Page 107

Digital Modules

Block Diagram

Simplified diagram of potential for the ET 200B-32DI or ET 200B-32DI 0.2 ms and TB2/DC or TB4/DC:

ET 200B-32DI ET 200B-32DI 0.2ms

24 V

PROFIBUS-DP

5V 24 V Logic

5V

+–

32x I0: 0...7 I1: 0...7 I2: 0...7 I3: 0...7 Interface between electronics block and terminal block

X1 TB2/DC or TB4/DC

Station number selection

Suppr. logic STOP/RUN switch

Connection PROFIBUS-DP

L5+ M5

Out. Voltage sensor

M5

L5+ M5

Ground PE

Screw for grounding (see Sec. 3.4)

Digital inputs

24 V supply

Figure 7-24 Block Diagram: ET 200B-32DI (6ES7 131-0BL00-0XB0) or ET 200B-32DI 0.2ms (6ES7 131-0BL10-0XB0) and TB2/DC or TB4/DC

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7-21

7

Page 108

Digital Modules

Block Diagram

Simplified diagram of the potential for the ET 200B-32DI or ET 200B-32DI 0.2 ms and TB2-4/DC:

ET 200B-32DI ET 200B-32DI 0.2ms

24 V

PROFIBUS-DP

5V 24 V Logic

5V

+–

32x I0: 0...7 I1: 0...7 I2: 0...7 I3: 0...7 Interface between electronics block and terminal block

X1 TB2-4/DC

Station number selection

Suppr. logic STOP/RUN switch

Connection PROFIBUS-DP

7

M5

PE

Out. Voltage sensor Ground PE Screw for grounding (see Sec. 3.4)

L5+ M5

L5+ M5

Digital inputs

24 V supply

Figure 7-25 Block Diagram: ET 200B-32DI (6ES7 131-0BL00-0XB0) or ET 200B-32DI 0.2ms (6ES7 131-0BL10-0XB0) and TB2-4/DC

7-22

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 109

Digital Modules

Pin Assignment

Table 7-4

The table below shows the pin assignment of the terminal blocks for ET 200B-32DI and ET 200B-32DI 0.2 ms. For the sake of clarity, the table also shows the terminal numbering of the terminal blocks, taking the TB2-4/DC by way of example.

Pin Assignment of Terminal Blocks TB2/DC, TB2-4/DC, TB4/DC and TB4M/DC for ET 200B-32DI (6ES7 131-0BL00-0XB0) and ET 200B-32DI 0.2ms (6ES7 131-0BL10-0XB0)

Terminal numbering TB2-4/DC

Terminal tier 1

Terminal tier 2 24 V (sensor voltage, internally jumpered, connected to L5+)

1

I0: Input .0

33

2

I0: Input .1

34

3

I0: Input .2

35

67

4

I0: Input .3

36

68

5

I0: Input .4

37

69

6

I0: Input .5

38

70

7

I0: Input .6

39

71

8

I0: Input .7

40

72

9

I1: Input .0

41

73

10

I1: Input .1

42

74

11

I1: Input .2

43

75

12

I1: Input .3

44

76

13

I1: Input .4

45

77

14

I1: Input .5

46

78

15

I1: Input .6

47

79

16

I1: Input .7

48

80

17

I2: Input .0

49

81

18

I2: Input .1

50

82

19

I2: Input .2

51

83

20

I2: Input .3

52

84

21

I2: Input .4

53

85

22

I2: Input .5

54

86

23

I2: Input .6

55

87

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

65 66

Terminal tier 3

Terminal tier 41

Ground (sensor voltage, internally jumpered, connected to M5)

PE (internally jumpered, but not connected to PE screw)

7

7-23

Page 110

Digital Modules

Table 7-4

Pin Assignment of Terminal Blocks TB2/DC, TB2-4/DC, TB4/DC and TB4M/DC for ET 200B-32DI (6ES7 131-0BL00-0XB0) and ET 200B-32DI 0.2ms (6ES7 131-0BL10-0XB0), continued Terminal tier 2

Terminal tier 1

1

7

24 V (sensor voltage, internally jumpered, connected to L5+)

88

Terminal tier 3

Terminal tier 41

Ground (sensor voltage, internally jumpered, connected to M5)

