For the Siemens ET 200B
Page 167
Digital Modules
Pin Assignment
Table 7-15
The table below shows the pin assignment of the terminal blocks for ET 200B-16DO-AC. For the sake of clarity, the table also shows the terminal numbering of the terminal blocks, taking the TB6/AC by way of example.
Pin Assignment of Terminal Block TB6/AC for ET 200B-16DO-AC (6ES7 132-0HF00-0XB0)
Terminal numbering TB6/AC
Terminal tier 1
Terminal tier 2 Voltage supply 1L1 for channel Q0: .0 to .3
Terminal tier 3 65
Voltage supply 1N for channel Q0: .0 to .3
1
Q0: Output .0
33
2
Q0: Output .1
34
3
Q0: Output .2
35
67
4
Q0: Output .3
36
68
5 not used
37
69
6 not used
38
70
7 not used
39
71
8 not used
40 not used
72 not used
66
7
9 not used
41 not used
73 not used
10 not used
42
74
11 not used
43
Voltage supply 2L1 for channel Q0: .4 to .7
Voltage supply 2N for channel Q0: .4 to .7
12 not used
44
76
13
Q0: Output .4
45
77
14
Q0: Output .5
46
78
15
Q0: Output .6
47
79
16
Q0: Output .7
48
80
17
Q1: Output .0
49
18
Q1: Output .1
50
19
Q1: Output .2
51
83
20
Q1: Output .3
52
84
21 not used
53
85
22 not used
54
86
23 not used
55
87
24 not used
56 not used
88 not used
25 not used
57 not used
89 not used
26 not used
58
Voltage supply 4L1 for channel Q1: .4 to .7
90
Voltage supply 4N for channel Q1: .4 to .7
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Voltage supply 3L1 for channel Q1: .0 to .3
75
81 82
Voltage supply 3N for channel Q1: .0 to .3
7-81
Page 168
Digital Modules
Table 7-15
Pin Assignment of Terminal Block TB6/AC for ET 200B-16DO-AC (6ES7 132-0HF00-0XB0), continued
Terminal tier 1
Terminal tier 2 Voltage supply 4L1 for channel Q1: .4 to .7
Terminal tier 3
27 not used
59
91
28 not used
60
29
Q1: Output .4
61
93
30
Q1: Output .5
62
94
31
Q1: Output .6
63
95
32
Q1: Output .7
64
96
92
Voltage supply 4N for channel Q1: .4 to .7
-
L1
Voltage supply, internal logic
N
Voltage supply, internal logic
-
L1
Voltage supply, internal logic
N
Voltage supply, internal logic
Important Note on Wiring
The following notes are important as regards the wiring of the ET 200B-16DO-AC:
If installed in an AC 230 V system, the following must always be connected to the same outer conductor (same phase): – 1L1/1N and 2L1/2N (same phase) – 3L1/3N and 4L1/4N (same phase)
7
7-82
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 169
Digital Modules
Technical Data
The technical data of electronics block ET 200B-16DO-AC is listed in the tables below.
Technical specifications Baud rates*
Outputs 9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud
Number of outputs
16
Bus protocol
PROFIBUS-DP
Galvanic isolation S In groups of
S Signal voltage
Yes (optocouplers) 4 79 to 264 V AC
Galvanic isolation to SINEC L2-DP bus
Yes, 500 V DC to logic, 1500 V AC to connection terminals
Power losses
Max. 11 W
Weight (EB and TB)
Approx. 805 g (29 oz)
Output voltage S For ‘‘1” signal (w50 mA) S For ‘‘1” signal (v50 mA)
235 x 130 x 60 mm (9.17 x 5.07 x 2.34 in.)
Output current S For ‘‘0” signal Delay of outputs
Max. 1.3 mA Max. 20 ms
Short-circuit protection
No
Switching frequency S Resistive load S Inductive load S Lamp load
10 Hz 0.5 Hz 1 Hz
Dimensions (EB and TB: W x H x D) Diagnostics functions Voltage monitoring
Green ‘‘RUN‘‘ LED
Bus monitoring SINEC L2-DP
Red ‘‘BF” LED
Group diagnostics for short-circuit, load voltage failure
No
Load voltage monitoring
No
Status of outputs
Green LEDs
Supply voltage for internal logic Supply voltage L1 S Rated value S Permissible range S Frequency S Current consumption from L1 *
120/230 V AC 85 to 264 V AC 47 to 63 Hz Typ. 150 mA
In operation with the IM 308-B, the maximum baud rate is 1500 kbaud.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Load current per output in preferred mounting position S 0 _C to 40 _C (32 _ F to 104 _ F) S 40 _C to 60 _C (32 _ F to 140 _ F) Load current per output in other mounting positions S 0 _C to 40 _C (32 _ F to 104 _ F) Lamp load Size of motor starter Parallel connection of 2 outputs
Max. L1 – 1.5 V Max. L1 – 8.5 V
7
0.5 A 0.35 A
0.35 A Max. 25 W Max. size 3 acc. to NEMA
Setting a digital input
Possible (though not in order to increase power) Possible
Cable length
Max. 600 m (1968 ft)
7-83
Page 170
Digital Modules
7.3.13
Electronics Block ET 200B-16RO-AC (6ES7 132-0HH00-0XB0)
Characteristics
The ET 200B-16RO-AC electronics block has the following characteristics:
16 relay outputs, floating in groups of 1 Load voltage: 120 V AC 24 ... 150 V DC
Output current: 4A for outputs 0.0, 0.7, 1.0 and 1.7 12 A for outputs 0.1 to 0.6 and 1.1 to 1.6
Suitable for AC/DC solenoid valves, switches, motor starters, smallpower motors, motors and lamps.
