SIMATIC ET 200B Distributed I/O Station Manual: 7 Digital Modules, pages 147 to 156

Pages 147 to 156 of 344, from SIMATIC ET 200B Distributed I/O Station Manual

The original document is the PDF (2.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Siemens ET 200B

Page 147

Digital Modules

Technical Data

The technical data of electronics block ET 200B-8DI/8DO HWA is listed in the tables below.

Technical Data

Inputs (continued)

Baud rates*

9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud

Bus protocol

PROFIBUS-DP

FREEZE and SYNC capa- Yes bility Galvanic isolation to SINEC L2-DP bus

Yes

Power losses

Max. 3.8 W

Weight (EB and TB)

Approx. 650 g

Dimensions (EB and TB: W x H x D)

Input current for “1” signal

Typ. 4 mA at 24 V Min. 2 mA

Delay of inputs

3 ms

Connection of 2-wire BERO Quiescent current

Possible

Connection of mechanical switches Cable length of sensors Unshielded

Possible v 1.5 mA

Max. 100 m (328 ft.)

Outputs 160 x 130 x 60

Number of outputs

8

Voltage monitoring

Green “RUN” LED

Galvanic isolation In groups of

No 8

Bus monitoring SINEC L2-DP

Red “BF” LED

Group diagnostics for short-circuit, load voltage failure

Red “DIA” LED

Load voltage monitoring

Green “L1+” LED

Status of inputs and outputs

Green LEDs

Diagnostics functions

Supply voltage for sensor supply, load voltage supply and internal logic Supply voltage (L1+,L3+) Rated value Permissible range Value for t < 0.5 s

24 V DC 18.5 ... 30.2 V 35 V

Current consumption from L3+ Logic Typ. 70 mA Sensors Max. 500 mA I2t (for the inrush current) Inputs v 0.05 A2s

Number of inputs

8

Galvanic isolation to inter- No nal electronic circuits Input voltage Rated value For “0” signal For “1” signal

Output voltage For “0” signal For “1” signal Output current For “0” signal For “1” signal Delay of outputs From “0” to “1” From “1” to “0” By hardware cutoff Switching frequency Resistive load Inductive load Lamp load

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7

Max. 1 mA Max. 0.5 A Typ. 50 Typ. 100 3 ms Max. 100 Hz Max. 0.5 Hz Max. 8 Hz

Short-circuit protection

Yes

Load current Total current

Max. 2 A

Lamp load

Max. 5 W

Setting a digital input

Possible

Limit of inductive cutoff voltage

Typ. (L1+) – 55 V

Cable length

Max. 100 m (328 ft.)

* 24 V DC – 30 V ... 5 V 13 V ... 30 V

Max. 2 V (idle) Min. (supply voltage – 3 V)

In operation with the IM 308-B, the maximum baud rate is1500 kbaud.

7-61

Page 148

Digital Modules

7.3.9

Electronics Block ET 200B-16DI/16DO (6ES7 133 0BL00-0XB0)

Characteristics

The ET 200B-16DI/16DO has the following characteristics:

16 inputs, non-floating 16 outputs, floating in groups of 8 Input voltage: 24 V DC Input delay: 3 ms Load voltage: 24 V DC Possible terminal blocks: TB2/DC, TB2-4/DC, TB4/DC, TB4M/DC Dimensional Drawing

See Figure 7-22 for the precise dimensions.

7

Figure 7-44 Front Elevation: ET 200B-16DI/16DO (6ES7 133-0BL00-0XB0)

7-62

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 149

Digital Modules

Block Diagram

Simplified diagram of the potential for the ET 200B-16DI/16DO and TB2/DC or TB4/DC:

ET 200B-16DI/16DO

24 V

PROFIBUS-DP

5V 24 V Logic

5V

+– Driver

Driver

I0: 0...7 8x 8x 16x I1: 0...7 Q0: Q1: 0...7 0...7 L1+ M1 L2+ M2 Interface between electronics block and terminal block

X1 TB2/DC or TB4/DC

Station number selection Connection PROFIBUS-DP M5

PE

I/O Supply/Voltage sensor Ground Screw for grounding (see Sec. 3.4)

Suppr. logic L1+M1

Suppr. logic STOP/RUN switch

Suppr. logic

L5+ M5

L2+M2

Digital outputs

L5+ M5

Digital inputs

24 V supply

Figure 7-45 Block Diagram: ET 200B-16DI/16DO (6ES7 133-0BL00-0XB0) and TB2/DC or TB4/DC

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7-63

7

Page 150

Digital Modules

Block Diagram

Simplified diagram of the potential for the ET 200B-16DI/16DO and TB2-4/DC:

ET 200B-16DI/16DO

24 V

PROFIBUS-DP

5V 24 V Logic

5V

+– Driver

I0: 0...7 8x 8x 16x I1: 0...7 Q0: Q1: 0...7 0...7 L1+ M1 L2+ M2 Interface between electronics block and terminal block

X1 TB2-4/DC

Station number selection Connection PROFIBUS-DP

7

Driver

M5

PE

Suppr. logic

I/O Supply/Voltage sensor Ground PE Screw for grounding (see Sec. 3.4)

L1+M1

Suppr. logic STOP/RUN switch

Suppr. logic

L5+ M5

L2+M2

Digital outputs

L5+ M5

24 V supply

Digital inputs

Figure 7-46 Block Diagram: ET 200B-16DI/16DO (6ES7 133-0BL00-0XB0) and TB2-4/DC

7-64

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 151

Digital Modules

Pin Assignment

Table 7-12

The table below shows the pin assignment of the terminal blocks for ET 200B-16DI/16DO. For the sake of clarity, the table also shows the terminal numbering of the terminal blocks, taking the TB2-4/DC by way of example.

