Page 117

Digital Modules

Technical Data

The technical data of electronics block ET 200B-16DO is listed in the tables below.

Technical specifications

Outputs

Baud rates*

9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud

Number of outputs Galvanic isolation In groups of

Bus protocol

PROFIBUS-DP

SYNC capability

Yes

Galvanic isolation to SINEC L2-DP bus

Yes

Output voltage For “0” signal For “1” signal

Power losses

Max. 5 W

Weight (EB and TB)

Approx. 600 g (21 oz.)

Dimensions (EB and TB: W x H x D)

160 x 130 x 60 mm (6.24 x 5.07 x 2.34 in.)

Output voltage For “0” signal For “1” signal

Diagnostics functions Voltage monitoring

Green “RUN” LED

Bus monitoring SINEC L2-DP

Red “BF” LED

Group diagnostics for short-circuit, load voltage failure

Red “DIA ”LED

Load voltage monitoring, by group

Green “L1+”, “L2+” LEDs

Status of outputs

Green LEDs

Supply voltage for outputs, load voltage supply and internal logic Supply voltages (L1+,L2+,L3+) Rated value Permissible range Value for t < 0.5 s

24 V DC 18.5 to 30.2 V 35 V

Current consumption from L3+ Logic 80 mA I2t (for inrush current) Short-circuit protection in case of polarity reversal (L1+ and L2+) of load voltage

16 No 8 Max. 2 V (idle) Min. (supply voltage – 3 V) Max. 1 mA Max. 2 A (2 outputs per group; .0 and .1) Max. 0.5 A (6 outputs per group; .2 to .7)

Delay of outputs At max. lamp load

Max. 1 ms Max. 80 ms

Switching frequency Resistive load Inductive load Lamp load

Max. 100 Hz Max. 0.5 Hz Max. 8 Hz

Load current per group Total current In case of short-circuit

Max. 4 A Max. 6.5 A

Lamp load At I = 0.5 A At I = 2 A

Max. 5 W Max. 10 W

Setting a digital input

Possible

Limitation of voltage induced on current interruption

Typ. (L1+, L2+) –55 V

Cable length

Max. 100 m (328 ft.)

*

7

In operation with the IM 308-B, the maximum baud rate is 1500 kbaud.

< 0.05 A2s No

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7-31

Page 118

Digital Modules

7.3.4

Electronics Block ET 200B-16DO/2A (6ES7 132-0BH11-0XB0)

Characteristics

The ET 200B-16DO/2A electronics block has the following characteristics:

16 outputs, floating in groups of 4 Load voltage: 24 V DC Output current: 2 A Possible terminal blocks: TB2/DC, TB2-4/DC, TB4/DC, TB4M/DC Dimensional Drawing

See Figure 7-22 for the precise dimensions.

7

Figure 7-29 Front Elevation: ET 200B-16DO/2A (6ES7 132-0BH11-0XB0)

7-32

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 119

Digital Modules

Block Diagram

Simplified diagram of potential for the ET 200B-16DO/2A and TB2/DC or TB4/DC:

ET 200B-16DO/2A

24 V

PROFIBUS-DP

5V 24 V Logic

4x

4x

4x

Q0: Q0: Q1: Q1: L1+ M1 0...3 L2+ M2 4...7 L3+ M3 0...3 L4+ M4 4...7 Interface between electronics block and terminal block

X1 TB2/DC or TB4/DC

4x

5V

Station number selection Connection PROFIBUS-DP M5

Suppr. logic L1+M1

Suppr. logic L2+M2

Suppr. logic L3+M3

Suppr. logic L4+M4

L5+ M5

Suppr. logic STOP/RUN switch L5+ M5

Out. Supply Ground

PE Screw for grounding (see Sec. 3.4)

Digital outputs

24 V supply

Figure 7-30 Block Diagram: ET 200B-16DO/2A (6ES7 132-0BH11-0XB0) and TB2/DC or TB4/DC

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7-33

7

Page 120

Digital Modules

Block Diagram

Simplified diagram of the potential for the ET 200B-16DO/2A and TB2/DC or TB4/DC:

ET 200B-16DO/2A

24 V

PROFIBUS-DP

5V 24 V Logic

4x

4x

Station number selection Connection PROFIBUS-DP

7

4x

Q0: Q0: Q1: Q1: L1+ M1 0...3 L2+ M2 4...7 L3+ M3 0...3 L4+ M4 4...7 Interface between electronics block and terminal block

