Page 157

Digital Modules

Pin Assignment

Table 7-13

The table below shows the pin assignment of the terminal blocks for ET 200B-24DI/8DO and ET 200B-24DI/8DO 0.2 ms. For the sake of clarity, the table also shows the terminal numbering of the terminal blocks, taking the TB2-4/DC by way of example.

Pin Assignment of Terminal Blocks TB2/DC; TB2-4/DC and TB4/DC for ET 200B-24DI/8DO (6ES7 133-0BN01-0XB0) and ET 200B-24DI/8DO 0.2ms (6ES7 133-0BN11-0XB0)

Terminal numbering TB2-4/DC

Terminal tier 1

Terminal tier 2 Voltage supply L1+ for channel group Q0: .0 to .7

1

Q0: Output .0

33

2

Q0: Output .1

34

3

Q0: Output .2

35

67

4

Q0: Output .3

36

68

5

Q0: Output .4

37

69

6

Q0: Output .5

38

70

7

Q0: Output .6

39

71

8

Q0: Output .7

40

72

9

I0: Input .0

41

10

I0: Input .1

42

11

I0: Input .2

43

75

12

I0: Input .3

44

76

13

I0: Input .4

45

77

14

I0: Input .5

46

78

15

I0: Input .6

47

79

16

I0: Input .7

48

80

17

I1: Input .0

49

81

18

I1: Input .1

50

82

19

I1: Input .2

51

83

20

I1: Input .3

52

84

21

I1: Input .4

53

85

22

I1: Input .5

54

86

23

I1: Input .6

55

87

24

I1: Input .7

56

88

25

I2: Input .0

57

89

26

I2: Input .1

58

90

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

24 V (sensor voltage, connected to L5+)

65 66

73 74

Terminal tier 3

Terminal tier 41

Ground M1 for channel group Q0: .0 to .7

PE (internally jumpered, but not connected to PE screw)

7 Ground (sensor voltage, connected to M5)

7-71

Page 158

Digital Modules

Table 7-13

Pin Assignment of Terminal Blocks TB2/DC; TB2-4/DC and TB4/DC for ET 200B-24DI/8DO (6ES7 133-0BN01-0XB0) and ET 200B-24DI/8DO 0.2ms (6ES7 133-0BN11-0XB0), continued Terminal tier 2

Terminal tier 1

1

24 V (sensor voltage, connected to L5+)

27

I2: Input .2

59

91

28

I2: Input .3

60

29 30

I2: Input .4 I2: Input .5

61 62

93 94

31

I2: Input .6

63

95

32

I2: Input .7

92

Terminal tier 3

Terminal tier 41

Ground (sensor voltage, connected to M5)

PE (internally jumpered, but not connected to PE screw)

PE (internally jumpered, but not connected to PE screw)

64

96

–

L5+ Voltage supply, internal logic and sensor voltage 24 V

M5 Ground connection, internal logic and sensor voltage

–

L5+ Voltage supply, internal logic and sensor voltage 24 V

M5 Ground connection, internal logic and sensor voltage

TB2-4/DC only; in the TB4M/DC tier 4 is available for additional ground connections (see Section 7.2.7)

Important Note on Wiring

The following notes are important as regards the wiring of the ET 200B-24DI/8DO and ET 200B-24DI/8DO 0.2 ms:

The terminals for PE on the 4-tier terminal block are not connected to the PE connection of terminal block TB2-4/DC.

7

If all actuators are connected by two-wire cables to the TB2/DC, TB4/DC or TB2-4/DC, connect the ground of an actuator and the supply for the reference potential per group by means of a DIN 46231 cable cleat.

L1+ and L5+ and M1 and M5 are not interconnected. L5+ and terminals 41 ... 64 are interconnected, as are M5 and terminals 73 ... 96.

The two L5+ terminals are also interconnected. Fuse

7-72

The 24 V sensor supply is protected by fuse F1 (2.5 A) in the terminal blocks. Nevertheless, make sure that the current does not exceed the specifications in the technical data for the electronics block.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 159

Digital Modules

Technical Data

The technical data of electronics blocks ET 200B-24DI/8DO and ET 200B-24DI/8DO 0.2 ms is listed in the tables below.

Technical specifications

Inputs, continued

Baud rates*

9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud

Bus protocol

PROFIBUS-DP

FREEZE and SYNC capa- Yes* bility

Delay of inputs for 6ES7 133-0BN00-0XB0

3 ms

Delay of inputs for 6ES7 133-0BN10-0XB0

0.2 ms Possible

Possible

Galvanic isolation to SINEC L2-DP bus

Yes

Connection of 2-wire BERO Quiescent current

Power losses

Max. 5.5 W

Connection of mechanical switches

Weight (EB and TB)

Approx. 800 g (28 oz.)

Cable length of sensors Unshielded

235 x 130 x 60 mm (9.17 x 5.07 x 2.34 in.)

