The text of a manual · part 17 of 41
SIMATIC ET 200B Distributed I/O Station Manual: 7 Digital Modules, pages 117 to 126
Pages 117 to 126 of 344, from SIMATIC ET 200B Distributed I/O Station Manual
The original document is the PDF (2.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens ET 200B
Page 117
Digital Modules
Technical Data
The technical data of electronics block ET 200B-16DO is listed in the tables below.
Technical specifications
Outputs
Baud rates*
9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud
Number of outputs Galvanic isolation In groups of
Bus protocol
PROFIBUS-DP
SYNC capability
Yes
Galvanic isolation to SINEC L2-DP bus
Yes
Output voltage For “0” signal For “1” signal
Power losses
Max. 5 W
Weight (EB and TB)
Approx. 600 g (21 oz.)
Dimensions (EB and TB: W x H x D)
160 x 130 x 60 mm (6.24 x 5.07 x 2.34 in.)
Output voltage For “0” signal For “1” signal
Diagnostics functions Voltage monitoring
Green “RUN” LED
Bus monitoring SINEC L2-DP
Red “BF” LED
Group diagnostics for short-circuit, load voltage failure
Red “DIA ”LED
Load voltage monitoring, by group
Green “L1+”, “L2+” LEDs
Status of outputs
Green LEDs
Supply voltage for outputs, load voltage supply and internal logic Supply voltages (L1+,L2+,L3+) Rated value Permissible range Value for t < 0.5 s
24 V DC 18.5 to 30.2 V 35 V
Current consumption from L3+ Logic 80 mA I2t (for inrush current) Short-circuit protection in case of polarity reversal (L1+ and L2+) of load voltage
16 No 8 Max. 2 V (idle) Min. (supply voltage – 3 V) Max. 1 mA Max. 2 A (2 outputs per group; .0 and .1) Max. 0.5 A (6 outputs per group; .2 to .7)
Delay of outputs At max. lamp load
Max. 1 ms Max. 80 ms
Switching frequency Resistive load Inductive load Lamp load
Max. 100 Hz Max. 0.5 Hz Max. 8 Hz
Load current per group Total current In case of short-circuit
Max. 4 A Max. 6.5 A
Lamp load At I = 0.5 A At I = 2 A
Max. 5 W Max. 10 W
Setting a digital input
Possible
Limitation of voltage induced on current interruption
Typ. (L1+, L2+) –55 V
Cable length
Max. 100 m (328 ft.)
*
7
In operation with the IM 308-B, the maximum baud rate is 1500 kbaud.
< 0.05 A2s No
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
7-31
Page 118
Digital Modules
7.3.4
Electronics Block ET 200B-16DO/2A (6ES7 132-0BH11-0XB0)
Characteristics
The ET 200B-16DO/2A electronics block has the following characteristics:
16 outputs, floating in groups of 4 Load voltage: 24 V DC Output current: 2 A Possible terminal blocks: TB2/DC, TB2-4/DC, TB4/DC, TB4M/DC Dimensional Drawing
See Figure 7-22 for the precise dimensions.
7
Figure 7-29 Front Elevation: ET 200B-16DO/2A (6ES7 132-0BH11-0XB0)
7-32
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 119
Digital Modules
Block Diagram
Simplified diagram of potential for the ET 200B-16DO/2A and TB2/DC or TB4/DC:
ET 200B-16DO/2A
24 V
PROFIBUS-DP
5V 24 V Logic
4x
4x
4x
Q0: Q0: Q1: Q1: L1+ M1 0...3 L2+ M2 4...7 L3+ M3 0...3 L4+ M4 4...7 Interface between electronics block and terminal block
X1 TB2/DC or TB4/DC
4x
5V
Station number selection Connection PROFIBUS-DP M5
Suppr. logic L1+M1
Suppr. logic L2+M2
Suppr. logic L3+M3
Suppr. logic L4+M4
L5+ M5
Suppr. logic STOP/RUN switch L5+ M5
Out. Supply Ground
PE Screw for grounding (see Sec. 3.4)
Digital outputs
24 V supply
Figure 7-30 Block Diagram: ET 200B-16DO/2A (6ES7 132-0BH11-0XB0) and TB2/DC or TB4/DC
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
7-33
7
Page 120
Digital Modules
Block Diagram
Simplified diagram of the potential for the ET 200B-16DO/2A and TB2/DC or TB4/DC:
ET 200B-16DO/2A
24 V
PROFIBUS-DP
5V 24 V Logic
4x
4x
Station number selection Connection PROFIBUS-DP
7
4x
Q0: Q0: Q1: Q1: L1+ M1 0...3 L2+ M2 4...7 L3+ M3 0...3 L4+ M4 4...7 Interface between electronics block and terminal block
X1 TB2-4/DC
4x
5V
M5
PE
Suppr. logic L1+M1
Suppr. logic L2+M2
Suppr. logic
Suppr. logic
L3+M3
L4+M4
L5+ M5
Suppr. logic STOP/RUN switch L5+ M5
Out. Supply Ground PE Screw for grounding (see Sec. 3.4)
Digital outputs
24 V supply
Figure 7-31 Block Diagram: ET 200B-16DO/2A (6ES7 132-0BH11-0XB0) and TB2-4/DC
7-34
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 121
Digital Modules
Pin Assignment
Table 7-6
The table below shows the pin assignment of the terminal blocks for ET 200B-16DO/2A. For the sake of clarity, the table also shows the terminal numbering of the terminal blocks, taking the TB2-4/DC by way of example.
