SIMATIC ET 200B Distributed I/O Station Manual: 7 Digital Modules, pages 147 to 156
Pages 147 to 156 of 344, from SIMATIC ET 200B Distributed I/O Station Manual
The original document is the PDF (2.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens ET 200B
Page 147
Digital Modules
Technical Data
The technical data of electronics block ET 200B-8DI/8DO HWA is listed in the tables below.
Technical Data
Inputs (continued)
Baud rates*
9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud
Bus protocol
PROFIBUS-DP
FREEZE and SYNC capa- Yes bility Galvanic isolation to SINEC L2-DP bus
Yes
Power losses
Max. 3.8 W
Weight (EB and TB)
Approx. 650 g
Dimensions (EB and TB: W x H x D)
Input current for “1” signal
Typ. 4 mA at 24 V Min. 2 mA
Delay of inputs
3 ms
Connection of 2-wire BERO Quiescent current
Possible
Connection of mechanical switches Cable length of sensors Unshielded
Possible v 1.5 mA
Max. 100 m (328 ft.)
Outputs 160 x 130 x 60
Number of outputs
8
Voltage monitoring
Green “RUN” LED
Galvanic isolation In groups of
No 8
Bus monitoring SINEC L2-DP
Red “BF” LED
Group diagnostics for short-circuit, load voltage failure
Red “DIA” LED
Load voltage monitoring
Green “L1+” LED
Status of inputs and outputs
Green LEDs
Diagnostics functions
Supply voltage for sensor supply, load voltage supply and internal logic Supply voltage (L1+,L3+) Rated value Permissible range Value for t < 0.5 s
24 V DC 18.5 ... 30.2 V 35 V
Current consumption from L3+ Logic Typ. 70 mA Sensors Max. 500 mA I2t (for the inrush current) Inputs v 0.05 A2s
Number of inputs
8
Galvanic isolation to inter- No nal electronic circuits Input voltage Rated value For “0” signal For “1” signal
Output voltage For “0” signal For “1” signal Output current For “0” signal For “1” signal Delay of outputs From “0” to “1” From “1” to “0” By hardware cutoff Switching frequency Resistive load Inductive load Lamp load
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
7
Max. 1 mA Max. 0.5 A Typ. 50 Typ. 100 3 ms Max. 100 Hz Max. 0.5 Hz Max. 8 Hz
Short-circuit protection
Yes
Load current Total current
Max. 2 A
Lamp load
Max. 5 W
Setting a digital input
Possible
Limit of inductive cutoff voltage
Typ. (L1+) – 55 V
Cable length
Max. 100 m (328 ft.)
* 24 V DC – 30 V ... 5 V 13 V ... 30 V
Max. 2 V (idle) Min. (supply voltage – 3 V)
In operation with the IM 308-B, the maximum baud rate is1500 kbaud.
7-61
Page 148
Digital Modules
7.3.9
Electronics Block ET 200B-16DI/16DO (6ES7 133 0BL00-0XB0)
Characteristics
The ET 200B-16DI/16DO has the following characteristics:
16 inputs, non-floating 16 outputs, floating in groups of 8 Input voltage: 24 V DC Input delay: 3 ms Load voltage: 24 V DC Possible terminal blocks: TB2/DC, TB2-4/DC, TB4/DC, TB4M/DC Dimensional Drawing
See Figure 7-22 for the precise dimensions.
7
Figure 7-44 Front Elevation: ET 200B-16DI/16DO (6ES7 133-0BL00-0XB0)
7-62
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 149
Digital Modules
Block Diagram
Simplified diagram of the potential for the ET 200B-16DI/16DO and TB2/DC or TB4/DC:
ET 200B-16DI/16DO
24 V
PROFIBUS-DP
5V 24 V Logic
5V
+– Driver
Driver
I0: 0...7 8x 8x 16x I1: 0...7 Q0: Q1: 0...7 0...7 L1+ M1 L2+ M2 Interface between electronics block and terminal block
X1 TB2/DC or TB4/DC
Station number selection Connection PROFIBUS-DP M5
PE
I/O Supply/Voltage sensor Ground Screw for grounding (see Sec. 3.4)
Suppr. logic L1+M1
Suppr. logic STOP/RUN switch
Suppr. logic
L5+ M5
L2+M2
Digital outputs
L5+ M5
Digital inputs
24 V supply
Figure 7-45 Block Diagram: ET 200B-16DI/16DO (6ES7 133-0BL00-0XB0) and TB2/DC or TB4/DC
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
7-63
7
Page 150
Digital Modules
Block Diagram
Simplified diagram of the potential for the ET 200B-16DI/16DO and TB2-4/DC:
ET 200B-16DI/16DO
24 V
PROFIBUS-DP
5V 24 V Logic
5V
+– Driver
I0: 0...7 8x 8x 16x I1: 0...7 Q0: Q1: 0...7 0...7 L1+ M1 L2+ M2 Interface between electronics block and terminal block
X1 TB2-4/DC
Station number selection Connection PROFIBUS-DP
7
Driver
M5
PE
Suppr. logic
I/O Supply/Voltage sensor Ground PE Screw for grounding (see Sec. 3.4)
L1+M1
Suppr. logic STOP/RUN switch
Suppr. logic
L5+ M5
L2+M2
Digital outputs
L5+ M5
24 V supply
Digital inputs
Figure 7-46 Block Diagram: ET 200B-16DI/16DO (6ES7 133-0BL00-0XB0) and TB2-4/DC
7-64
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 151
Digital Modules
Pin Assignment
Table 7-12
The table below shows the pin assignment of the terminal blocks for ET 200B-16DI/16DO. For the sake of clarity, the table also shows the terminal numbering of the terminal blocks, taking the TB2-4/DC by way of example.