Pin Assignment of Terminal Blocks TB2/DC, TB2-4/DC, TB4/DC and TB4M/DC for ET 200B-16DI/16DO (6ES7 133-0BL00-0XB0)

Terminal numbering TB2-4/DC

Terminal tier 1

Terminal tier 1

1

Q0: Output .0

33

2

Q0: Output .1

34

3

Q0: Output .2

35

4

Q0: Output .3

36

68

5

Q0: Output .4

37

69

6

Q0: Output .5

38

70

7

Q0: Output .6

39

71

8

Q0: Output .7

40

72

9

Q1: Output .0

41

10

Q1: Output .1

42

Voltage supply L1+ for channel group Q0: .0 to .7

Voltage supply L2+ for channel group Q1: .0 to .7

65 66 67

73 74

11

Q1: Output .2

43

12

Q1: Output .3

44

76

13

Q1: Output .4

45

77

14

Q1: Output .5

46

78

15

Q1: Output .6

47

79

16

Q1: Output .7

48

17

I0: Input .0

49

18

I0: Input .1

50

19

I0: Input .2

51

20

I0: Input .3

52

84

21

I0: Input .4

53

85

22

I0: Input .5

54

86

23

I0: Input .6

55

87

24

I0: Input .7

56

88

25

I1: Input .0

57

89

26

I1: Input .1

58

90

27

I1: Input .2

59

91

28

I1: Input .3

60

92

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

75

Terminal tier 3

Terminal tier 41

Ground supply M1 for channel group Q0: .0 to .7

PE (internally jumpered, but not connected to PE screw)

7 Ground supply M2 for channel group Q0: .0 to .7

80 24 V (sensor voltage) (internally jumpered, connected to L5+)

81 82 83

Ground (sensor voltage) (internally jumpered, connected to M5)

7-65

Page 152

Digital Modules

Table 7-12

Pin Assignment of Terminal Blocks TB2/DC, TB2-4/DC, TB4/DC and TB4M/DC for ET 200B-16DI/16DO (6ES7 133-0BL00-0XB0), continued Terminal tier 1

Terminal tier 1 29 30

I1: Input .4 I1: Input .5

61 62

31

I1: Input .6

63

32

I1: Input .7

-

-

1

24 V (sensor voltage) (internally jumpered, connected to L5+)

93 94 95

Terminal tier 3

Terminal tier 41

Ground (sensor voltage) (internally jumpered, connected to M5)

PE (internally jumpered, but not connected to PE screw)

64

96

L5+ Voltage supply, internal logic and sensor voltage 24 V L5+ Voltage supply, internal logic and sensor voltage 24 V

M5 Ground connection, internal logic and sensor voltage M5 Ground connection, internal logic and sensor voltage

PE (internally jumpered, but not connected to PE screw)

TB2-4/DC only; in the TB4M/DC tier 4 is available for additional ground connections (see Section 7.2.7)

Important Note on Wiring

The following notes are important as regards the wiring of the ET 200B-16DI/16DO:

The terminals for PE on the 4-tier terminal block are not connected to the PE connection of terminal block TB2-4/DC.

If all actuators are connected by two-wire cables to the TB2/DC, TB4/DC or TB2-4/DC, connect the ground of an actuator and the supply for the reference potential per group by means of a DIN 46231 cable cleat.

7

L1+, L2+ and L5+ or M1, M2 and M5 are not interconnected. L5+ and terminals 49 ... 64 are interconnected, as are M5 and terminals 81 ... 96.

The two L5+ terminals are also internally interconnected. Fuse

7-66

The 24 V sensor supply is protected by fuse F1 (2.5 A) in the terminal blocks. Nevertheless, make sure that the current does not exceed the specifications in the technical data for the electronics block.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 153

Digital Modules

Technical Data

The technical data of electronics block ET 200B-16DI/16DO is listed in the tables below.

Technical Data

Inputs (continued)

Baud rates*

9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud

Bus protocol

PROFIBUS-DP

FREEZE and SYNC capa- Yes bility Galvanic isolation to SINEC L2-DP bus

Yes

Power losses

Max. 5.5 W

Weight (EB and TB)

Approx. 800 g (28 oz.)

Dimensions (EB and TB: W x H x D)

Input current For “1” signal

Typ. 4 mA at 24 V Min. 2 mA

Delay of inputs

3 ms

Connection of 2-wire BERO Quiescent current Connection of mechanical switches Cable length of sensors Unshielded

Possible v 1.5 mA Possible

Max. 100 m (328 ft.)

