SIMATIC ET 200B Distributed I/O Station Manual: 7 Digital Modules, pages 127 to 136

Pages 127 to 136 of 344, from SIMATIC ET 200B Distributed I/O Station Manual

The original document is the PDF (2.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Siemens ET 200B

Page 127

Digital Modules

Pin Assignment

Table 7-7

The table below shows the pin assignment of the terminal blocks for ET 200B-32DO. For the sake of clarity, the table also shows the terminal numbering of the terminal blocks, taking the TB2-4/DC by way of example.

Pin Assignment of Terminal Blocks TB2/DC, TB2-4/DC, TB4/DC and TB4M/DC for ET 200B-32DO (6ES7 132-0BL01-0XB0)

Terminal numbering TB2-4/DC

Terminal tier 1

Terminal tier 2 Voltage supply L1+ for channel group Q0: .0 to .7 (internally jumpered)

1

Q0: Output .0

33

2

Q0: Output .1

34

3

Q0: Output .2

35

4

Q0: Output .3

36

68

5

Q0: Output .4

37

69

6

Q0: Output .5

38

70

7

Q0: Output .6

39

71

8

Q0: Output .7

40

72

9

Q1: Output .0

41

10

Q1: Output .1

42

Voltage supply L2+ for channel group Q1: .4 to .7 (internally jumpered)

65 66

73 74

11

Q1: Output .2

43

Q1: Output .3

44

76

13

Q1: Output .4

45

77

14

Q1: Output .5

46

78

15

Q1: Output .6

47

79

16

Q1: Output .7

48

80

17

Q2: Output .0

49

18

Q2: Output .1

50

19

Q2: Output .2

51

20

Q2: Output .3

52

84

21

Q2: Output .4

53

85

22

Q2: Output .5

54

86

23

Q2: Output .6

55

87

24

Q2: Output .7

56

88

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Terminal tier 41

Ground M1 for channel group Q0: .0 to .7 (internally jumpered)

PE (internally jumpered, but not connected to PE screw)

67

12

Voltage supply L3+ for channel group Q2: .0 to .7 (internally jumpered)

Terminal tier 3

75

81 82

7 Ground M2 for channel group Q01: .0 to .7 (internally jumpered)

Ground M3 for channel group Q2: .0 to .7 (internally jumpered)

83

7-41

Page 128

Digital Modules

Table 7-7

Pin Assignment of Terminal Blocks TB2/DC, TB2-4/DC, TB4/DC and TB4M/DC for ET 200B-32DO (6ES7 132-0BL01-0XB0), continued Terminal tier 2

Terminal tier 1

1

Voltage supply L4+ for channel group Q3: .0 to .7 (internally jumpered)

89

Terminal tier 3

Terminal tier 41

Ground M4 for channel group Q3: .0 to .7 (internally jumpered)

PE (internally jumpered, but not connected to PE screw)

PE (internally jumpered, but not connected to PE screw)

25

Q3: Output .0

57

26

Q3: Output .1

58

27

Q3: Output .2

59

28

Q3: Output .3

60

92

29

Q3: Output .4

61

93

30

Q3: Output .5

62

94

31

Q3: Output .6

63

95

32

Q3: Output .7

64

96

–

L5+ Voltage supply, internal logic

M5 Ground connection, internal logic

–

L5+ Voltage supply, internal logic

M5 Ground connection, internal logic

90 91

TB2-4/DC only; in the TB4M/DC tier 4 is available for additional ground connections (see Section 7.2.7)

Important Note on Wiring

The following notes are important as regards the wiring of the ET 200B-32DO:

The terminals for PE on the 4-tier terminal block are not connected to the

7

PE connection of terminal block TB2-4/DC.

If all actuators are connected by two-wire cables to the TB2/DC, TB4/DC or TB2-4/DC, connect the ground of an actuator and the supply for the reference potential per group by means of a DIN 46231 cable cleat.

L1+ ... L5+ and M1 ... M5 are not internally interconnected. The two L5+ terminals are internally interconnected.

7-42

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 129

Digital Modules

Technical Data

The technical data of electronics block ET 200B-32DO is listed in the tables below.

Technical specifications

Outputs

Baud rates*

9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud

Number of outputs Galvanic isolation In groups of

Bus protocol

PROFIBUS-DP

SYNC capability

Yes

Galvanic isolation to SINEC L2-DP bus

Yes

Output voltage For “0” signal For “1” signal

Power losses

Max. 7.9 W

Weight (EB and TB)

Approx. 800 g (28 oz.)