Pin Assignment of Terminal Blocks TB2/DC, TB2-4/DC, TB4/DC and TB4M/DC for ET 200B-16DI/16DO (6ES7 133-0BL00-0XB0)
Terminal numbering TB2-4/DC
Terminal tier 1
Terminal tier 1
1
Q0: Output .0
33
2
Q0: Output .1
34
3
Q0: Output .2
35
4
Q0: Output .3
36
68
5
Q0: Output .4
37
69
6
Q0: Output .5
38
70
7
Q0: Output .6
39
71
8
Q0: Output .7
40
72
9
Q1: Output .0
41
10
Q1: Output .1
42
Voltage supply L1+ for channel group Q0: .0 to .7
Voltage supply L2+ for channel group Q1: .0 to .7
65 66 67
73 74
11
Q1: Output .2
43
12
Q1: Output .3
44
76
13
Q1: Output .4
45
77
14
Q1: Output .5
46
78
15
Q1: Output .6
47
79
16
Q1: Output .7
48
17
I0: Input .0
49
18
I0: Input .1
50
19
I0: Input .2
51
20
I0: Input .3
52
84
21
I0: Input .4
53
85
22
I0: Input .5
54
86
23
I0: Input .6
55
87
24
I0: Input .7
56
88
25
I1: Input .0
57
89
26
I1: Input .1
58
90
27
I1: Input .2
59
91
28
I1: Input .3
60
92
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
75
Terminal tier 3
Terminal tier 41
Ground supply M1 for channel group Q0: .0 to .7
PE (internally jumpered, but not connected to PE screw)
7 Ground supply M2 for channel group Q0: .0 to .7
80 24 V (sensor voltage) (internally jumpered, connected to L5+)
81 82 83
Ground (sensor voltage) (internally jumpered, connected to M5)
7-65
Page 152
Digital Modules
Table 7-12
Pin Assignment of Terminal Blocks TB2/DC, TB2-4/DC, TB4/DC and TB4M/DC for ET 200B-16DI/16DO (6ES7 133-0BL00-0XB0), continued Terminal tier 1
Terminal tier 1 29 30
I1: Input .4 I1: Input .5
61 62
31
I1: Input .6
63
32
I1: Input .7
-
-
1
24 V (sensor voltage) (internally jumpered, connected to L5+)
93 94 95
Terminal tier 3
Terminal tier 41
Ground (sensor voltage) (internally jumpered, connected to M5)
PE (internally jumpered, but not connected to PE screw)
64
96
L5+ Voltage supply, internal logic and sensor voltage 24 V L5+ Voltage supply, internal logic and sensor voltage 24 V
M5 Ground connection, internal logic and sensor voltage M5 Ground connection, internal logic and sensor voltage
PE (internally jumpered, but not connected to PE screw)
TB2-4/DC only; in the TB4M/DC tier 4 is available for additional ground connections (see Section 7.2.7)
Important Note on Wiring
The following notes are important as regards the wiring of the ET 200B-16DI/16DO:
The terminals for PE on the 4-tier terminal block are not connected to the PE connection of terminal block TB2-4/DC.
If all actuators are connected by two-wire cables to the TB2/DC, TB4/DC or TB2-4/DC, connect the ground of an actuator and the supply for the reference potential per group by means of a DIN 46231 cable cleat.
7
L1+, L2+ and L5+ or M1, M2 and M5 are not interconnected. L5+ and terminals 49 ... 64 are interconnected, as are M5 and terminals 81 ... 96.
The two L5+ terminals are also internally interconnected. Fuse
7-66
The 24 V sensor supply is protected by fuse F1 (2.5 A) in the terminal blocks. Nevertheless, make sure that the current does not exceed the specifications in the technical data for the electronics block.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 153
Digital Modules
Technical Data
The technical data of electronics block ET 200B-16DI/16DO is listed in the tables below.
Technical Data
Inputs (continued)
Baud rates*
9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud
Bus protocol
PROFIBUS-DP
FREEZE and SYNC capa- Yes bility Galvanic isolation to SINEC L2-DP bus
Yes
Power losses
Max. 5.5 W
Weight (EB and TB)
Approx. 800 g (28 oz.)
Dimensions (EB and TB: W x H x D)
Input current For “1” signal
Typ. 4 mA at 24 V Min. 2 mA
Delay of inputs
3 ms
Connection of 2-wire BERO Quiescent current Connection of mechanical switches Cable length of sensors Unshielded
Possible v 1.5 mA Possible
Max. 100 m (328 ft.)