Outputs 235 x 130 x 60

Diagnostics functions Voltage monitoring

Green “RUN ”LED

Bus monitoring SINEC L2-DP

Red “BF ”LED

Group diagnostics for short-circuit, load voltage failure

Red “DIA” LED

Load voltage monitoring

Green “L1+/L2+” LEDs

Status of inputs and outputs

Green LEDs

Number of outputs Galvanic isolation In groups of Output voltage For “0” signal For “1” signal

16 Yes 8 Max. 2 V (idle) Min. (supply voltage – 3 V)

Output current For “0” signal For “1” signal

Max. 1 mA Max. 0.5 A

Delay of outputs From “0” to “1” From “1” to “0”

Approx. 20 ms Max. 0.5 ms

Switching frequency Resistive load Inductive load Lamp load

Max. 1000 Hz Max. 0.5 Hz Max. 8 Hz

Short-circuit protection

Yes

Current consumption from L5+ Logic Typ. 85 mA Sensors Max. 1 A

Load current per group Total current

Max. 2 A

Lamp load

Max. 5 W

I2t (for inrush current) Inputs v 0.05 A2s

Setting a digital input

Possible Typ. (L1+/L2+) – 55 V

Number of inputs

16

Limit of inductive cutoff voltage Cable length

Max. 100 m (328 ft.)

Supply voltage for outputs, load voltage supply and internal logic Supply voltages (L1+, L2+, L5+) Rated value Permissible range Value for t < 0.5 s

24 V DC 18.5 ... 30.2 V 35 V

Galvanic isolation to inter- No nal electronic circuits Input voltage Rated value For “0” signal For “1” signal

*

7

In operation with the IM 308-B, the maximum baud rate is 1500 kbaud.

24 V DC – 30 V ... 5 V 13 V ... 30 V

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7-67

Page 154

Digital Modules

7.3.10

Electronics Blocks ET 200B-24DI/8DO (6ES7 133-0BN01-0XB0) and ET 200B-24DI/8DO 0.2ms (6ES7 133-0BN11-0XB0)

Characteristics

The ET 200B-24DI/8DO and ET 200B-24DI/8DO 0.2ms electronics blocks have the following characteristics:

24 inputs, non-floating 8 outputs, floating in groups of 8 Input voltage: 24 V DC Input delay: 6ES7 133-0BN01-0XB0 ³ 3 ms 6ES7 133-0BN11-0XB0 ³ 0.2 ms

Load voltage: 24 V DC Possible terminal blocks: TB2/DC, TB2-4/DC, TB4/DC, TB4M/DC Dimensional Drawing

See Figure 7-22 for the precise dimensions.

7

Figure 7-47 Front Elevation: ET 200B-24DI/8DO (6ES7 133-0BN01-0XB0) and ET 200B-24DI/8DO 0.2ms (6ES7 133-0BN11-0XB0)

7-68

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 155

Digital Modules

Block Diagram

Simplified diagram of the potential for the ET 200B-24DI/8DO or ET 200B-24DI/8DO 0.2 ms and TB2/DC or TB4/DC:

ET 200B-24DI/8DO ET 200B-24DI/8DO0.2ms

24 V

PROFIBUS-DP

5V 24 V Logic

5V

+– Driver

I0: 0...7 I1: 0...7 24x I2: 0...7

8x

Q0: L1+ M1 0...7 Interface between electronics block and terminal block

X1 TB2/DC or TB4/DC

Station number selection Connection PROFIBUS-DP M5

PE

Suppr. logic STOP/RUN switch

Suppr. logic

L1+ M1 I/O Supply/ Voltage sensor Ground Screw for grounding (see Sec. 3.4)

L5+ M5

L5+ M5

Digital outputs

Digital inputs

24 V supply

Figure 7-48 Block Diagram: ET 200B-24DI/8DO (6ES7 133-0BN01-0XB0) or ET 200B-24DI/8DO 0.2ms (6ES7 133-0BN11-0XB0) and TB2/DC or TB4/DC

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7-69

7

Page 156

Digital Modules

Block Diagram

Simplified diagram of the potential for the ET 200B-24DI/8DO or ET 200B-24DI/8DO 0.2 ms and TB2-4/DC:

ET 200B-24DI/8DO ET 200B-24DI/8DO0.2ms

24 V

PROFIBUS-DP

5V 24 V Logic

5V

+– Driver

I0: 0...7 I1: 0...7 24x I2: 0...7

8x

X1 TB2-4/DC

Q0: L1+ M1 0...7 Interface between electronics block and terminal block Station number selection Connection PROFIBUS-DP

7

M5

PE

Suppr. logic STOP/RUN switch

Suppr. logic

L1+ M1 I/O Supply/ Voltage sensor Ground PE Screw for grounding (see Sec. 3.4)

L5+ M5

L5+ M5

Digital outputs

Digital inputs

24 V supply

Figure 7-49 Block Diagram: ET 200B-24DI/8DO (6ES7 133-0BN01-0XB0) or ET 200B-24DI/8DO 0.2ms (6ES7 133-0BN11-0XB0) and TB2-4/DC

7-70

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c