Possible terminal block: TB6/AC Dimensional Drawing
See Figure 7-22 for the precise dimensions.
7
Ć16RO-AC
Figure 7-54 Front Elevation: ET 200B-16RO-AC (6ES7 132-0HH00-0XB0)
7-84
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 171
Digital Modules
Block Diagram
Simplified diagram of the potential for the ET 200B-16RO-AC and TB6/DC:
ET 200B-16RO-AC
PROFIBUS-DP
Galvanic isolation
120/ 230 5V V
Logic
16x
24 V M24
AB
L1 N Interface between electronics block and terminal block
X1 TB6/AC
120/ 230 24 V V
5VM
Station number selection
Conn. PROFIBUS-DP
PE
Suppr. logic/fuse N
L1
Contact N conductor
Screw for grounding (see Sec. 3.4)
Relay outputs
120/230 V AC supply
Figure 7-55 Block Diagram: ET 200B-16RO-AC (6ES7 132-0HH00-0XB0) and TB6/AC
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
7-85
7
Page 172
Digital Modules
Pin Assignment
Table 7-16
The table below shows the pin assignment of the terminal blocks for ET 200B-16RO-AC. For the sake of clarity, the table also shows the terminal numbering of the terminal blocks, taking the TB6/AC by way of example.
Pin Assignment of Terminal Block TB6/AC for ET 200B-16RO-AC (6ES7 132-0HH00-0XB0)
Terminal numbering TB6/AC
Terminal tier 1
7
Terminal tier 2
1 2
Q0: Connection 0/1
33
Q0: Connection 1/0
3
Q0: Connection 1/1
4
Q0: Connection 0/0
Terminal tier 3 65 not used
34
66 not used
35
67 not used
Q0: Connection 2/0
36
68 not used
5
Q0: Connection 2/1
37
69 not used
6
Q0: Connection 3/0
38
70 not used
7
Q0: Connection 3/1
39
71 not used
8 not used
40 not used
71 not used
9 not used
41 not used
73 not used
10
Q0: Connection 4/1
42
Q0: Connection 7/0
74 not used
11
Q0: Connection 4/0
43
75 not used
12
Q0: Connection 5/1
44
76 not used
13
Q0: Connection 5/0
45
77 not used
14
Q0: Connection 6/1
46
78 not used
15
Q0: Connection 6/0
47
79 not used
16
Q0: Connection 7/1
48
80 not used
17
Q1: Connection 0/0
49
81 not used
18
Q1: Connection 1/0
50
82 not used
19
Q1: Connection 1/1
51
83 not used
20
Q1: Connection 2/0
52
84 not used
21
Q1: Connection 2/1
53
85 not used
22
Q1: Connection 3/0
54
86 not used
23
Q1: Connection 3/1
55
87 not used
24 not used
56 not used
88 not used
25 not used
57 not used
89 not used
26
Q1: Connection 4/1
58
Q1: Connection 7/0
90 not used
7-86
Q1: Connection 0/0
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 173
Digital Modules
Table 7-16
Pin Assignment of Terminal Block TB6/AC for ET 200B-16RO-AC (6ES7 132-0HH00-0XB0), continued
Terminal tier 1
Terminal tier 2
27
Q1: Connection 4/0
59
28
Q1: Connection 5/1
29 30
Q1: Connection 7/0
Terminal tier 3 91 not used
60
92 not used
Q1: Connection 5/0
61
93 not used
Q1: Connection 6/1
62
94 not used
31
Q1: Connection 6/0
63
95 not used
32
Q1: Connection 7/1
64
96 not used
-
L1
Voltage supply, internal logic
N
Voltage supply, internal logic
-
L1
Voltage supply, internal logic
N
Voltage supply, internal logic
Important Note on Wiring
The following notes are important as regards the wiring of the ET 200B-16RO-AC:
Protect the module against inductive voltage surges at the relay contacts. Suitable surge protectors are RC elements or varistors connected across the relay contact or across the load. The size and ratings of the protective elements must be dimensioned to suit the size and type of load.