Outputs 235 x 130 x 60
Diagnostics functions Voltage monitoring
Green “RUN ”LED
Bus monitoring SINEC L2-DP
Red “BF ”LED
Group diagnostics for short-circuit, load voltage failure
Red “DIA” LED
Load voltage monitoring
Green “L1+/L2+” LEDs
Status of inputs and outputs
Green LEDs
Number of outputs Galvanic isolation In groups of Output voltage For “0” signal For “1” signal
16 Yes 8 Max. 2 V (idle) Min. (supply voltage – 3 V)
Output current For “0” signal For “1” signal
Max. 1 mA Max. 0.5 A
Delay of outputs From “0” to “1” From “1” to “0”
Approx. 20 ms Max. 0.5 ms
Switching frequency Resistive load Inductive load Lamp load
Max. 1000 Hz Max. 0.5 Hz Max. 8 Hz
Short-circuit protection
Yes
Current consumption from L5+ Logic Typ. 85 mA Sensors Max. 1 A
Load current per group Total current
Max. 2 A
Lamp load
Max. 5 W
I2t (for inrush current) Inputs v 0.05 A2s
Setting a digital input
Possible Typ. (L1+/L2+) – 55 V
Number of inputs
16
Limit of inductive cutoff voltage Cable length
Max. 100 m (328 ft.)
Supply voltage for outputs, load voltage supply and internal logic Supply voltages (L1+, L2+, L5+) Rated value Permissible range Value for t < 0.5 s
24 V DC 18.5 ... 30.2 V 35 V
Galvanic isolation to inter- No nal electronic circuits Input voltage Rated value For “0” signal For “1” signal
*
7
In operation with the IM 308-B, the maximum baud rate is 1500 kbaud.
24 V DC – 30 V ... 5 V 13 V ... 30 V
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
7-67
Page 154
Digital Modules
7.3.10
Electronics Blocks ET 200B-24DI/8DO (6ES7 133-0BN01-0XB0) and ET 200B-24DI/8DO 0.2ms (6ES7 133-0BN11-0XB0)
Characteristics
The ET 200B-24DI/8DO and ET 200B-24DI/8DO 0.2ms electronics blocks have the following characteristics:
24 inputs, non-floating 8 outputs, floating in groups of 8 Input voltage: 24 V DC Input delay: 6ES7 133-0BN01-0XB0 ³ 3 ms 6ES7 133-0BN11-0XB0 ³ 0.2 ms
Load voltage: 24 V DC Possible terminal blocks: TB2/DC, TB2-4/DC, TB4/DC, TB4M/DC Dimensional Drawing
See Figure 7-22 for the precise dimensions.
7
Figure 7-47 Front Elevation: ET 200B-24DI/8DO (6ES7 133-0BN01-0XB0) and ET 200B-24DI/8DO 0.2ms (6ES7 133-0BN11-0XB0)
7-68
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 155
Digital Modules
Block Diagram
Simplified diagram of the potential for the ET 200B-24DI/8DO or ET 200B-24DI/8DO 0.2 ms and TB2/DC or TB4/DC:
ET 200B-24DI/8DO ET 200B-24DI/8DO0.2ms
24 V
PROFIBUS-DP
5V 24 V Logic
5V
+– Driver
I0: 0...7 I1: 0...7 24x I2: 0...7
8x
Q0: L1+ M1 0...7 Interface between electronics block and terminal block
X1 TB2/DC or TB4/DC
Station number selection Connection PROFIBUS-DP M5
PE
Suppr. logic STOP/RUN switch
Suppr. logic
L1+ M1 I/O Supply/ Voltage sensor Ground Screw for grounding (see Sec. 3.4)
L5+ M5
L5+ M5
Digital outputs
Digital inputs
24 V supply
Figure 7-48 Block Diagram: ET 200B-24DI/8DO (6ES7 133-0BN01-0XB0) or ET 200B-24DI/8DO 0.2ms (6ES7 133-0BN11-0XB0) and TB2/DC or TB4/DC
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
7-69
7
Page 156
Digital Modules
Block Diagram
Simplified diagram of the potential for the ET 200B-24DI/8DO or ET 200B-24DI/8DO 0.2 ms and TB2-4/DC:
ET 200B-24DI/8DO ET 200B-24DI/8DO0.2ms
24 V
PROFIBUS-DP
5V 24 V Logic
5V
+– Driver
I0: 0...7 I1: 0...7 24x I2: 0...7
8x
X1 TB2-4/DC
Q0: L1+ M1 0...7 Interface between electronics block and terminal block Station number selection Connection PROFIBUS-DP
7
M5
PE
Suppr. logic STOP/RUN switch
Suppr. logic
L1+ M1 I/O Supply/ Voltage sensor Ground PE Screw for grounding (see Sec. 3.4)
L5+ M5
L5+ M5
Digital outputs
Digital inputs
24 V supply
Figure 7-49 Block Diagram: ET 200B-24DI/8DO (6ES7 133-0BN01-0XB0) or ET 200B-24DI/8DO 0.2ms (6ES7 133-0BN11-0XB0) and TB2-4/DC
7-70
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c