Page 127
Digital Modules
Pin Assignment
Table 7-7
The table below shows the pin assignment of the terminal blocks for ET 200B-32DO. For the sake of clarity, the table also shows the terminal numbering of the terminal blocks, taking the TB2-4/DC by way of example.
Pin Assignment of Terminal Blocks TB2/DC, TB2-4/DC, TB4/DC and TB4M/DC for ET 200B-32DO (6ES7 132-0BL01-0XB0)
Terminal numbering TB2-4/DC
Terminal tier 1
Terminal tier 2 Voltage supply L1+ for channel group Q0: .0 to .7 (internally jumpered)
1
Q0: Output .0
33
2
Q0: Output .1
34
3
Q0: Output .2
35
4
Q0: Output .3
36
68
5
Q0: Output .4
37
69
6
Q0: Output .5
38
70
7
Q0: Output .6
39
71
8
Q0: Output .7
40
72
9
Q1: Output .0
41
10
Q1: Output .1
42
Voltage supply L2+ for channel group Q1: .4 to .7 (internally jumpered)
65 66
73 74
11
Q1: Output .2
43
Q1: Output .3
44
76
13
Q1: Output .4
45
77
14
Q1: Output .5
46
78
15
Q1: Output .6
47
79
16
Q1: Output .7
48
80
17
Q2: Output .0
49
18
Q2: Output .1
50
19
Q2: Output .2
51
20
Q2: Output .3
52
84
21
Q2: Output .4
53
85
22
Q2: Output .5
54
86
23
Q2: Output .6
55
87
24
Q2: Output .7
56
88
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Terminal tier 41
Ground M1 for channel group Q0: .0 to .7 (internally jumpered)
PE (internally jumpered, but not connected to PE screw)
67
12
Voltage supply L3+ for channel group Q2: .0 to .7 (internally jumpered)
Terminal tier 3
75
81 82
7 Ground M2 for channel group Q01: .0 to .7 (internally jumpered)
Ground M3 for channel group Q2: .0 to .7 (internally jumpered)
83
7-41
Page 128
Digital Modules
Table 7-7
Pin Assignment of Terminal Blocks TB2/DC, TB2-4/DC, TB4/DC and TB4M/DC for ET 200B-32DO (6ES7 132-0BL01-0XB0), continued Terminal tier 2
Terminal tier 1
1
Voltage supply L4+ for channel group Q3: .0 to .7 (internally jumpered)
89
Terminal tier 3
Terminal tier 41
Ground M4 for channel group Q3: .0 to .7 (internally jumpered)
PE (internally jumpered, but not connected to PE screw)
PE (internally jumpered, but not connected to PE screw)
25
Q3: Output .0
57
26
Q3: Output .1
58
27
Q3: Output .2
59
28
Q3: Output .3
60
92
29
Q3: Output .4
61
93
30
Q3: Output .5
62
94
31
Q3: Output .6
63
95
32
Q3: Output .7
64
96
–
L5+ Voltage supply, internal logic
M5 Ground connection, internal logic
–
L5+ Voltage supply, internal logic
M5 Ground connection, internal logic
90 91
TB2-4/DC only; in the TB4M/DC tier 4 is available for additional ground connections (see Section 7.2.7)
Important Note on Wiring
The following notes are important as regards the wiring of the ET 200B-32DO:
The terminals for PE on the 4-tier terminal block are not connected to the
7
PE connection of terminal block TB2-4/DC.
If all actuators are connected by two-wire cables to the TB2/DC, TB4/DC or TB2-4/DC, connect the ground of an actuator and the supply for the reference potential per group by means of a DIN 46231 cable cleat.
L1+ ... L5+ and M1 ... M5 are not internally interconnected. The two L5+ terminals are internally interconnected.
7-42
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 129
Digital Modules
Technical Data
The technical data of electronics block ET 200B-32DO is listed in the tables below.
Technical specifications
Outputs
Baud rates*
9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud
Number of outputs Galvanic isolation In groups of
Bus protocol
PROFIBUS-DP
SYNC capability
Yes
Galvanic isolation to SINEC L2-DP bus
Yes
Output voltage For “0” signal For “1” signal
Power losses
Max. 7.9 W
Weight (EB and TB)
Approx. 800 g (28 oz.)
Dimensions (EB and TB: W x H x D)
235 x 130 x 60 mm (9.17 x 5.07 x 2.34 in.)