Voltage surge protectors of this kind extend the service life of the relay contacts.
7
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
7-87
Page 174
Digital Modules
Technical Data
The technical data of electronics block ET 200B-16RO-AC is listed in the tables below.
Technical specifications Baud rates*
Bus protocol
Relay outputs 9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud PROFIBUS-DP
Galvanic isolation to SINEC L2-DP bus
Yes, 500 V DC to logic, 1500 V AC to connection terminals
Power losses
20 W
Weight (EB and TB)
814 g (29 oz)
Dimensions (EB and TB: W x H x D)
235 x 130 x 60 mm (9.17 x 5.09 x 2.34 in.)
Voltage monitoring
Green ‘‘RUN” LED
Bus monitoring SINEC L2-DP
Red ‘‘BF” LED
Group diagnostics for short-circuit, load voltage failure
No
Load voltage monitoring
No
Status of outputs
Green LEDs
Supply voltage for internal logic Supply voltage L1 S Rated value S Permissible range S Frequency S Current consumption from L1 *
120/230 V AC 85 to 264 V AC 47 to 63 Hz Typ. 210 mA
In operation with the IM 308-B, the maximum baud rate is 1500 kbaud.
7-88
4 (0.0, 0.7, 1.0 and 1.7) 12 (0.1 to 0.6, 1.1 to 1.6)
Galvanic isolation S In groups of
Yes (relays) 1
Short-circuit protection Relay type
No Takamisawa NY 24 W-K
Output voltage S Rated value
S Permissible range Continuous current Ith
Diagnostics functions
7
Number of outputs S High current S Low current
24 to 150 V DC 120 V AC 0,1 to 150 V DC 79 to 150 V AC Max. 4 A (for high current points) Max. 2 A (for low current points)
Switching capacity of contacts S High current points Resistive load 0 to 40 _C 60 _C (32 to 104 _ F) (140_ F) 24 V DC/120 V AC 4A 2A 120 V DC 0.2 A 0.2 A Inductive load 24 V DC/120 V AC 2A 2A 120 V DC 0.2 A 0.2 A S Low current points Resistive and 0 to 40 _C 60 _C inductive loads (32 to 104 _ F) (140_ F) 24 V DC/120 V AC 2A 1A 120 V DC 0.2 A 0.2 A Switching cycles of contacts acc. to VDE 0660, Part 200 S DC-11 S AC-15 u100 x 106 u300 x 105
Switching frequency S Resistive load S Inductive load
Max. 10 Hz Max. 2 Hz
Cable length Setting a digital input
Max. 600 m (1968 ft.) Possible
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 175
Digital Modules
7.3.14
Electronics Block ET 200B-8DI/8RO-AC (6ES7 133-0HH00-0XB0)
Characteristics
The ET 200B-8DI/8RO-AC electronics block has the following characteristics:
8 inputs, floating in groups of 4 8 relay outputs, floating in groups of 1 Input voltage: 120/230 V AC Inputs suitable for switches and 2-wire proximity switches acc. to IEC 1131, type 1
8 relay outputs, floating in groups of 1 Output load voltage:
120 V AC 24 ... 150 V DC
Output current: 4 A for outputs 0.0 and 0.7 2 A for outputs 0.1 to 0.6
Outputs suitable for AC/DC solenoid valves, switches, motor starters, small-power motors, motors and lamps.
Possible terminal block: TB6/AC Dimensional Drawing
See Figure 7-22 for the precise dimensions.
7
Figure 7-56 Front Elevation: ET 200B-8DI/8RO-AC (6ES7 133-0HH00-0XB0)
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
7-89
Page 176
Digital Modules
Block Diagram
Simplified diagram of the potential for the ET 200B-8DI/8RO-AC and TB6/DC:
ET 200B-8DI/ 8RO-AC
120/ 230 24 V V
Galvanic isolation TxD RxD Logic
PROFIBUS DP 9
+–
4x
120/ 230 5V V
+–
4x 8x
24 V M24 X1 TB6/AC
AB 5 VM
I0: I0: 1N 4...7 2N 0...3 Interface between electronics block and terminal block Station number selection
1N 1L1 Conn. PROFI- Volt. sens. BUS-DP N cond. Screw for grounded configuration PE (see Section 3.4)
7
L1 N
Suppr. logic/fuse 2N 2L1 L1
Digital inputs
Relay outputs
N
120/230 V AC supply
Figure 7-57 Block Diagram: ET 200B-8DI/8RO-AC (6ES7 133-0HH00-0XB0) and TB6/AC
7-90
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c