PE (internally jumpered, but not connected to PE screw)

PE (internally jumpered, but not connected to PE screw)

24

I2: Input .7

56

25

I3: Input .0

57

26

I3: Input .1

58

90

27

I3: Input .2

59

91

28

I3: Input .3

60

92

29

I3: Input .4

61

93

30

I3: Input .5

62

94

31

I3: Input .6

63

95

32

I3: Input .7

64

96

–

L5+ Voltage supply, internal logic and sensor voltage 24 V

M5 Ground connection, internal logic and sensor voltage

–

L5+ Voltage supply, internal logic and sensor voltage 24 V

M5 Ground connection, internal logic and sensor voltage

89

TB2-4/DC only; in the TB4M/DC tier 4 is available for additional ground connections (see Section 7.2.7)

Important Note on Wiring

The following notes are important as regards the wiring of the ET 200B-32DI and ET 200B-32DI 0.2 ms:

The terminals for PE on the 4-tier terminal block are not connected to the PE connection of terminal block TB2-4/DC.

L5+ and terminals 33 ... 64 are interconnected, as are M5 and terminals 65 ... 96.

The two L5+ terminals are also internally interconnected. Fuse

7-24

The 24 V sensor supply is protected by fuse F1 (2.5 A) in the terminal blocks. Nevertheless, make sure that the current does not exceed the specifications in the technical data for the electronics block.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 111

Digital Modules

Technical Data

The technical data of electronics blocks ET 200B-32DI and ET 200B-32DI 0.2 ms is listed in the tables below.

Technical specifications

Inputs

Baud rates* for 6ES7 131-0BL10-0XB0 and 6ES7 131-0BL00-0BL0

Number of inputs

Bus protocol for 6ES7 131-0BL10-0XB0 and 6ES7 131-0BL00-0XB0

9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud

PROFIBUS-DP

FREEZE capability for 6ES7 131-0BL10-0XB0 and 6ES7 131-0BL00-0XB0

Yes

Galvanic isolation to SINEC L2-DP

Yes

Power losses

Typ. 4.8 W

Weight (EB and TB)

Approx. 800 g (28 oz.)

Dimensions (EB and TB: W x H x D)

235 x 130 x 60 mm (9.17 x 5.07 x 2.34 in.)

32

Galvanic isolation to inter- No nal electronic circuits Input voltage Rated value For “0” signal For “1” signal

24 V DC – 30 V to 5 V 13 V to 30 V

Input current for “1” signal

Typ. 4 mA for 24 V Min. 2 mA

Delay of inputs for 6ES7 131-0BL00-0XB0

3 ms

Delay of inputs for 6ES7 131-0BL10-0XB0

0.2 ms

Connection of 2-wire BERO Quiescent current Connection of mechanical switches Cable length of sensors Unshielded

Possible

* v 1.5 mA Possible

Max. 100 m (328 ft.)

In operation with the IM 308-B, the maximum baud rate is 1500 kbaud.

Diagnostics functions Voltage monitoring

Green “RUN” LED

Bus monitoring SINEC L2-DP

Red “BF” LED

Status of inputs

Green LEDs

Supply voltage for inputs, sensor supply and internal logic Supply logic (L5+) Rated value Permissible range Value for t < 0.5 s

24 V DC 18.5 to 30.2 V 35 V

Current consumption from L5+ Logic Typ. 70 mA Sensors Max. 1 A I2 t (for inrush current)

< 0.05 A2s

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7-25

7

Page 112

Digital Modules

7.3.3

Electronics Block ET 200B-16DO (6ES7 132-0BH01-0XB0)

Characteristics

The ET 200B-16DO electronics block has the following characteristics:

16 outputs, non-floating Load voltage: 24 V DC Output current: 12

0.5 A, 4

2A

Suitable for solenoid valves and DC contactors. Possible terminal blocks: TB1/DC, TB1-4/DC, TB3/DC Dimensional Drawing

See Figure 7-18 for the precise dimensions.

