SIMATIC ET 200B Distributed I/O Station Manual: 7 Digital Modules, pages 137 to 146

Pages 137 to 146 of 344, from SIMATIC ET 200B Distributed I/O Station Manual

The original document is the PDF (2.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Siemens ET 200B

Page 137

Digital Modules

Block Diagram

Simplified diagram of the potential for the ET 200B-8DI/8DO and TB1-4/DC:

ET 200B-8DI/8DO

24 V

PROFIBUS-DP

5V 24 V Logic

5V

+– Driver 8x

8x

I0: 0...7 Q0: 0...7 L1+ Interface between electronics block and terminal block

X1 TB1-4/DC

Station number selection

Suppr. logic STOP/RUN switch

Connection PROFIBUS-DP M

PE

L3+ M

I/O Voltage sensor Ground PE Screw for grounding (see Sec. 3.4)

L1+

Outputs

Inputs

L3+ M

24 V supply

Figure 7-40 Block Diagram: ET 200B-8DI/8DO (6ES7 133-0BH01-0XB0) and TB1-4/DC

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7-51

7

Page 138

Digital Modules

Pin Assignment

Table 7-9

The table below shows the pin assignment of the terminal blocks for ET 200B-8DI/8DO. For the sake of clarity, the table also shows the terminal numbering of the terminal blocks, taking the TB1-4/DC by way of example.

Pin Assignment of Terminal Blocks TB1/DC; TB1-4/DC and TB3/DC for ET 200B-8DI/8DO (6ES7 133-0BH01-0XB0)

Terminal numbering TB1-4/DC

Terminal tier 1

7

1

Q0: Output .0

17

2

Q0: Output .1

18

3

Q0: Output .2

19

4

Q0: Output .3

20

36

5

Q0: Output .4

21

37

6

Q0: Output .5

22

38

7

Q0: Output .6

23

39

8

Q0: Output .7

24

40

24 V (sensor voltage, internally jumpered, connected to L3+)

33 34 35

Terminal tier 3

Terminal tier 41

Ground (outputs) (internally jumpered, connected to M1, M2, M3)

PE (internally jumpered, but not connected to PE screw)

9

I0: Input .0

25

41

10

I0: Input .1

26

42

11

I0: Input .2

27

43

12

I0: Input .3

28

44

13

I0: Input .4

29

45

14

I0: Input .5

30

46

15

I0: Input .6

31

47

16

I0: Input .7

32

48

L1+ Voltage supply L1+ for channel group Q0: .0 to .7 L2+ not used

M1 Ground supply M1 for channel group Q0: .0 to .7 M2 not used

L3+ Voltage supply, internal logic and sensor voltage 24 V L3+ Voltage supply, internal logic and sensor voltage 24 V

M3 Ground connection, internal logic and sensor voltage M3 Ground connection, internal logic and sensor voltage

-

-

-

1

Terminal tier 2

Ground (sensor voltage) (internally jumpered, connected to M1, M2, M3)

PE (internally jumpered, but not connected to PE screw)

TB1-4/DC only

7-52

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 139

Digital Modules

Important Note on Wiring

The following notes are important as regards the wiring of the ET 200B-8DI/8DO:

The terminals for PE on the 4-tier terminal block are not connected to the PE connection of terminal block TB1-4/DC.

L1+ and L3+ are not internally interconnected. L3+ and terminals 25 ... 32 are interconnected, as are M1, M2, M3 and terminals 33 ... 48.

The two L3+ terminals are also interconnected. Fuse

The 24 V sensor supply is protected by fuse F1 (1.6 A) in the terminal blocks. Nevertheless, make sure that the current does not exceed the specifications in the technical data for the electronics block.

7

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7-53

Page 140

Digital Modules

Technical Data

The technical data of electronics block ET 200B-8DI/8DO is listed in the tables below.

Technical specifications

Inputs, continued

Baud rates*

9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud

Bus protocol

PROFIBUS-DP

FREEZE and SYNC capa- Yes bility Galvanic isolation to SINEC L2-DP bus

Yes

Power losses

Max. 3.8 W

Weight (EB and TB)

Approx. 650 g (22.75 oz.)

Dimensions (EB and TB: W x H x D)

160 x 130 x 60 mm (6.24 x 5.07 x 2.34 in.)

