SIMATIC ET 200B Distributed I/O Station Manual: 7 Digital Modules, pages 157 to 166
Pages 157 to 166 of 344, from SIMATIC ET 200B Distributed I/O Station Manual
The original document is the PDF (2.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens ET 200B
Page 157
Digital Modules
Pin Assignment
Table 7-13
The table below shows the pin assignment of the terminal blocks for ET 200B-24DI/8DO and ET 200B-24DI/8DO 0.2 ms. For the sake of clarity, the table also shows the terminal numbering of the terminal blocks, taking the TB2-4/DC by way of example.
Pin Assignment of Terminal Blocks TB2/DC; TB2-4/DC and TB4/DC for ET 200B-24DI/8DO (6ES7 133-0BN01-0XB0) and ET 200B-24DI/8DO 0.2ms (6ES7 133-0BN11-0XB0)
Terminal numbering TB2-4/DC
Terminal tier 1
Terminal tier 2 Voltage supply L1+ for channel group Q0: .0 to .7
1
Q0: Output .0
33
2
Q0: Output .1
34
3
Q0: Output .2
35
67
4
Q0: Output .3
36
68
5
Q0: Output .4
37
69
6
Q0: Output .5
38
70
7
Q0: Output .6
39
71
8
Q0: Output .7
40
72
9
I0: Input .0
41
10
I0: Input .1
42
11
I0: Input .2
43
75
12
I0: Input .3
44
76
13
I0: Input .4
45
77
14
I0: Input .5
46
78
15
I0: Input .6
47
79
16
I0: Input .7
48
80
17
I1: Input .0
49
81
18
I1: Input .1
50
82
19
I1: Input .2
51
83
20
I1: Input .3
52
84
21
I1: Input .4
53
85
22
I1: Input .5
54
86
23
I1: Input .6
55
87
24
I1: Input .7
56
88
25
I2: Input .0
57
89
26
I2: Input .1
58
90
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
24 V (sensor voltage, connected to L5+)
65 66
73 74
Terminal tier 3
Terminal tier 41
Ground M1 for channel group Q0: .0 to .7
PE (internally jumpered, but not connected to PE screw)
7 Ground (sensor voltage, connected to M5)
7-71
Page 158
Digital Modules
Table 7-13
Pin Assignment of Terminal Blocks TB2/DC; TB2-4/DC and TB4/DC for ET 200B-24DI/8DO (6ES7 133-0BN01-0XB0) and ET 200B-24DI/8DO 0.2ms (6ES7 133-0BN11-0XB0), continued Terminal tier 2
Terminal tier 1
1
24 V (sensor voltage, connected to L5+)
27
I2: Input .2
59
91
28
I2: Input .3
60
29 30
I2: Input .4 I2: Input .5
61 62
93 94
31
I2: Input .6
63
95
32
I2: Input .7
92
Terminal tier 3
Terminal tier 41
Ground (sensor voltage, connected to M5)
PE (internally jumpered, but not connected to PE screw)
PE (internally jumpered, but not connected to PE screw)
64
96
–
L5+ Voltage supply, internal logic and sensor voltage 24 V
M5 Ground connection, internal logic and sensor voltage
–
L5+ Voltage supply, internal logic and sensor voltage 24 V
M5 Ground connection, internal logic and sensor voltage
TB2-4/DC only; in the TB4M/DC tier 4 is available for additional ground connections (see Section 7.2.7)
Important Note on Wiring
The following notes are important as regards the wiring of the ET 200B-24DI/8DO and ET 200B-24DI/8DO 0.2 ms:
The terminals for PE on the 4-tier terminal block are not connected to the PE connection of terminal block TB2-4/DC.
7
If all actuators are connected by two-wire cables to the TB2/DC, TB4/DC or TB2-4/DC, connect the ground of an actuator and the supply for the reference potential per group by means of a DIN 46231 cable cleat.
L1+ and L5+ and M1 and M5 are not interconnected. L5+ and terminals 41 ... 64 are interconnected, as are M5 and terminals 73 ... 96.
The two L5+ terminals are also interconnected. Fuse
7-72
The 24 V sensor supply is protected by fuse F1 (2.5 A) in the terminal blocks. Nevertheless, make sure that the current does not exceed the specifications in the technical data for the electronics block.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 159
Digital Modules
Technical Data
The technical data of electronics blocks ET 200B-24DI/8DO and ET 200B-24DI/8DO 0.2 ms is listed in the tables below.
Technical specifications
Inputs, continued
Baud rates*
9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud
Bus protocol
PROFIBUS-DP
FREEZE and SYNC capa- Yes* bility
Delay of inputs for 6ES7 133-0BN00-0XB0
3 ms
Delay of inputs for 6ES7 133-0BN10-0XB0
0.2 ms Possible
Possible
Galvanic isolation to SINEC L2-DP bus
Yes
Connection of 2-wire BERO Quiescent current
Power losses
Max. 5.5 W
Connection of mechanical switches
Weight (EB and TB)
Approx. 800 g (28 oz.)