Diagnostics functions Voltage monitoring
Green “RUN ”LED
Bus monitoring SINEC L2-DP
Red “BF” LED
Group diagnostics for short-circuit, load voltage failure
Red “DIA” LED
Load voltage monitoring
Green “L1+/L2+”, “L3+/L4+” LEDs
Status of outputs
Green LEDs
Supply voltage for outputs, load voltage supply and internal logic Supply voltage (L1+,L2+,L3+,L4+,L5+) Rated value Permissible range Value for t < 0.5 s
24 V DC 18.5 to 30.2 V 35 V
32 Yes 8 Max. 2 V (idle) Min. (supply voltage – 3 V)
Output current For “0” signal For “1” signal
Max. 1 mA Max. 0.5 A
Delay of outputs From “0” to “1” From “1” to “0”
Approx. 20 ms Max. 0.5 ms
Switching frequency Resistive load Inductive load Lamp load
Max. 1000 Hz Max. 0.5 Hz Max. 8 Hz
Short-circuit protection
Yes
Load current per group Total current
Max. 2 A
Lamp load
Max. 5 W
Setting a digital input
Possible
Limitation of voltage induced on current interruption
Typ. (L1+ ... L4+) – 55 V
Cable length
Max. 100 m (328 ft.)
*
7
In operation with the IM 308-B, the maximum baud rate is 1500 kbaud.
I2 t < 0.05 A2s (for inrush current) Current consumption from L5+ Logic Typ. 75 mA
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
7-43
Page 130
Digital Modules
7.3.6
Electronics block ET 200B-8RO (6ES7 132-0GF00-0XB0)
Characteristics
The ET 200B-8RO electronics block has the following characteristics:
8 relay outputs, floating in groups of 1 Switching voltage: 24 to 60 V DC Possible terminal blocks: TB1/DC, TB1-4/DC or TB3/DC Dimensional Drawing
See Figure 7-18 for the precise dimensions.
7
Figure 7-35 Front Elevation: ET 200B-8RO (6ES7 132-0GF00-0XB0)
7-44
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 131
Digital Modules
Block Diagram
Simplified diagram of the potential for the ET 200B-8RO and TB1/DC or TB3/DC:
ET 200B-8RO
24 V
PROFIBUS-DP
5V 24 V Logic
5V
8x
X/0 X/1 Interface between electronics block and terminal block
X1 TB1/DC or TB3/DC
Station number selection
Suppr. logic STOP/RUN switch
Connection PROFIBUS-DP Contact
M
L3+ M
L1+L2+ L3+ M
Ground PE
Screw for grounding (see Sec. 3.4)
Relay outputs
24 V supply
Figure 7-36 Block Diagram: ET 200B-8RO (6ES7 132-0GF00-0XB0) and TB1/DC or TB3/DC
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
7-45
7
Page 132
Digital Modules
Block Diagram
Simplified diagram of the potential for the ET 200B-8RO and TB1-4/DC:
ET 200B-8RO
24 V
PROFIBUS-DP
5V 24 V Logic
5V
8x
X/0 X/1 Interface between electronics block and terminal block
X1 TB1-4/DC
Station number selection
Suppr. logic STOP/RUN switch
Connection PROFIBUS-DP
7
Contact
M
L3+ M
L1+L2+ L3+ M
Ground PE PE
Screw for grounding (see Sec. 3.4)
Relay outputs
24 V supply
Figure 7-37 Block Diagram: ET 200B-8RO (6ES7 132-0GF00-0XB0) and TB1-4/DC
7-46
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 133
Digital Modules
Pin Assignment
Table 7-8
The table below shows the pin assignment of the terminal blocks for ET 200B-8RO. For the sake of clarity, the table also shows the terminal numbering of the terminal blocks, taking the TB1-4/DC by way of example.
