operation with SIMATIC S5 and S7, a list of permissible address IDs, and the parameters of the analog modules. In Section
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c you will find on Page
8.1
Analog modules
8-2
8.2
Terminal block TB8 (6ES7 193-0CD40-0XA0)
8-3
8.3
Terminal block TB8 and bus connector
8-4
8.4
Electronics block ET 200B-4/8AI (6ES7 134-0KH01-0XB0)
8-5
8.5
Electronics block ET 200B-4AI (6ES7 134-0HF01-0XB0)
8-51
8.6
Electronics block ET 200B-4AO (6ES7 135-0HF01-0XB0)
8-76
8-1
Page 182
Analog Modules
8.1
Analog Modules
Introduction
The tables below give an overview of the ET 200B analog modules.
List of Electronics Blocks
The following types of electronics block are available: Table 8-1
Analog Electronics Blocks of ET 200B
Electronics block
List of Terminal Blocks
ET 200B-4/8AI
8 analog differential inputs or 8 thermocouples, 4 resistance measurement, 4 resistance thermometer (PT 100, Ni 100) (measuring principle: integrating)
ET 200B-4AI
4 analog differential inputs (measuring principle: successive approximation)
ET 200B-4AO
4 analog outputs
A single terminal block is available for all analog electronics blocks: Table 8-2
Analog Terminal Block of ET 200B
Terminal block
8
TB8
8-2
Description
Description 4/8-channel, spring-latch terminals
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 183
Analog Modules
8.2
Terminal Block TB8 (6ES7 193-0CD40-0XA0)
Dimensional Drawing, TB8
Dimensional drawing: terminal block TB8 (spring-latch terminals)
Mounting holes
8 Figure 8-1
Dimensional Drawing: Terminal Block TB8 (Spring-Latch Terminals)
Terminal Numbering
Figure 8-2 is an enlargement of the terminal numbering printed on the TB8 (spring-latch terminals).
Coding plug
Figure 8-2
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Terminal Numbering: Terminal Block TB8 (Spring-Latch Terminals)
8-3
Page 184
Analog Modules
8.3
Terminal Block TB8 and Bus Connector
Dimensional Drawing
Figure 8-3 contains the dimensional drawings (side elevation) of the terminal block TB8 with electronics block installed and two different bus connectors.
6ES7 972-0BA10-0XB0
Figure 8-3
8
8-4
6ES7 972-0BB10-0XB0
Dimensional Drawing: Side Elevation with Bus Connectors (6ES7 972-0BA10-0XA0 and 6ES7 972-0BB10-0XA0)
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 185
Analog Modules
8.4
Electronics Block ET 200B-4/8AI (6ES7 134-0KH01-0XB0)
Characteristics
The ET 200B-4/8AI electronics block has the following characteristics:
8 inputs in 4 channel groups, galvanically isolated from voltage supply to the internal logic
Transducers supported: – Thermocouples: types E, J, K, L, N, T, U – Resistance thermometers: Pt 100, Ni 100 – Resistors: 48 W, 150 W, 300 W, 600 W – Voltage sensors: mV, mV, 500 mV, mV (2-wire connection)
Measuring principle: integrating Integration times: 2.5 ms, 16.7 ms, 20 ms, 100 ms Supply voltage: 24 V DC Measured-value range selection via COM ET 200 or STEP 7 or directly via parameterization telegram (see Chapter 4)
Dimensional Drawing
Dimensional drawing of the ET 200B-4/8AI:
8
Figure 8-4
Dimensional Drawing: ET 200B-4/8AI (6ES7 134-0KH01-0XB0)
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-5
Page 186
Analog Modules
Terminal Numbering
Figure 8-5 is an enlargement of the terminal numbering printed on the ET 200B-4/8AI.
Figure 8-5
List of Subsections
Connection Diagram: ET 200B-4/8AI (6ES7 134-0KH01-0XB0)
The following aspects of the ET 200B-4/8AI are described below: In Section you will find on Page
8.4.1
Connecting transducers
8-7
8.4.2
Configuration options
8-20
8.4.3
Setting the operating mode
8-23
8.4.4
Analog-value representation, operation with SIMATIC S5
8-26
8.4.5
Analog-value representation, operation with SIMATIC S7
8-39
8.4.6
Schematic circuit diagram, terminal assignment and technical data
8-47
8
8-6
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 187
Analog Modules
8.4.1
Connecting Transducers
Possible Connections
You can connect the following to the ET 200B-4/8AI electronics block:
Up to 8 thermocouples with compensating box Up to 4 resistance thermometers in 2-wire or 4-wire connection Up to 4 resistors in 2-wire or 4-wire connection Up to 8 voltage sensors (2-wire connection) Mixed configurations with different types of sensor are possible.
Channel Group
A channel group consists of two channels set with the parameterization software COM ET 200 or STEP 7 (diagnostics enable, measurement type, measuring range, etc.) and with the coding plug on the TB8 (input circuit). The settings of a channel group apply to all the channels in the group in question.