7

Figure 7-26 Front Elevation: ET 200B-16DO (6ES7 132-0BH01-0XB0)

7-26

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 113

Digital Modules

Block Diagram

Simplified diagram of potential for the ET 200B-16DO and TB1/DC or TB3/DC:

ET 200B-16DO

24 V

PROFIBUS-DP

5V 24 V Logic

5V

8x

8x

Supply Q0: 0...7 L1+ L2+ L3+ M Q1: 0...7 Interface between electronics block and terminal block

X1 TB1/DC or TB3/DC

Station number selection

Suppr. logic STOP/RUN switch

Connection PROFIBUS-DP M

Out.

L1+ L2+ L3+ M

Ground PE

Screw for grounding (see Sec. 3.4)

Digital outputs

24 V supply

Figure 7-27 Block Diagram: ET 200B-16DO (6ES7 132-0BH01-0XB0) and TB1/DC or TB3/DC

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7-27

7

Page 114

Digital Modules

Block Diagram

Simplified diagram of the potential for the ET 200B-16DO and TB1-4/DC:

ET 200B-16DO

24 V

PROFIBUS-DP

5V 24 V Logic

5V

8x

8x

Supply Q0: 0...7 L1+ L2+ L3+ M Q1: 0...7 Interface between electronics block and terminal block

X1 TB1-4/DC

Connection PROFIBUS-DP

7

Suppr. logic STOP/RUN switch

Station number selection Out.

L1+L2+ L3+ M

M Ground PE PE

Screw for grounding (see Sec. 3.4)

Digital outputs

24 V supply

Figure 7-28 Block Diagram: ET 200B-16DO (6ES7 132-0BH01-0XB0) and TB1-4/DC

7-28

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 115

Digital Modules

Pin Assignment

Table 7-5

The table below shows the pin assignment of the terminal blocks for ET 200B-16DO. For the sake of clarity, the table also shows the terminal numbering of the terminal blocks, taking the TB1-4/DC by way of example.

Pin Assignment of Terminal Blocks TB1/DC, TB1-4/DC and TB3/DC for ET 200B-16DO (6ES7 132-0BH01-0XB0)

Terminal numbering TB1-4/DC

Terminal tier 1

Terminal tier 2 not used (internally jumpered)

Terminal tier 41

Ground (internally jumpered, connected to M1, M2, M3)

PE (internally jumpered, but not connected to PE screw)

1

Q0: Output .0*

17

2

Q0: Output .1*

18

3

Q0: Output .2

19

35

4

Q0: Output .3

20

36

5

Q0: Output .4

21

37

6

Q0: Output .5

22

38

7

Q0: Output .6

23

39

8

Q0: Output .7

24

40

9

Q1: Output .0*

25

41

10

Q1: Output .1*

26

42

11

Q1: Output .2

27

43

12

Q1: Output .3

28

44

13

Q1: Output .4

29

45

14

Q1: Output .5

30

46

15

Q1: Output .6

31

47

16

Q1: Output .7

32

48

–

L1+ Voltage supply L1+ for channel group Q0: .0 to .7

M1 Ground supply M1 for channel group Q0: .0 to .7

–

L2+ Voltage supply L2+ for channel group Q1: .0 to .7

M2 Ground supply M2 for channel group Q1: .0 to .7

*

33

Terminal tier 3

34

7

PE (internally jumpered, but not connected to PE screw)

The maximum load for these outputs is 2A, the maximum load for all other outputs is 0.5 A.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

7-29

Page 116

Digital Modules

Table 7-5

Pin Assignment of Terminal Blocks TB1/DC, TB1-4/DC and TB3/DC for ET 200B-16DO (6ES7 132-0BH01-0XB0), continued Terminal tier 2

Terminal tier 3

–

L3+ Voltage supply, internal logic

M3 Ground connection, internal logic

–

L3+ Voltage supply, internal logic

M3 Ground connection, internal logic

Terminal tier 1

1

Terminal tier 41 PE (internally jumpered but not connected to PE screw)

TB1-4/DC only

Important Note on Wiring

The following notes are important as regards the wiring of the ET 200B-16DO:

The terminals for PE on the 4-tier terminal block are not connected to the PE connection of terminal block TB1-4/DC.

L1+, L2+ and L3+ are not interconnected. M1, M2, M3 and terminals 33 ... 48 are internally interconnected. The two L3+ terminals are internally interconnected.

7

7-30

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c