SIMATIC ET 200B Distributed I/O Station Manual: 7 Digital Modules, pages 177 to 180

Pages 177 to 180 of 344, from SIMATIC ET 200B Distributed I/O Station Manual

The original document is the PDF (2.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Siemens ET 200B

Page 177

Digital Modules

Pin Assignment

Table 7-17

The table below shows the pin assignment of the terminal blocks for ET 200B-8DI/8RO-AC. For the sake of clarity, the table also shows the terminal numbering of the terminal blocks, taking the TB6/AC by way of example.

Pin Assignment of Terminal Block TB6/AC for ET 200B-8DI/8RO-AC (6ES7 133-0HH00-0XB0)

Terminal numbering TB6/AC

Terminal tier 1

Terminal tier 2 Sensor voltage 1L1 for channel I0: .0 to .3

Terminal tier 3 65

Sensor voltage 1N for channel I0: .0 to .3

1

I0: Input .0

33

2

I0: Input .1

34

3

I0: Input .2

35

67

4

I0: Input .3

36

68

5 not used

37

69

6 not used

38

70

7 not used

39

71

8 not used

40 not used

72 not used

9 not used

41 not used

73 not used

10 not used

42 not used

43

Sensor voltage 2L1 for channel I0: .4 to .7

74

11

Sensor voltage 2N for channel I0: .4 to .7

12 not used

44

76

13

I0: Input .4

45

77

14 15

I0: Input .5 I0: Input .6

46 47

78 79

16

I0: Input .7

48

66

75

7

80 Q0: Output 0/0

17

Q0: Output 0/1

49

81 not used

18

Q0: Output 1/0

50

82 not used

19

Q0: Output 1/1

51

83 not used

20

Q0: Output 2/0

52

84 not used

21

Q0: Output 2/1

53

85 not used

22

Q0: Output 3/0

54

86 not used

23

Q0: Output 3/1

55

87 not used

24 not used

56 not used

88 not used

25 not used

57 not used

89 not used

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7-91

Page 178

Digital Modules

Table 7-17

Pin Assignment of Terminal Block TB6/AC for ET 200B-8DI/8RO-AC (6ES7 133-0HH00-0XB0), continued

Terminal tier 1

Terminal tier 2

26

Q0: Output 4/1

58

27

Q0: Output 4/0

28 29

Q0: Output 7/0

Terminal tier 3 90 not used

59

91 not used

Q0: Output 5/1

60

92 not used

Q0: Output 5/0

61

93 not used

30

Q0: Output 6/1

62

94 not used

31

Q0: Output 6/0

63

95 not used

32

Q0: Output 7/1

64

96 not used

-

L1

Voltage supply, internal logic

N

Voltage supply, internal logic

-

L1

Voltage supply, internal logic

N

Voltage supply, internal logic

Important Note on Wiring

The following notes are important as regards the wiring of the ET 200B-8DI/8RO-AC:

S If installed in an 230 V AC system with ambient temperatures in excess of 40 _C only 6 inputs can be used and rated input current must not exceed AC 240 V.

S If installed in an 230 V AC system, the following must always be connected to the same outer conductor (same phase):

7

– 1L1/1N and 2L1/2N (same phase) – 3L1/3N and 4L1/4N (same phase)

S Protect the module against inductive voltage surges at the relay contacts. Suitable surge protectors are RC elements or varistors connected across the relay contact or across the load. The size and ratings of the protective elements must be dimensioned to suit the size and type of load.

S Voltage surge protectors of this kind extend the service life of the relay contacts.

7-92

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 179

Digital Modules

Technical Data

The technical data of electronics block ET 200B-8DI/8RO-AC is listed in the tables below.

Technical specifications Baud rates*

Inputs 9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud

Bus protocol

PROFIBUS-DP

Galvanic isolation to SINEC L2-DP bus

Yes, 500 V DC to logic, 1500 V AC to connection terminals

Power losses

13 W

Weight (EB and TB)

811 g (29 oz)

Dimensions (EB and TB: W x H x D)

235 x 130 x 60 mm (9.17 x 5.07 x 2.34 in.)

Diagnostics functions Voltage monitoring

Green LED ‘‘RUN”

Bus monitoring SINEC L2-DP

Red LED ‘‘BF”

Group diagnostics for short-circuit, load voltage failure

No

Load voltage monitoring

No

Status of outputs

Green LEDs

Supply voltage for internal logic Supply voltage L1 Rated value Permissible range Frequency Current consumption from L1 *

Number of inputs

8

Galvanic isolation In groups of

Yes (optocouplers) 4

Input voltage Rated value For ‘‘0” signal For ‘‘1” signal Input current for ‘‘1” signal at 120, 60 Hz at 230 V, 50 Hz

120/230 V AC 0 to 40 V AC 79 to 264 V AC 3 to 16 mA Typ. 6.5 mA Typ. 10.5 mA

Type of input acc. to IEC 1131

Type 1

Delay of inputs

0 to 25 ms

Connection of 2-wire BERO Permissible quiescent current

No

Connection of mechanical switches

Yes

Cable length of sensors Cable length

2 mA

7 Max. 600 m (1968 ft.)

Relay outputs 120/230 V AC, 85 to 264 V AC 47 to 63 Hz Typ. 165 mA

In operation with the IM 308-B, the maximum baud rate is 1500 kbaud.

Number of outputs High current Low current

2 (0.0, 0.7) 6 (0.1 to 0.6)

Galvanic isolation In groups of

Yes (relays) 1

Short-circuit protection Relay type Output voltage Rated value

No Takamisawa NY 24W-K

Permissible range Continuous current Ith

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

24 to 150 V DC 120 V AC 0.1 to 150 V DC 79 to 150 V AC Max. 4 A (for high current points) Max. 2 A (for low current points)

7-93

Page 180

Digital Modules

Relay outputs, continued Switching capacity of contacts S High current points Resistive load 0 to 40 _C (32 to 104 _ F) 24 V DC/ 4A 120/230 V AC 120 V DC 0.2 A Inductive load 24 V DC/ 2A 120/230 V AC 120 V DC 0.2 A S Low current points Resistive and inductive 0 to 40 _C loads (32 to 104 _ F) 24 V DC/ 2A 120/230 V AC 120 V DC 0.2 A

7

60 _C (140_ F) 2A 0.2 A

2A 0.2 A

60 _C (140_ F) 1A 0.2 A

Switching cycles of contacts acc. to VDE 0660, Part 200 S DC-11 S AC-15

> 100 x 106 > 300 x 105

Switching frequency S Resistive load S Inductive load

Max. 10 Hz Max. 2 Hz

Cable length

Max. 600 m (1968 ft.)

Setting a digital input

Possible

7-94

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c