Diagnostics functions

7

Voltage monitoring

Green “RUN” LED

Bus monitoring SINEC L2-DP

Red “BF” LED

Group diagnostics for short-circuit, load voltage failure

Red “DIA” LED

Load voltage monitoring

Green “L1+” LED

Status of inputs and outputs

Green LEDs

Input current for “1” signal Typ. 4 mA at 24 V Min. 2 mA Delay of inputs

3 ms

Connection of 2-wire BERO Quiescent current Connection of mechanical switches Cable length of sensors Unshielded

Possible v 1.5 mA Possible

Max. 100 m (328 ft.)

Outputs Number of outputs Galvanic isolation In groups of Output voltage For “0” signal For “1” signal

8 No 8 Max. 2 V (idle) Min. (supply voltage – 3 V)

Output current For “0” signal For “1” signal

Max. 1 mA Max. 0.5 A

Supply voltage for sensor supply, load voltage supply and internal logic

Delay of outputs From “0” to “1” From “1” to “0”

Approx. 20 ms Max. 0.5 ms

Supply voltage (L1+,L3+) Rated value Permissible range Value for t < 0.5 s

Switching frequency Resistive load Inductive load Lamp load

Max. 100 Hz Max. 0.5 Hz Max. 8 Hz

Short-circuit protection

Yes

Load current Total current

Max. 2 A

Lamp load

Max. 5 W

Setting a digital input

Possible

Limit of inductive cutoff voltage

Typ. (L1+) – 55 V

Galvanic isolation to inter- No nal electronic circuits

Cable length

Max. 100 m (328 ft.)

Input voltage Rated value For “0” signal For “1” signal

*

24 V DC 18.5 to 30.2 V 35 V

Current consumption from L3+ Logic Typ. 70 mA Sensors Max. 500 mA I2t (for inrush current) Inputs

< 0.05 A2s

Number of inputs

8

7-54

24 V DC – 30 V to 5 V 13 V to 30 V

In operation with the IM 308-B, the maximum baud rate is 1500 kbaud.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 141

Digital Modules

7.3.8

Electronics Block ET 200B-8DI/8DO HWA (6ES7 133-0BH10-0XB0)

characteristics

The ET 200B-8DI/8DO HWA electronics block has the following characteristics:

8 inputs, non-floating 8 outputs, non-floating The outputs can be deactivated by a programmed deactivation level applied to the input.

Input voltage: 24 V DC Input delay: 3 ms Load voltage: 24 V DC Possible terminal blocks: TB1/DC, TB1-4/DC or TB3/DC Dimensional Drawing

See Figure 7-18 for the precise dimensions.

7

Figure 7-41 Front Elevation: ET 200B-8DI/8DO HWA (6ES7 133-0BH10-0XB0)

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7-55

Page 142

Digital Modules

Block Diagram

Simplifieddiagram of potential for the ET 200B-8DI/8DO HWA and TB1/DC or TB3/DC:

ET 200B-8DI/8DO HWA

24 V

PROFIBUS-DP

5V 24 V Logic

5V

+– Driver 8x

8x

I0: 0...7 Q0: 0...7 L1+ Interface between electronics block and terminal block

X1 TB1/DC or TB3/DC

Station number selection

Suppr. logic STOP/RUN switch

Connection PROFIBUS-DP

7

M

PE

L3+ M

I/O Voltage sensor Ground Screw for grounding (see Sec. 3.4)

L1+

Outputs

Inputs

L3+ M

24 V supply

Figure 7-42 Block Diagram: ET 200B-8DI/8DO HWA (6ES7 133-0BH10-0XB0) and TB1/DC or TB3/DC

7-56

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 143

Digital Modules

Block Diagram

Simplifieddiagram of potential for the ET 200B-8DI/8DO HWA and TB1-4/DC:

ET 200B-8DI/8DO

24 V

PROFIBUS-DP

5V 24 V Logic

5V

+– Driver 8x

8x

I0: 0...7 Q0: 0...7 L1+ Interface between electronics block and terminal block

X1 TB1-4/DC

Station number selection

Suppr. logic STOP/RUN switch

Connection PROFIBUS-DP M

PE

L3+ M

I/O Voltage sensor Ground PE Screw for grounding (see Sec. 3.4)

L1+

Outputs

Inputs

L3+ M

24 V supply

Figure 7-43 Block Diagram: ET 200B-8DI/8DO HWA (6ES7 133-0BH10-0XB0) and TB1-4/DC

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7-57

7

Page 144

Digital Modules

Pin Assignment

Table 7-10

The table below shows the pin assignment of the terminal blocks for ET 200B-8DI/8DO HWA. For the sake of clarity, the table also shows the terminal numbering of the terminal blocks, taking the TB1-4/DC by way of example.