Input Circuit
There are two ways of measuring analog signals from thermocouples, resistance thermometers, resistors and voltage transducers:
Floating-ground measurement Ground-referenced measurement You set the input circuit for floating-ground or ground-referenced measurement by means of the coding plugs on the TB8 (one coding plug per channel group)
Floating-Ground Measurement
In the case of floating-ground measurement (differential measurement), each signal line has its own signal reference conductor. Differential measurement is required in the following cases:
If the sensors are connected to different potentials and If the different signal sources are physically apart. Note The maximum permissible common mode voltage (VCM) of the differential inputs to analog ground (MA) is The maximum permissible voltage difference between MA and PE must not exceed 75 V DC/60 V AC. Avoid ground loops!
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
8-7
8
Page 188
Analog Modules
GroundReferenced Measurement
In the case of ground-referenced measurement, all signal reference conductors in the TB8 are connected to a common reference point (analog ground MA). To avoid ground loops, galvanically isolated and ungrounded signal sources (thermocouples, Pt 100, voltage sources) are required. Note Connect MA to PE ( ) to enhance noise immunity in the case of groundreferenced measurement.
Connecting Thermocouples with Compensating Boxes
The ET 200B-4/8AI does not have an internal compensating box. The influence of temperature on the reference junction can be countered with a compensating box. Please note the following rules when connecting a compensating box:
In a configuration with external compensation you need only one compensating box for all the thermocouples of a single type (E, J, K, L, N, T, U) in a module. Connect the compensating box to terminals K+ and K- (see for example Figure 8-6).
In a configuration with external compensation you can connect a maximum of 4 different thermocouples (a different type of thermocouple for each channel group) if you use a separate compensating box for each connection.
8
In this case the unused K+ and K- terminals must be connected to MA. (see Figure 8-7)
In a configuration with external compensation and one compensating box per channel the same thermocouple type must be used per channel group.
The compensating box requires a floating power supply. The power supply unit of the compensating box must have a grounded braided shield. Figures 8-6 to 8-8 illustrate the connection options for thermocouples. A maximum of 8 thermocouples can be connected. Valid Compensating Boxes
We recommend the following compensating boxes for connection to the ET 200B-4/8AI:
Compensating box type U with current stabilizer. Reference junction with built-in power supply unit.
8-8
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 189
Analog Modules
Order Numbers
The order numbers of the compensating boxes and the associated components can be found in the tables below. Table 8-3
Compensating Box Type U with Current Stabilizer. Accessories
Weight
Order Number
Type U compensating box Reference temp. 20 °C (68 °F)³ 0 mV 0 °C (32 °F)³ 0 mV
0.22 kg (7.7 oz.) 0.22 kg (7.7 oz.)
C70153-A502-A1 C70153-A502-A5
Insert for type U compensating box (as spare part and for installation in distribution boxes or similar) Reference temp. 20 °C (68 °F)³ 0 mV 0 °C (32 °F)³ 0 mV
0.09 kg (3.15 oz.) 0.09 kg (3.15 oz.)
C70153-A502-B7 C70153-A502-B9
Current stabilizer for feeding a compensating box for thermocouple Fe/Cu Ni, Ni Cr/Ni Reference temp. 20 °C (68 °F)³ 0 mV 0 °C (32 °F)³ 0 mV
0.25 kg (8.75 oz.) 0.25 kg (8.75 oz.)
M55232-A1 M55232-A2
Table 8-4
Reference Junction with Built-in Power Supply Unit Accessories
Order Number
Reference junction with built-in power supply unit for busbar installation
Auxiliary energy
220 V AC 110 V AC 24 V AC 24 V DC
Connection to thermocouple Fe-CuNi Type L Fe/Cu Ni Type J Ni Cr/Ni Type K Cu-CuNi Type U Cu/Cu Ni Type T Reference temperature
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
0 °C 20 °C
B1 B2 B3 B4
8 1 2 3 6 7 00 20
8-9
Page 190
Analog Modules
On the Following Pages
The following pages contain a connection example for every connection possibility and measuring principle. Please note the following rules.
Rules
Please note the following rules when connecting measured-value sensors to the ET 200B-4/8AI:
The permissible potential difference at the differential input (x.1 ´ x.2 or x.3 ´ x.4, x = 0 to 3) must not exceed +1 V.
The maximum permissible common mode voltage (VCM) between the differential inputs (x.1 ´ x.2, x.3 ´ x.4, x = 0 to 3) and analog ground MA is + 1 V.
The maximum permissible isolation voltage between analog ground (MA) and PE ( ) or between the reference potential of the supply voltage (M) is 75 V DC/60 V AC.
You must short-circuit the connection terminals of unused voltage inputs and connect them to MA. If the coding plug is in the C position, the connection to MA is not required (already jumpered internally).
If you connect only one voltage sensor (2-wire connection) to one channel, you must also short-circuit the remaining free differential input of the channel group and connect it to MA. If the coding plug is in the C position, the connection to MA is not required (already jumpered internally).
If you connect a compensating box, you must short-circuit terminals “K+” and “K-”. For this purpose, set the coding plug to the “C” position.
8
Note Please note the explanation of shielding of analog lines in Sections 3.1 and 3.5.
8-10
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c