Cable length of sensors Unshielded
235 x 130 x 60 mm (9.17 x 5.07 x 2.34 in.)
Outputs
Dimensions (EB and TB: W x H x D) Diagnostics functions Voltage monitoring
Green “RUN” LED
Bus monitoring SINEC L2-DP
Red “BF” LED
Group diagnostics for short-circuit, load voltage failure
Red “DIA” LED
Load voltage monitoring
Green “L1+” LED
Status of inputs and outputs
Green LEDs
Supply voltage for sensor supply, load voltage supply and internal logic Supply voltage (L1+,L5+) Rated value Permissible range Value for t < 0.5 s
24 V DC 18.5 to 30.2 V 35 V
Current consumption from L5+ Logic Typ. 85 mA Sensors Max. 1 A I2t (for the inrush current) < 0.05 A2s Inputs Number of inputs
24
Galvanic isolation to inter- No nal electronic circuits Input voltage Rated value For “0” signal For “1” signal
24 V DC – 30 V to 5 V 13 V to 30 V
Input current for “1” signal
Typ. 4 mA at 24 V Min. 2 mA
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c v 1.5 mA
Max. 100 m (328 ft.)
Number of outputs
8
Galvanic isolation In groups of
Yes 8
Output voltage For “0” signal For “1” signal
Max. 2 V (idle) Min. (supply voltage – 3 V)
Output current For “0” signal For “1” signal
Max. 1 mA Max. 0.5 A
Delay of outputs From “0” to “1” From “1” to “0”
Approx. 20 Max. 0.5 ms
Switching frequency Resistive load Inductive load Lamp load
Max. 1000 Hz Max. 0.5 Hz Max. 8 Hz
Short-circuit protection
Yes
Load current Total current
Max. 2 A
Lamp load
Max. 5 W
Setting a digital input
Possible
Limitation of voltage induced on current interruption
Typ. (L5+) – 55 V
Cable length
Max. 100 m (328 ft.)
*
7
In operation with the IM 308-B, the maximum baud rate is1500 kbaud.
7-73
Page 160
Digital Modules
7.3.11
Electronics Block ET 200B-16DI-AC (6ES7 131-0HF00-0XB0)
Characteristics
The ET 200B-16DI-AC electronics block has the following characteristics:
16 inputs, floating in groups of 4 Input voltage: 120/230 V AC Suitable for switches and 2-wire proximity switches acc. to IEC 1131, type 1
Possible terminal block: TB6/AC Dimensional Drawing
See Figure 7-22 for the precise dimensions.
7
Figure 7-50 Front Elevation: ET 200B-16DI-AC (6ES7 131-0HF00-0XB0)
7-74
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 161
Digital Modules
Block Diagram
Simplified diagram of the potential for the ET 200B-16DI-AC and TB6/AC:
ET 200B-16DI-AC
120/ 230 24 V V
Galvanic isolation
PROFIBUS-DP
120/ 230 5V V
Logic
+–
+–
4x
24 V M24 X1 TB6/AC
AB 5 VM
+–
4x
+–
4x
4x
I0: I0: I1: I1: 1N4...7 2N 0...3 3N4...7 4N 0...3 Interface between electronics block and terminal block Station number selection
Suppr. logic/fuse
Conn.
Input Voltage sensor N conductor
PROFIBUS-DP
PE
L1 N
1L1 1N
Screw for grounding (see Sec. 3.4)
2L1 2N
3L1 3N
Digital inputs
4L1 4N
N
L1
120/230 V AC supply
Figure 7-51 Block Diagram: ET 200B-16DI-AC (6ES7 131-0HF00-0XB0) and TB6/AC
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
7-75
7
Page 162
Digital Modules
Pin Assignment
Table 7-14
The table below shows the pin assignment of the terminal blocks for ET 200B-16DI-AC. For the sake of clarity, the table also shows the terminal numbering of the terminal block, taking the TB6/AC by way of example.