Pin Assignment of Terminal Blocks TB1/DC; TB1-4/DC and TB3/DC for ET 200B-8DI/8DO HWA (6ES7 133-0BH10-0XB0)

Terminal numbering TB1-4/DC

Terminal tier 1

7

1

Q0: Output .0

17

2

Q0: Output .1

18

3

Q0: Output .2

19

4

Q0: Output .3

20

36

5

Q0: Output .4

21

37

6

Q0: Output .5

22

38

7

Q0: Output .6

23

39

8

Q0: Output .7

24

40

24 V (sensor voltage, internally jumpered, connected to L3+)

33 34 35

Terminal tier 3

Terminal tier 41

Ground (outputs) (internally jumpered, connected to M1, M2, M3)

PE (internally jumpered, but not connected to PE screw)

9

I0: Input .0

25

41

10

I0: Input .1

26

42

11

I0: Input .2

27

43

12

I0: Input .3

28

44

13

I0: Input .4

29

45

14

I0: Input .5

30

46

15

I0: Input .6

31

47

16

I0: Input .7

32

48

L1+ Voltage supply L1+ for channel group Q0: .0 to .7 L2+ not used

M1 Ground supply M1 for channel group Q0: .0 to .7 M2 not used

L3+ Voltage supply, internal logic and sensor voltage 24 V L3+ Voltage supply, internal logic and sensor voltage 24 V

M3 Ground connection, internal logic and sensor voltage M3 Ground connection, internal logic and sensor voltage

–

– –

–

1

Terminal tier 2

Ground (sensor voltage) (internally jumpered, connected to M1, M2, M3)

PE (internally jumpered, but not connected to PE screw)

TB1-4/DC only

7-58

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 145

Digital Modules

HW Cutoff

Outputs .0 to .7 are deactivated as soon as the programmed cutoff level is applied to the corresponding input .0 to .7. The relationship between inputs and outputs is permanent (I .0 ³ O .0, I .1 ³ O .1, ...). Address assignment: EB x AB y AB y + 1

Bit Assignment in the ”Cutoff Level” Byte

Inputs .0 to .7 Outputs .0 to .7 Cutoff level .0 to .7 (negated)

2 consecutive bytes in the address space of the CPU

The ”cutoff level” byte defaults to ”0”, i.e. output y.n is deactivated (set to ”0”), if signal ”1” is present at input x.n. 0: Output is deactivated by signal ”1” at corresponding input. 1: Output is deactivated by signal ”1” at corresponding input Table 7-11

Truth Table for Hardware Cutoff of ET 200B-8DI/8DO HWA Ix.0 . . .

I x.0

Output byte y

Input byte

Ix.7

Oy.0 . . .

Oy.0 ”1”

Oy.7 Output byte y+1 with cutoff level entered (per output)

Oy+1.0 . . .

Enable

7

”0” Oy+1.0 = ”0”

Oy+1.7

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

IB x.n

OB y+1.n

OB y.n

Output signal .n

0

0

0

0

0

0

1

1

1

0 any

0

1

1

0

0

1

1

1

1

0

1 any

0 deactivated deactivated

7-59

Page 146

Digital Modules

Note

The following notes are important as regards the wiring and hardware cutoff of ET 200B-8DI/8DO HWA:

The terminals for PE on the 4-tier terminal block are not connected to the PE connection of terminal block TB1-4/DC.

L1+ and L3+ are not internally interconnected. L3+ and terminals 17 ... 32 are interconnected, as are M1, M2, M3 and terminals 33 ... 48.

The two L3+ terminals are also interconnected. Outputs can switch through temporarily:

!

Warning The configuration described below is such that POWER OFF, STOP or transient voltage collapse at the terminal block cause the outputs of the ET 200B-8DI/8DO HWA to switch through briefly. Case 3 in Table 7-11 ”Truth Table” (gray background): ”cutoff level” byte OB y+1” programmed to ”0”, outputs set to ”1” by S5/S7 application program. ³ signal ”1” at input I x.n activates the hardware cutoff. Cause: POWER OFF, STOP or transient voltage collapse shuts off the sensor voltage, but the logic continues to function for at least another 20 ms (bridging power failure). The lack of the sensor voltage means that signal ”0” is detected at the inputs and the outputs are enabled if the configuration is as described above.

7 Fuse

7-60

The 24 V sensor supply is protected by fuse F1 (1.6 A) in the terminal blocks. Nevertheless, make sure that the current does not exceed the specifications in the technical data for the electronics block.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c