X1 TB2-4/DC

4x

5V

M5

PE

Suppr. logic L1+M1

Suppr. logic L2+M2

Suppr. logic

Suppr. logic

L3+M3

L4+M4

L5+ M5

Suppr. logic STOP/RUN switch L5+ M5

Out. Supply Ground PE Screw for grounding (see Sec. 3.4)

Digital outputs

24 V supply

Figure 7-31 Block Diagram: ET 200B-16DO/2A (6ES7 132-0BH11-0XB0) and TB2-4/DC

7-34

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 121

Digital Modules

Pin Assignment

Table 7-6

The table below shows the pin assignment of the terminal blocks for ET 200B-16DO/2A. For the sake of clarity, the table also shows the terminal numbering of the terminal blocks, taking the TB2-4/DC by way of example.

Pin Assignment of Terminal Blocks TB2/DC; TB2-4/DC, TB4/DC and TB4M/DC for ET 200B-16DO/2A (6ES7 132-0BH11-0XB0)

Terminal numbering TB2-4/DC

Terminal tier 1

Terminal tier 2 Voltage supply L1+ for channel group Q0: .0 to .3 (internally jumpered)

1

Q0: Output .0

33

2 not used

34

3

Q0: Output .1

35

4 not used

36

68

5

Q0: Output .2

37

69

6 not used

38

70

7

Q0: Output .3

39

71

8 not used

40

72

9

Q0: Output .4

41

10 not used

42

Voltage supply L2+ for channel group Q0: .4 to .7 (internally jumpered)

65 66

73 74

11

Q0: Output .5

43 not used

44

76

13

Q0: Output .6

45

77

14 not used

46

78

15

Q0: Output .7

47

79

16 not used

48

80

17

Q1: Output .0

49

18 not used

50

19

Q1: Output .1

51

20 not used

52

84

21

Q1: Output .2

53

85

22 not used

54

86

23

Q1: Output .3

55

87

24 not used

56

88

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Terminal tier 41

Ground M1 for channel group Q0: .0 to .3 (internally jumpered)

PE (internally jumpered, but not connected to PE screw)

67

12

Voltage supply L3+ for channel group Q1: .0 to .3 (internally jumpered)

Terminal tier 3

7 Ground M2 for channel group Q0: .4 to .7 (internally jumpered)

75

81 82

Ground M3 for channel group Q1: .0 to .3 (internally jumpered)

83

7-35

Page 122

Digital Modules

Table 7-6

Pin Assignment of Terminal Blocks TB2/DC; TB2-4/DC, TB4/DC and TB4M/DC for ET 200B-16DO/2A (6ES7 132-0BH11-0XB0), continued Terminal tier 2

Terminal tier 1

1

Voltage supply L4+ for channel group Q1: .4 to .7 (internally jumpered)

89

Terminal tier 3

Terminal tier 41

Ground M4 for channel group Q1: .4 to .7 (internally jumpered)

PE (internally jumpered, but not connected to PE screw)

PE (internally jumpered, but not connected to PE screw)

25

Q1: Output .4

57

26 not used

58

27

Q1: Output .5

59

28 not used

60

92

29

Q1: Output .6

61

93

30 not used

62

94

31

Q1: Output .7

63

95

32 not used

64

96

–

L5+ Voltage supply, internal logic

M5 Ground connection, internal logic

–

L5+ Voltage supply, internal logic

M5 Ground connection, internal logic

90 91

TB2-4/DC only; in the TB4M/DC tier 4 is available for additional ground connections (see Section 7.2.7)

Important Note on Wiring

The following notes are important as regards the wiring of the ET 200B-16DO/2A:

The terminals for PE on the 4-tier terminal block are not connected to the

7

PE connection of terminal block TB2-4/DC.

L1+ ... L5+ and M1 ... M5 are not internally interconnected. The two L5+ terminals are internally interconnected.

7-36

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 123

Digital Modules

Technical Data

The technical data of electronics block ET 200B-16DO/2A is listed in the tables below.

Technical specifications

Outputs

Baud rates*

9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud

Number of outputs Galvanic isolation In groups of

Bus protocol

PROFIBUS-DP

SYNC capability

Yes

Galvanic isolation to SINEC L2-DP bus

Yes

Output voltage For “0” signal For “1” signal

Power losses

Max. 7 W

Weight (EB and TB)

Approx. 900 g (31.5 oz.)

Dimensions (EB and TB: W x H x D)

235 x 130 x 60 mm (9.17 x 5.07 x 2.34 in.)