Pin Assignment of Terminal Blocks TB1/DC; TB1-4/DC and TB3/DC for ET 200B-8RO (6ES7 132-0GF00-0XB0)
Terminal numbering TB1-4/DC
Terminal tier 1
1
Terminal tier 2 not used (internally jumpered)
33
Terminal tier 3
Terminal tier 41
Ground (internally jumpered, connected to M1, M2, M3)
PE (internally jumpered, but not connected to PE screw)
1
Q0: Connection 0/0
17
2
Q0: Connection 0/1
18
3
Q0: Connection 1/0
19
35
4
Q0: Connection 1/1
20
36
5
Q0: Connection 2/0
21
37
6
Q0: Connection 2/1
22
38
7
Q0: Connection 3/0
23
39
8
Q0: Connection 3/1
24
40
9
Q0: Connection 4/0
25
41
10
Q0: Connection 4/1
26
42
11
Q0: Connection 5/0
27
43
12
Q0: Connection 5/1
28
44
13
Q0: Connection 6/0
29
45
14
Q0: Connection 6/1
30
46
15
Q0: Connection 7/0
31
47
16
Q0: Connection 7/1
32
48
–
L1+ not used
M1 not used
–
L2+ not used
M2 not used
–
L3+ Voltage supply, internal logic
M3 Ground connection, internal logic
–
L3+ Voltage supply, internal logic
M3 Ground connection, internal logic
34
7
PE (internally jumpered, but not connected to PE screw)
TB1-4/DC only
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
7-47
Page 134
Digital Modules
Important Note on Wiring
The following notes are important as regards the wiring of the ET 200B-8RO:
The terminals for PE on the 4-tier terminal block are not connected to the PE connection of terminal block TB1-4/DC.
M1, M2, M3 and terminals 33 ... 48 are interconnected. The two L3+ terminals are internally interconnected. Technical Data
The technical data of electronics block ET 200B-8RO is listed in the tables below.
Technical specifications
7
Relay outputs
Baud rates*
9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud
Number of outputs Galvanic isolation In groups of
8 Yes 1
Bus protocol
PROFIBUS-DP
SYNC capability
Yes
Galvanic isolation to the SINEC L2-DP bus
Yes
No Max. 5 A Dold OW 5699
Power losses
Typ. 2 W
Weight (EB and TB)
Approx. 650 g (22.75 oz.)
Short-circuit protection Continuous current Ith Relay type Cycling capacity of contacts Resistive load
Dimensions (EB and TB: W x H x D)
160 x 130 x 60 mm (6.24 x 5.07 x 2.34 in.)
Inductive load
Max. 2 A at 24 V DC Max. 1.5 A at 48 V DC Max. 1 A at 60 V DC Max. 0.5 A at 30 V DC
Voltage monitoring
Green “RUN” LED
Mechanical service life Switching rate
> 108 switching operations Max. 20/s
Bus monitoring SINEC L2-DP
Red “BF” LED
Cable length Unshielded
Max. 100 m (328 ft.)
Status of outputs
Green LEDs
Setting of a digital input
Possible
Diagnostics functions
Supply voltage for relay outputs and internal logic Supply voltage (L3+) Rated value Permissible range Value for t < 0.5 s
*
In operation with the IM 308-B, the maximum baud rate is 1500 kbaud.
24 V DC 18.5 to 30.2 V 35 V
Current consumption from L3+ Logic Typ. 130 mA 2 I t (for inrush current) < 0.05 A2s
7-48
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 135
Digital Modules
7.3.7
Electronics Block ET 200B-8DI/8DO (6ES7 133-0BH01-0XB0)
Characteristics
The ET 200B-8DI/8DO electronics block has the following characteristics:
8 inputs, non-floating 8 outputs, non-floating Input voltage: 24 V DC Input delay: 3 ms Load voltage: 24 V DC Possible terminal blocks: TB1/DC, TB1-4/DC or TB3/DC Dimensional Drawing
See Figure 7-18 for the precise dimensions.
7
Figure 7-38 Front Elevation: ET 200B-8DI/8DO (6ES7 133-0BH01-0XB0)
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
7-49
Page 136
Digital Modules
Block Diagram
Simplified diagram of potential for the ET 200B-8DI/8DO and TB1/DC or TB3/DC:
ET 200B-8DI/8DO
24 V
PROFIBUS-DP
5V 24 V Logic
5V
+– Driver 8x
8x
I0: 0...7 Q0: 0...7 L1+ Interface between electronics block and terminal block
X1 TB1/DC or TB3/DC
Station number selection
Suppr. logic STOP/RUN switch
Connection PROFIBUS-DP
7
M
PE
L3+ M
I/O Voltage sensor Ground Screw for grounding (see Sec. 3.4)
L1+
Outputs
Inputs
L3+ M
24 V supply
Figure 7-39 Block Diagram: ET 200B-8DI/8DO (6ES7 133-0BH01-0XB0) and TB1/DC or TB3/DC
7-50
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c