Outputs

Dimensions (EB and TB: W x H x D) Diagnostics functions Voltage monitoring

Green “RUN” LED

Bus monitoring SINEC L2-DP

Red “BF” LED

Group diagnostics for short-circuit, load voltage failure

Red “DIA” LED

Load voltage monitoring

Green “L1+” LED

Status of inputs and outputs

Green LEDs

Supply voltage for sensor supply, load voltage supply and internal logic Supply voltage (L1+,L5+) Rated value Permissible range Value for t < 0.5 s

24 V DC 18.5 to 30.2 V 35 V

Current consumption from L5+ Logic Typ. 85 mA Sensors Max. 1 A I2t (for the inrush current) < 0.05 A2s Inputs Number of inputs

24

Galvanic isolation to inter- No nal electronic circuits Input voltage Rated value For “0” signal For “1” signal

24 V DC – 30 V to 5 V 13 V to 30 V

Input current for “1” signal

Typ. 4 mA at 24 V Min. 2 mA

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c v 1.5 mA

Max. 100 m (328 ft.)

Number of outputs

8

Galvanic isolation In groups of

Yes 8

Output voltage For “0” signal For “1” signal

Max. 2 V (idle) Min. (supply voltage – 3 V)

Output current For “0” signal For “1” signal

Max. 1 mA Max. 0.5 A

Delay of outputs From “0” to “1” From “1” to “0”

Approx. 20 Max. 0.5 ms

Switching frequency Resistive load Inductive load Lamp load

Max. 1000 Hz Max. 0.5 Hz Max. 8 Hz

Short-circuit protection

Yes

Load current Total current

Max. 2 A

Lamp load

Max. 5 W

Setting a digital input

Possible

Limitation of voltage induced on current interruption

Typ. (L5+) – 55 V

Cable length

Max. 100 m (328 ft.)

*

7

In operation with the IM 308-B, the maximum baud rate is1500 kbaud.

7-73

Page 160

Digital Modules

7.3.11

Electronics Block ET 200B-16DI-AC (6ES7 131-0HF00-0XB0)

Characteristics

The ET 200B-16DI-AC electronics block has the following characteristics:

16 inputs, floating in groups of 4 Input voltage: 120/230 V AC Suitable for switches and 2-wire proximity switches acc. to IEC 1131, type 1

Possible terminal block: TB6/AC Dimensional Drawing

See Figure 7-22 for the precise dimensions.

7

Figure 7-50 Front Elevation: ET 200B-16DI-AC (6ES7 131-0HF00-0XB0)

7-74

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 161

Digital Modules

Block Diagram

Simplified diagram of the potential for the ET 200B-16DI-AC and TB6/AC:

ET 200B-16DI-AC

120/ 230 24 V V

Galvanic isolation

PROFIBUS-DP

120/ 230 5V V

Logic

+–

+–

4x

24 V M24 X1 TB6/AC

AB 5 VM

+–

4x

+–

4x

4x

I0: I0: I1: I1: 1N4...7 2N 0...3 3N4...7 4N 0...3 Interface between electronics block and terminal block Station number selection

Suppr. logic/fuse

Conn.

Input Voltage sensor N conductor

PROFIBUS-DP

PE

L1 N

1L1 1N

Screw for grounding (see Sec. 3.4)

2L1 2N

3L1 3N

Digital inputs

4L1 4N

N

L1

120/230 V AC supply

Figure 7-51 Block Diagram: ET 200B-16DI-AC (6ES7 131-0HF00-0XB0) and TB6/AC

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7-75

7

Page 162

Digital Modules

Pin Assignment

Table 7-14

The table below shows the pin assignment of the terminal blocks for ET 200B-16DI-AC. For the sake of clarity, the table also shows the terminal numbering of the terminal block, taking the TB6/AC by way of example.

Pin Assignment of Terminal Block TB6/AC for ET 200B-16DI-AC (6ES7 131-0HF00-0XB0)

Terminal numbering TB6/AC

Terminal tier 1

7

Terminal tier 2 Sensor voltage 1L1 for channel I0: .0 to .3

Terminal tier 3 65

Sensor voltage 1N for channel I0: .0 to .3

1

I0: Input .0

33

2

I0: Input .1

34

3

I0: Input .2

35

67

4

I0: Input .3

36

68

5 not used

37

69

6 not used

38

70

7 not used

39

71

8 not used

40 not used

72 not used

9 not used

41 not used

73 not used

10 not used

42

Sensor voltage 2L1 for channel I0: .4 to .7

74

Sensor voltage 2N for channel I0: .4 to .7

66

11 not used

43

12 not used

44

76

13 14

I0: Input .4 I0: Input .5

45 46

77 78

15

I0: Input .6

47

79

16

I0: Input .7

48

80

17

I1: Input .0

49

18

I1: Input .1

50

19

I1: Input .2

51

83

20

I1: Input .3

52

84

21 not used

53

85

22 not used

54

86

23 not used

55

87

24 not used

56 not used

88 not used

25 not used

57 not used

89 not used

26 not used

58

Sensor voltage 4L1 for channel I1: .4 to .7

90

Sensor voltage 4N for channel I1: .4 to .7

7-76

Sensor voltage 3L1 for channel I1: .0 to .3

75

81 82

Sensor voltage 3N for channel I1: .0 to .3

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 163

Digital Modules

Table 7-14

Pin Assignment of Terminal Block TB6/AC for ET 200B-16DI-AC (6ES7 131-0HF00-0XB0), continued