Pin Assignment of Terminal Block TB6/AC for ET 200B-16DI-AC (6ES7 131-0HF00-0XB0)
Terminal numbering TB6/AC
Terminal tier 1
7
Terminal tier 2 Sensor voltage 1L1 for channel I0: .0 to .3
Terminal tier 3 65
Sensor voltage 1N for channel I0: .0 to .3
1
I0: Input .0
33
2
I0: Input .1
34
3
I0: Input .2
35
67
4
I0: Input .3
36
68
5 not used
37
69
6 not used
38
70
7 not used
39
71
8 not used
40 not used
72 not used
9 not used
41 not used
73 not used
10 not used
42
Sensor voltage 2L1 for channel I0: .4 to .7
74
Sensor voltage 2N for channel I0: .4 to .7
66
11 not used
43
12 not used
44
76
13 14
I0: Input .4 I0: Input .5
45 46
77 78
15
I0: Input .6
47
79
16
I0: Input .7
48
80
17
I1: Input .0
49
18
I1: Input .1
50
19
I1: Input .2
51
83
20
I1: Input .3
52
84
21 not used
53
85
22 not used
54
86
23 not used
55
87
24 not used
56 not used
88 not used
25 not used
57 not used
89 not used
26 not used
58
Sensor voltage 4L1 for channel I1: .4 to .7
90
Sensor voltage 4N for channel I1: .4 to .7
7-76
Sensor voltage 3L1 for channel I1: .0 to .3
75
81 82
Sensor voltage 3N for channel I1: .0 to .3
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 163
Digital Modules
Table 7-14
Pin Assignment of Terminal Block TB6/AC for ET 200B-16DI-AC (6ES7 131-0HF00-0XB0), continued
Terminal tier 1
Terminal tier 2 Sensor voltage 4L1 for channel I1: .4 to .7
Terminal tier 3
27 not used
59
91
28 not used
60
29
I1: Input .4
61
93
30
I1: Input .5
62
94
31
I1: Input .6
63
95
32
I1: Input .7
64
96
92
Sensor voltage 4N for channel I1: .4 to .7
-
L1
Voltage supply, internal logic
N
Voltage supply, internal logic
-
L1
Voltage supply, internal logic
N
Voltage supply, internal logic
Important Note on Wiring
The following notes are important as regards the wiring of the ET 200B-16DI-AC:
S If installed in an 230 V AC system, the following must always be connected to the same outer conductor (same phase): – 1L1/1N and 2L1/2N (same phase) – 3L1/3N and 4L1/4N (same phase)
S If installed in an 230 V AC system with ambient temperatures in excess of 40 _C only 12 inputs can be used and rated input current must not exceed 240 V AC.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
7-77
7
Page 164
Digital Modules
Technical Data
The technical data of electronics block ET 200B-16DI-AC is listed in the tables below.
Technical specifications
Inputs
Baud rates*
9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud
Bus protocol
PROFIBUS-DP
Galvanic isolation to SINEC L2-DP
Yes, 500 V DC to logic, 1500 V AC to connection terminals
Power losses at 230 V at 120 V Weight (EB and TB)
Typ. 6 W Typ. 4.5 W 811 g (29 oz.)
Dimensions (EB and TB: W x H x D)
235 x 130 x 60 mm (9.17 x 5.07 x 2.34 in.)
Diagnostics functions
7
Voltage monitoring
Green ‘‘RUN” LED
Bus monitoringSINEC L2-DP
Red ‘‘BF” LED
Status of inputs
Green LEDs
Supply voltage for internal logic Supply voltage L1 Rated value Permissible range Frequency Current consumption from L1
7-78
120/230 V AC 85 to 264 V AC 47 to 63 Hz Typ. 60 mA
Number of inputs Galvanic isolation In groups of Input voltage Rated value For ‘‘0” signal For ‘‘1” signal Input current for ‘‘1” signal At 120 V, 60 Hz At 230 V, 50 Hz Type of input acc. to IEC 1131 Delay of inputs Connection of 2-wire BERO Permissible quiescent current Connection of mechanical switches Cable length *
16 Yes (optocouplers) 4 120/230 V AC 0 to 40 V AC 79 to 264 V AC 3 to 16 mA Typ. 6.5 mA Typ. 10.5 mA Type 1 0 to 25 ms No 2 mA Yes Max. 600 m (1968 ft)
In operation with the IM 308-B, the maximum baud rate is 1500 kbaud.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 165
Digital Modules
7.3.12
Electronics Block ET 200B-16DO-AC (6ES7 132-0HF00-0XB0)
Characteristics
The ET 200B-16DO-AC electronics block has the following characteristics:
16 outputs, floating in groups of 4 Output current: 0.5 A Load voltage: 120/230 V AC Possible terminal block: TB6/AC Dimensional Drawing
See Figure 7-22 for the precise dimensions.
7
Figure 7-52 Front Elevation: ET 200B-16DO-AC (6ES7 132-0HF00-0XB0)
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
7-79
Page 166
Digital Modules
Block Diagram
Simplified diagram of the potential for the ET 200B-16DO-AC and TB6/AC:
ET 200B-16DO-AC
120/ 230 24 V V
Galvanic isolation
PROFIBUS-DP
120/ 230 5V V
Logic
4x
24 V M24 X1 TB6/AC
AB 5VM
PROFIBUS-DP
PE
4x
4x
Q0: Q0: Q1: Q1: 0...3 1L1 4...7 2L1 0...3 3L1 4...7 Interface between electronics block and terminal block Station number selection
Conn.
7
4x
Out. Supply
N conductor Screw for grounding (see Sec. 3.4)
L1 N
4L1
Suppr. logic/fuse 1L1 1N
2L1 2N
3L1 3N
4L1 4N
Digital outputs
L1
N
120/230 V AC supply
Figure 7-53 Block Diagram: ET 200B-16DO-AC (6ES7 132-0HF00-0XB0) and TB6/AC
7-80
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c