Dimensions (EB and TB: W x H x D)

235 x 130 x 60 mm (9.17 x 5.07 x 2.34 in.)

Diagnostics functions Voltage monitoring

Green “RUN ”LED

Bus monitoring SINEC L2-DP

Red “BF” LED

Group diagnostics for short-circuit, load voltage failure

Red “DIA” LED

Load voltage monitoring

Green “L1+/L2+”, “L3+/L4+” LEDs

Status of outputs

Green LEDs

Supply voltage for outputs, load voltage supply and internal logic Supply voltage (L1+,L2+,L3+,L4+,L5+) Rated value Permissible range Value for t < 0.5 s

24 V DC 18.5 to 30.2 V 35 V

32 Yes 8 Max. 2 V (idle) Min. (supply voltage – 3 V)

Output current For “0” signal For “1” signal

Max. 1 mA Max. 0.5 A

Delay of outputs From “0” to “1” From “1” to “0”

Approx. 20 ms Max. 0.5 ms

Switching frequency Resistive load Inductive load Lamp load

Max. 1000 Hz Max. 0.5 Hz Max. 8 Hz

Short-circuit protection

Yes

Load current per group Total current

Max. 2 A

Lamp load

Max. 5 W

Setting a digital input

Possible

Limitation of voltage induced on current interruption

Typ. (L1+ ... L4+) – 55 V

Cable length

Max. 100 m (328 ft.)

*

7

In operation with the IM 308-B, the maximum baud rate is 1500 kbaud.

I2 t < 0.05 A2s (for inrush current) Current consumption from L5+ Logic Typ. 75 mA

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7-43

Page 130

Digital Modules

7.3.6

Electronics block ET 200B-8RO (6ES7 132-0GF00-0XB0)

Characteristics

The ET 200B-8RO electronics block has the following characteristics:

8 relay outputs, floating in groups of 1 Switching voltage: 24 to 60 V DC Possible terminal blocks: TB1/DC, TB1-4/DC or TB3/DC Dimensional Drawing

See Figure 7-18 for the precise dimensions.

7

Figure 7-35 Front Elevation: ET 200B-8RO (6ES7 132-0GF00-0XB0)

7-44

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 131

Digital Modules

Block Diagram

Simplified diagram of the potential for the ET 200B-8RO and TB1/DC or TB3/DC:

ET 200B-8RO

24 V

PROFIBUS-DP

5V 24 V Logic

5V

8x

X/0 X/1 Interface between electronics block and terminal block

X1 TB1/DC or TB3/DC

Station number selection

Suppr. logic STOP/RUN switch

Connection PROFIBUS-DP Contact

M

L3+ M

L1+L2+ L3+ M

Ground PE

Screw for grounding (see Sec. 3.4)

Relay outputs

24 V supply

Figure 7-36 Block Diagram: ET 200B-8RO (6ES7 132-0GF00-0XB0) and TB1/DC or TB3/DC

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7-45

7

Page 132

Digital Modules

Block Diagram

Simplified diagram of the potential for the ET 200B-8RO and TB1-4/DC:

ET 200B-8RO

24 V

PROFIBUS-DP

5V 24 V Logic

5V

8x

X/0 X/1 Interface between electronics block and terminal block

X1 TB1-4/DC

Station number selection

Suppr. logic STOP/RUN switch

Connection PROFIBUS-DP

7

Contact

M

L3+ M

L1+L2+ L3+ M

Ground PE PE

Screw for grounding (see Sec. 3.4)

Relay outputs

24 V supply

Figure 7-37 Block Diagram: ET 200B-8RO (6ES7 132-0GF00-0XB0) and TB1-4/DC

7-46

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 133

Digital Modules

Pin Assignment

Table 7-8

The table below shows the pin assignment of the terminal blocks for ET 200B-8RO. For the sake of clarity, the table also shows the terminal numbering of the terminal blocks, taking the TB1-4/DC by way of example.