Terminal tier 1

Terminal tier 2 Sensor voltage 4L1 for channel I1: .4 to .7

Terminal tier 3

27 not used

59

91

28 not used

60

29

I1: Input .4

61

93

30

I1: Input .5

62

94

31

I1: Input .6

63

95

32

I1: Input .7

64

96

92

Sensor voltage 4N for channel I1: .4 to .7

-

L1

Voltage supply, internal logic

N

Voltage supply, internal logic

-

L1

Voltage supply, internal logic

N

Voltage supply, internal logic

Important Note on Wiring

The following notes are important as regards the wiring of the ET 200B-16DI-AC:

S If installed in an 230 V AC system, the following must always be connected to the same outer conductor (same phase): – 1L1/1N and 2L1/2N (same phase) – 3L1/3N and 4L1/4N (same phase)

S If installed in an 230 V AC system with ambient temperatures in excess of 40 _C only 12 inputs can be used and rated input current must not exceed 240 V AC.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7-77

7

Page 164

Digital Modules

Technical Data

The technical data of electronics block ET 200B-16DI-AC is listed in the tables below.

Technical specifications

Inputs

Baud rates*

9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud

Bus protocol

PROFIBUS-DP

Galvanic isolation to SINEC L2-DP

Yes, 500 V DC to logic, 1500 V AC to connection terminals

Power losses at 230 V at 120 V Weight (EB and TB)

Typ. 6 W Typ. 4.5 W 811 g (29 oz.)

Dimensions (EB and TB: W x H x D)

235 x 130 x 60 mm (9.17 x 5.07 x 2.34 in.)

Diagnostics functions

7

Voltage monitoring

Green ‘‘RUN” LED

Bus monitoringSINEC L2-DP

Red ‘‘BF” LED

Status of inputs

Green LEDs

Supply voltage for internal logic Supply voltage L1 Rated value Permissible range Frequency Current consumption from L1

7-78

120/230 V AC 85 to 264 V AC 47 to 63 Hz Typ. 60 mA

Number of inputs Galvanic isolation In groups of Input voltage Rated value For ‘‘0” signal For ‘‘1” signal Input current for ‘‘1” signal At 120 V, 60 Hz At 230 V, 50 Hz Type of input acc. to IEC 1131 Delay of inputs Connection of 2-wire BERO Permissible quiescent current Connection of mechanical switches Cable length *

16 Yes (optocouplers) 4 120/230 V AC 0 to 40 V AC 79 to 264 V AC 3 to 16 mA Typ. 6.5 mA Typ. 10.5 mA Type 1 0 to 25 ms No 2 mA Yes Max. 600 m (1968 ft)

In operation with the IM 308-B, the maximum baud rate is 1500 kbaud.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 165

Digital Modules

7.3.12

Electronics Block ET 200B-16DO-AC (6ES7 132-0HF00-0XB0)

Characteristics

The ET 200B-16DO-AC electronics block has the following characteristics:

16 outputs, floating in groups of 4 Output current: 0.5 A Load voltage: 120/230 V AC Possible terminal block: TB6/AC Dimensional Drawing

See Figure 7-22 for the precise dimensions.

7

Figure 7-52 Front Elevation: ET 200B-16DO-AC (6ES7 132-0HF00-0XB0)

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7-79

Page 166

Digital Modules

Block Diagram

Simplified diagram of the potential for the ET 200B-16DO-AC and TB6/AC:

ET 200B-16DO-AC

120/ 230 24 V V

Galvanic isolation

PROFIBUS-DP

120/ 230 5V V

Logic

4x

24 V M24 X1 TB6/AC

AB 5VM

PROFIBUS-DP

PE

4x

4x

Q0: Q0: Q1: Q1: 0...3 1L1 4...7 2L1 0...3 3L1 4...7 Interface between electronics block and terminal block Station number selection

Conn.

7

4x

Out. Supply

N conductor Screw for grounding (see Sec. 3.4)

L1 N

4L1

Suppr. logic/fuse 1L1 1N

2L1 2N

3L1 3N

4L1 4N

Digital outputs

L1

N

120/230 V AC supply

Figure 7-53 Block Diagram: ET 200B-16DO-AC (6ES7 132-0HF00-0XB0) and TB6/AC

7-80

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c