Page 177
Digital Modules
Pin Assignment
Table 7-17
The table below shows the pin assignment of the terminal blocks for ET 200B-8DI/8RO-AC. For the sake of clarity, the table also shows the terminal numbering of the terminal blocks, taking the TB6/AC by way of example.
Pin Assignment of Terminal Block TB6/AC for ET 200B-8DI/8RO-AC (6ES7 133-0HH00-0XB0)
Terminal numbering TB6/AC
Terminal tier 1
Terminal tier 2 Sensor voltage 1L1 for channel I0: .0 to .3
Terminal tier 3 65
Sensor voltage 1N for channel I0: .0 to .3
1
I0: Input .0
33
2
I0: Input .1
34
3
I0: Input .2
35
67
4
I0: Input .3
36
68
5 not used
37
69
6 not used
38
70
7 not used
39
71
8 not used
40 not used
72 not used
9 not used
41 not used
73 not used
10 not used
42 not used
43
Sensor voltage 2L1 for channel I0: .4 to .7
74
11
Sensor voltage 2N for channel I0: .4 to .7
12 not used
44
76
13
I0: Input .4
45
77
14 15
I0: Input .5 I0: Input .6
46 47
78 79
16
I0: Input .7
48
66
75
7
80 Q0: Output 0/0
17
Q0: Output 0/1
49
81 not used
18
Q0: Output 1/0
50
82 not used
19
Q0: Output 1/1
51
83 not used
20
Q0: Output 2/0
52
84 not used
21
Q0: Output 2/1
53
85 not used
22
Q0: Output 3/0
54
86 not used
23
Q0: Output 3/1
55
87 not used
24 not used
56 not used
88 not used
25 not used
57 not used
89 not used
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
7-91
Page 178
Digital Modules
Table 7-17
Pin Assignment of Terminal Block TB6/AC for ET 200B-8DI/8RO-AC (6ES7 133-0HH00-0XB0), continued
Terminal tier 1
Terminal tier 2
26
Q0: Output 4/1
58
27
Q0: Output 4/0
28 29
Q0: Output 7/0
Terminal tier 3 90 not used
59
91 not used
Q0: Output 5/1
60
92 not used
Q0: Output 5/0
61
93 not used
30
Q0: Output 6/1
62
94 not used
31
Q0: Output 6/0
63
95 not used
32
Q0: Output 7/1
64
96 not used
-
L1
Voltage supply, internal logic
N
Voltage supply, internal logic
-
L1
Voltage supply, internal logic
N
Voltage supply, internal logic
Important Note on Wiring
The following notes are important as regards the wiring of the ET 200B-8DI/8RO-AC:
S If installed in an 230 V AC system with ambient temperatures in excess of 40 _C only 6 inputs can be used and rated input current must not exceed AC 240 V.
S If installed in an 230 V AC system, the following must always be connected to the same outer conductor (same phase):
7
– 1L1/1N and 2L1/2N (same phase) – 3L1/3N and 4L1/4N (same phase)
S Protect the module against inductive voltage surges at the relay contacts. Suitable surge protectors are RC elements or varistors connected across the relay contact or across the load. The size and ratings of the protective elements must be dimensioned to suit the size and type of load.
S Voltage surge protectors of this kind extend the service life of the relay contacts.
7-92
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 179
Digital Modules
Technical Data
The technical data of electronics block ET 200B-8DI/8RO-AC is listed in the tables below.
Technical specifications Baud rates*
Inputs 9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud
Bus protocol
PROFIBUS-DP
Galvanic isolation to SINEC L2-DP bus
Yes, 500 V DC to logic, 1500 V AC to connection terminals
Power losses
13 W
Weight (EB and TB)
811 g (29 oz)
Dimensions (EB and TB: W x H x D)
235 x 130 x 60 mm (9.17 x 5.07 x 2.34 in.)
Diagnostics functions Voltage monitoring
Green LED ‘‘RUN”
Bus monitoring SINEC L2-DP
Red LED ‘‘BF”
Group diagnostics for short-circuit, load voltage failure
No
Load voltage monitoring
No
Status of outputs
Green LEDs
Supply voltage for internal logic Supply voltage L1 Rated value Permissible range Frequency Current consumption from L1 *
Number of inputs
8
Galvanic isolation In groups of
Yes (optocouplers) 4
Input voltage Rated value For ‘‘0” signal For ‘‘1” signal Input current for ‘‘1” signal at 120, 60 Hz at 230 V, 50 Hz
120/230 V AC 0 to 40 V AC 79 to 264 V AC 3 to 16 mA Typ. 6.5 mA Typ. 10.5 mA
Type of input acc. to IEC 1131
Type 1
Delay of inputs
0 to 25 ms
Connection of 2-wire BERO Permissible quiescent current
No
Connection of mechanical switches
Yes
Cable length of sensors Cable length
2 mA
7 Max. 600 m (1968 ft.)
Relay outputs 120/230 V AC, 85 to 264 V AC 47 to 63 Hz Typ. 165 mA
In operation with the IM 308-B, the maximum baud rate is 1500 kbaud.
Number of outputs High current Low current
2 (0.0, 0.7) 6 (0.1 to 0.6)
Galvanic isolation In groups of
Yes (relays) 1
Short-circuit protection Relay type Output voltage Rated value
No Takamisawa NY 24W-K
Permissible range Continuous current Ith
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
24 to 150 V DC 120 V AC 0.1 to 150 V DC 79 to 150 V AC Max. 4 A (for high current points) Max. 2 A (for low current points)
7-93
Page 180
Digital Modules
Relay outputs, continued Switching capacity of contacts S High current points Resistive load 0 to 40 _C (32 to 104 _ F) 24 V DC/ 4A 120/230 V AC 120 V DC 0.2 A Inductive load 24 V DC/ 2A 120/230 V AC 120 V DC 0.2 A S Low current points Resistive and inductive 0 to 40 _C loads (32 to 104 _ F) 24 V DC/ 2A 120/230 V AC 120 V DC 0.2 A
7
60 _C (140_ F) 2A 0.2 A
2A 0.2 A
60 _C (140_ F) 1A 0.2 A
Switching cycles of contacts acc. to VDE 0660, Part 200 S DC-11 S AC-15
> 100 x 106 > 300 x 105
Switching frequency S Resistive load S Inductive load
Max. 10 Hz Max. 2 Hz
Cable length
Max. 600 m (1968 ft.)
Setting a digital input
Possible
7-94
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c