Pin Assignment of Terminal Blocks TB1/DC; TB1-4/DC and TB3/DC for ET 200B-8RO (6ES7 132-0GF00-0XB0)

Terminal numbering TB1-4/DC

Terminal tier 1

1

Terminal tier 2 not used (internally jumpered)

33

Terminal tier 3

Terminal tier 41

Ground (internally jumpered, connected to M1, M2, M3)

PE (internally jumpered, but not connected to PE screw)

1

Q0: Connection 0/0

17

2

Q0: Connection 0/1

18

3

Q0: Connection 1/0

19

35

4

Q0: Connection 1/1

20

36

5

Q0: Connection 2/0

21

37

6

Q0: Connection 2/1

22

38

7

Q0: Connection 3/0

23

39

8

Q0: Connection 3/1

24

40

9

Q0: Connection 4/0

25

41

10

Q0: Connection 4/1

26

42

11

Q0: Connection 5/0

27

43

12

Q0: Connection 5/1

28

44

13

Q0: Connection 6/0

29

45

14

Q0: Connection 6/1

30

46

15

Q0: Connection 7/0

31

47

16

Q0: Connection 7/1

32

48

–

L1+ not used

M1 not used

–

L2+ not used

M2 not used

–

L3+ Voltage supply, internal logic

M3 Ground connection, internal logic

–

L3+ Voltage supply, internal logic

M3 Ground connection, internal logic

34

7

PE (internally jumpered, but not connected to PE screw)

TB1-4/DC only

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7-47

Page 134

Digital Modules

Important Note on Wiring

The following notes are important as regards the wiring of the ET 200B-8RO:

The terminals for PE on the 4-tier terminal block are not connected to the PE connection of terminal block TB1-4/DC.

M1, M2, M3 and terminals 33 ... 48 are interconnected. The two L3+ terminals are internally interconnected. Technical Data

The technical data of electronics block ET 200B-8RO is listed in the tables below.

Technical specifications

7

Relay outputs

Baud rates*

9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud

Number of outputs Galvanic isolation In groups of

8 Yes 1

Bus protocol

PROFIBUS-DP

SYNC capability

Yes

Galvanic isolation to the SINEC L2-DP bus

Yes

No Max. 5 A Dold OW 5699

Power losses

Typ. 2 W

Weight (EB and TB)

Approx. 650 g (22.75 oz.)

Short-circuit protection Continuous current Ith Relay type Cycling capacity of contacts Resistive load

Dimensions (EB and TB: W x H x D)

160 x 130 x 60 mm (6.24 x 5.07 x 2.34 in.)

Inductive load

Max. 2 A at 24 V DC Max. 1.5 A at 48 V DC Max. 1 A at 60 V DC Max. 0.5 A at 30 V DC

Voltage monitoring

Green “RUN” LED

Mechanical service life Switching rate

> 108 switching operations Max. 20/s

Bus monitoring SINEC L2-DP

Red “BF” LED

Cable length Unshielded

Max. 100 m (328 ft.)

Status of outputs

Green LEDs

Setting of a digital input

Possible

Diagnostics functions

Supply voltage for relay outputs and internal logic Supply voltage (L3+) Rated value Permissible range Value for t < 0.5 s

*

In operation with the IM 308-B, the maximum baud rate is 1500 kbaud.

24 V DC 18.5 to 30.2 V 35 V

Current consumption from L3+ Logic Typ. 130 mA 2 I t (for inrush current) < 0.05 A2s

7-48

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 135

Digital Modules

7.3.7

Electronics Block ET 200B-8DI/8DO (6ES7 133-0BH01-0XB0)

Characteristics

The ET 200B-8DI/8DO electronics block has the following characteristics:

8 inputs, non-floating 8 outputs, non-floating Input voltage: 24 V DC Input delay: 3 ms Load voltage: 24 V DC Possible terminal blocks: TB1/DC, TB1-4/DC or TB3/DC Dimensional Drawing

See Figure 7-18 for the precise dimensions.

7

Figure 7-38 Front Elevation: ET 200B-8DI/8DO (6ES7 133-0BH01-0XB0)

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7-49

Page 136

Digital Modules

Block Diagram

Simplified diagram of potential for the ET 200B-8DI/8DO and TB1/DC or TB3/DC:

ET 200B-8DI/8DO

24 V

PROFIBUS-DP

5V 24 V Logic

5V

+– Driver 8x

8x

I0: 0...7 Q0: 0...7 L1+ Interface between electronics block and terminal block

X1 TB1/DC or TB3/DC

Station number selection

Suppr. logic STOP/RUN switch

Connection PROFIBUS-DP

7

M

PE

L3+ M

I/O Voltage sensor Ground Screw for grounding (see Sec. 3.4)

L1+

Outputs

Inputs

L3+ M

24 V supply

Figure 7-39 Block Diagram: ET 200B-8DI/8DO (6ES7 133-0BH01-0XB0) and TB1/DC or TB3/DC

7-50

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c