Pin Assignment of Terminal Blocks TB2/DC; TB2-4/DC, TB4/DC and TB4M/DC for ET 200B-16DO/2A (6ES7 132-0BH11-0XB0)
Terminal numbering TB2-4/DC
Terminal tier 1
Terminal tier 2 Voltage supply L1+ for channel group Q0: .0 to .3 (internally jumpered)
1
Q0: Output .0
33
2 not used
34
3
Q0: Output .1
35
4 not used
36
68
5
Q0: Output .2
37
69
6 not used
38
70
7
Q0: Output .3
39
71
8 not used
40
72
9
Q0: Output .4
41
10 not used
42
Voltage supply L2+ for channel group Q0: .4 to .7 (internally jumpered)
65 66
73 74
11
Q0: Output .5
43 not used
44
76
13
Q0: Output .6
45
77
14 not used
46
78
15
Q0: Output .7
47
79
16 not used
48
80
17
Q1: Output .0
49
18 not used
50
19
Q1: Output .1
51
20 not used
52
84
21
Q1: Output .2
53
85
22 not used
54
86
23
Q1: Output .3
55
87
24 not used
56
88
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Terminal tier 41
Ground M1 for channel group Q0: .0 to .3 (internally jumpered)
PE (internally jumpered, but not connected to PE screw)
67
12
Voltage supply L3+ for channel group Q1: .0 to .3 (internally jumpered)
Terminal tier 3
7 Ground M2 for channel group Q0: .4 to .7 (internally jumpered)
75
81 82
Ground M3 for channel group Q1: .0 to .3 (internally jumpered)
83
7-35
Page 122
Digital Modules
Table 7-6
Pin Assignment of Terminal Blocks TB2/DC; TB2-4/DC, TB4/DC and TB4M/DC for ET 200B-16DO/2A (6ES7 132-0BH11-0XB0), continued Terminal tier 2
Terminal tier 1
1
Voltage supply L4+ for channel group Q1: .4 to .7 (internally jumpered)
89
Terminal tier 3
Terminal tier 41
Ground M4 for channel group Q1: .4 to .7 (internally jumpered)
PE (internally jumpered, but not connected to PE screw)
PE (internally jumpered, but not connected to PE screw)
25
Q1: Output .4
57
26 not used
58
27
Q1: Output .5
59
28 not used
60
92
29
Q1: Output .6
61
93
30 not used
62
94
31
Q1: Output .7
63
95
32 not used
64
96
–
L5+ Voltage supply, internal logic
M5 Ground connection, internal logic
–
L5+ Voltage supply, internal logic
M5 Ground connection, internal logic
90 91
TB2-4/DC only; in the TB4M/DC tier 4 is available for additional ground connections (see Section 7.2.7)
Important Note on Wiring
The following notes are important as regards the wiring of the ET 200B-16DO/2A:
The terminals for PE on the 4-tier terminal block are not connected to the
7
PE connection of terminal block TB2-4/DC.
L1+ ... L5+ and M1 ... M5 are not internally interconnected. The two L5+ terminals are internally interconnected.
7-36
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 123
Digital Modules
Technical Data
The technical data of electronics block ET 200B-16DO/2A is listed in the tables below.
Technical specifications
Outputs
Baud rates*
9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud
Number of outputs Galvanic isolation In groups of
Bus protocol
PROFIBUS-DP
SYNC capability
Yes
Galvanic isolation to SINEC L2-DP bus
Yes
Output voltage For “0” signal For “1” signal
Power losses
Max. 7 W
Weight (EB and TB)
Approx. 900 g (31.5 oz.)