Diagnostics functions

16 Yes 4 Max. 2 V (idle) Min. (supply voltage – 3 V)

Output For “0” signal For “1” signal

Max. 1 mA Max. 2 A

Delay of outputs At max. lamp load

Max. 1 ms Max. 80 ms

Switching frequency Resistive load Inductive load Lamp load

Max. 100 Hz Max. 0.5 Hz Max. 8 Hz

Voltage monitoring

Green “RUN” LED

Bus monitoring SINEC L2-DP

Red “BF” LED

Group diagnostics for short-circuit, load voltage failure

Red “DIA” LED

Load current per group Total current In case of short-circuit

Max. 4 A Max. 6.5 A

Load voltage monitoring, by channel group (QO, Q1)

Green LEDs “L1+”/“L2+” (QO: .0 to 7) “L3+”/“L4+” (Q1: .0 to 7)

Lamp load

Max. 10 W

Setting a digital input

Possible

Status of outputs

Green LEDs

Limit of inductive cutoff voltage

Typ. (L1+ ... L4+) – 50 V

Supply voltage for outputs, load voltage supply and internal logic

Cable length

Max. 100 m (328 ft.)

Supply voltage (L1+,L2+,L3+,L4+,L5+) Rated value Permissible range Value at t < 0.5 s

*

7

In operation with the IM 308-B, the maximum baud rate is 1500 kbaud.

24 V DC 18.5 to 30.2 V 35 V

Current consumption from L5+ Logic 100 mA I2 t (for inrush current) Short-circuit protection in case of polarity reversal (L1+,L2+,L3+,L4+) of load voltage

< 0.05 A2s No

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7-37

Page 124

Digital Modules

7.3.5

Electronics Block ET 200B-32DO (6ES7 132-0BL01-0XB0)

Characteristics

The ET 200B-32DO electronics block has the following characteristics:

32 outputs, floating in groups of 8 Load voltage: 24 V DC Output voltage: 0.5 A Suitable for solenoid valves and DC contactors Possible terminal blocks: TB2/DC, TB2-4/DC, TB4/DC, TB4M/DC Dimensional Drawing

See Figure 7-22 for the precise dimensions.

7

Figure 7-32 Front Elevation: ET 200B-32DO (6ES7 132-0BL01-0XB0)

7-38

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 125

Digital Modules

Block Diagram

Simplified diagram of potential for the ET 200B-32DO and TB2/DC or TB4/DC:

ET 200B-32DO

24 V

PROFIBUS-DP

5V 24 V Logic

Driver

Driver

Driver

Driver

8x

8x

8x

8x

Q0: Q1: Q2: Q3: L1+ M1 0...7 L2+ M2 0...7 L3+ M3 0...7 L4+ M4 0...7 Interface between electronics block and terminal block

X1 TB2/DC or TB4/DC

5V

Station number selection Connection PROFIBUS-DP M5

PE

Suppr. logic L1+M1

Suppr. logic L2+M2

Suppr. logic L3+M3

Suppr. logic L4+M4

L5+ M5

Suppr. logic STOP/RUN switch L5+ M5

Out. Supply Ground Screw for grounding (see Sec. 3.4)

Digital outputs

24 V supply

Figure 7-33 Block Diagram: ET 200B-32DO (6ES7 132-0BL01-0XB0) and TB2/DC or TB4/DC

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7-39

7

Page 126

Digital Modules

Block Diagram

Simplified diagram of the potential for the ET 200B-32DO and TB2-4/DC:

ET 200B-32DO

24 V

PROFIBUS-DP

5V 24 V Logic

Driver

Driver

Driver

Driver

8x

8x

8x

8x

Q0: Q1: Q2: Q3: L1+ M1 0...7 L2+ M2 0...7 L3+ M3 0...7 L4+ M4 0...7 Interface between electronics block and terminal block

X1 TB2-4/DC

Station number selection Connection PROFIBUS-DP

Suppr. logic L1+M1

M5

7

5V

PE

Suppr. logic L2+M2

Suppr. logic

Suppr. logic

L3+M3

L4+M4

L5+ M5

Suppr. logic STOP/RUN switch L5+ M5

Out. Supply Ground PE Screw for grounding (see Sec. 3.4)

Digital outputs

24 V supply

Figure 7-34 Block Diagram: ET 200B-32DO (6ES7 132-0BL01-0XB0) and TB2-4/DC

7-40

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c