Dimensions (EB and TB: W x H x D)
235 x 130 x 60 mm (9.17 x 5.07 x 2.34 in.)
Diagnostics functions
16 Yes 4 Max. 2 V (idle) Min. (supply voltage – 3 V)
Output For “0” signal For “1” signal
Max. 1 mA Max. 2 A
Delay of outputs At max. lamp load
Max. 1 ms Max. 80 ms
Switching frequency Resistive load Inductive load Lamp load
Max. 100 Hz Max. 0.5 Hz Max. 8 Hz
Voltage monitoring
Green “RUN” LED
Bus monitoring SINEC L2-DP
Red “BF” LED
Group diagnostics for short-circuit, load voltage failure
Red “DIA” LED
Load current per group Total current In case of short-circuit
Max. 4 A Max. 6.5 A
Load voltage monitoring, by channel group (QO, Q1)
Green LEDs “L1+”/“L2+” (QO: .0 to 7) “L3+”/“L4+” (Q1: .0 to 7)
Lamp load
Max. 10 W
Setting a digital input
Possible
Status of outputs
Green LEDs
Limit of inductive cutoff voltage
Typ. (L1+ ... L4+) – 50 V
Supply voltage for outputs, load voltage supply and internal logic
Cable length
Max. 100 m (328 ft.)
Supply voltage (L1+,L2+,L3+,L4+,L5+) Rated value Permissible range Value at t < 0.5 s
*
7
In operation with the IM 308-B, the maximum baud rate is 1500 kbaud.
24 V DC 18.5 to 30.2 V 35 V
Current consumption from L5+ Logic 100 mA I2 t (for inrush current) Short-circuit protection in case of polarity reversal (L1+,L2+,L3+,L4+) of load voltage
< 0.05 A2s No
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
7-37
Page 124
Digital Modules
7.3.5
Electronics Block ET 200B-32DO (6ES7 132-0BL01-0XB0)
Characteristics
The ET 200B-32DO electronics block has the following characteristics:
32 outputs, floating in groups of 8 Load voltage: 24 V DC Output voltage: 0.5 A Suitable for solenoid valves and DC contactors Possible terminal blocks: TB2/DC, TB2-4/DC, TB4/DC, TB4M/DC Dimensional Drawing
See Figure 7-22 for the precise dimensions.
7
Figure 7-32 Front Elevation: ET 200B-32DO (6ES7 132-0BL01-0XB0)
7-38
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 125
Digital Modules
Block Diagram
Simplified diagram of potential for the ET 200B-32DO and TB2/DC or TB4/DC:
ET 200B-32DO
24 V
PROFIBUS-DP
5V 24 V Logic
Driver
Driver
Driver
Driver
8x
8x
8x
8x
Q0: Q1: Q2: Q3: L1+ M1 0...7 L2+ M2 0...7 L3+ M3 0...7 L4+ M4 0...7 Interface between electronics block and terminal block
X1 TB2/DC or TB4/DC
5V
Station number selection Connection PROFIBUS-DP M5
PE
Suppr. logic L1+M1
Suppr. logic L2+M2
Suppr. logic L3+M3
Suppr. logic L4+M4
L5+ M5
Suppr. logic STOP/RUN switch L5+ M5
Out. Supply Ground Screw for grounding (see Sec. 3.4)
Digital outputs
24 V supply
Figure 7-33 Block Diagram: ET 200B-32DO (6ES7 132-0BL01-0XB0) and TB2/DC or TB4/DC
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
7-39
7
Page 126
Digital Modules
Block Diagram
Simplified diagram of the potential for the ET 200B-32DO and TB2-4/DC:
ET 200B-32DO
24 V
PROFIBUS-DP
5V 24 V Logic
Driver
Driver
Driver
Driver
8x
8x
8x
8x
Q0: Q1: Q2: Q3: L1+ M1 0...7 L2+ M2 0...7 L3+ M3 0...7 L4+ M4 0...7 Interface between electronics block and terminal block
X1 TB2-4/DC
Station number selection Connection PROFIBUS-DP
Suppr. logic L1+M1
M5
7
5V
PE
Suppr. logic L2+M2
Suppr. logic
Suppr. logic
L3+M3
L4+M4
L5+ M5
Suppr. logic STOP/RUN switch L5+ M5
Out. Supply Ground PE Screw for grounding (see Sec. 3.4)
Digital outputs
24 V supply
Figure 7-34 Block Diagram: ET 200B-32DO (6ES7 132-0BL01-0XB0) and TB2-4/DC
7-40
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c