Page 107
Digital Modules
Block Diagram
Simplified diagram of potential for the ET 200B-32DI or ET 200B-32DI 0.2 ms and TB2/DC or TB4/DC:
ET 200B-32DI ET 200B-32DI 0.2ms
24 V
PROFIBUS-DP
5V 24 V Logic
5V
+–
32x I0: 0...7 I1: 0...7 I2: 0...7 I3: 0...7 Interface between electronics block and terminal block
X1 TB2/DC or TB4/DC
Station number selection
Suppr. logic STOP/RUN switch
Connection PROFIBUS-DP
L5+ M5
Out. Voltage sensor
M5
L5+ M5
Ground PE
Screw for grounding (see Sec. 3.4)
Digital inputs
24 V supply
Figure 7-24 Block Diagram: ET 200B-32DI (6ES7 131-0BL00-0XB0) or ET 200B-32DI 0.2ms (6ES7 131-0BL10-0XB0) and TB2/DC or TB4/DC
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
7-21
7
Page 108
Digital Modules
Block Diagram
Simplified diagram of the potential for the ET 200B-32DI or ET 200B-32DI 0.2 ms and TB2-4/DC:
ET 200B-32DI ET 200B-32DI 0.2ms
24 V
PROFIBUS-DP
5V 24 V Logic
5V
+–
32x I0: 0...7 I1: 0...7 I2: 0...7 I3: 0...7 Interface between electronics block and terminal block
X1 TB2-4/DC
Station number selection
Suppr. logic STOP/RUN switch
Connection PROFIBUS-DP
7
M5
PE
Out. Voltage sensor Ground PE Screw for grounding (see Sec. 3.4)
L5+ M5
L5+ M5
Digital inputs
24 V supply
Figure 7-25 Block Diagram: ET 200B-32DI (6ES7 131-0BL00-0XB0) or ET 200B-32DI 0.2ms (6ES7 131-0BL10-0XB0) and TB2-4/DC
7-22
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 109
Digital Modules
Pin Assignment
Table 7-4
The table below shows the pin assignment of the terminal blocks for ET 200B-32DI and ET 200B-32DI 0.2 ms. For the sake of clarity, the table also shows the terminal numbering of the terminal blocks, taking the TB2-4/DC by way of example.
Pin Assignment of Terminal Blocks TB2/DC, TB2-4/DC, TB4/DC and TB4M/DC for ET 200B-32DI (6ES7 131-0BL00-0XB0) and ET 200B-32DI 0.2ms (6ES7 131-0BL10-0XB0)
Terminal numbering TB2-4/DC
Terminal tier 1
Terminal tier 2 24 V (sensor voltage, internally jumpered, connected to L5+)
1
I0: Input .0
33
2
I0: Input .1
34
3
I0: Input .2
35
67
4
I0: Input .3
36
68
5
I0: Input .4
37
69
6
I0: Input .5
38
70
7
I0: Input .6
39
71
8
I0: Input .7
40
72
9
I1: Input .0
41
73
10
I1: Input .1
42
74
11
I1: Input .2
43
75
12
I1: Input .3
44
76
13
I1: Input .4
45
77
14
I1: Input .5
46
78
15
I1: Input .6
47
79
16
I1: Input .7
48
80
17
I2: Input .0
49
81
18
I2: Input .1
50
82
19
I2: Input .2
51
83
20
I2: Input .3
52
84
21
I2: Input .4
53
85
22
I2: Input .5
54
86
23
I2: Input .6
55
87
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
65 66
Terminal tier 3
Terminal tier 41
Ground (sensor voltage, internally jumpered, connected to M5)
PE (internally jumpered, but not connected to PE screw)
7
7-23
Page 110
Digital Modules
Table 7-4
Pin Assignment of Terminal Blocks TB2/DC, TB2-4/DC, TB4/DC and TB4M/DC for ET 200B-32DI (6ES7 131-0BL00-0XB0) and ET 200B-32DI 0.2ms (6ES7 131-0BL10-0XB0), continued Terminal tier 2
Terminal tier 1
1
7
24 V (sensor voltage, internally jumpered, connected to L5+)
88
Terminal tier 3
Terminal tier 41
Ground (sensor voltage, internally jumpered, connected to M5)
PE (internally jumpered, but not connected to PE screw)
PE (internally jumpered, but not connected to PE screw)
24
I2: Input .7
56
25
I3: Input .0
57
26
I3: Input .1
58
90
27
I3: Input .2
59
91
28
I3: Input .3
60
92
29
I3: Input .4
61
93
30
I3: Input .5
62
94
31
I3: Input .6
63
95
32
I3: Input .7
64
96
–
L5+ Voltage supply, internal logic and sensor voltage 24 V
M5 Ground connection, internal logic and sensor voltage
–
L5+ Voltage supply, internal logic and sensor voltage 24 V
M5 Ground connection, internal logic and sensor voltage
89
TB2-4/DC only; in the TB4M/DC tier 4 is available for additional ground connections (see Section 7.2.7)
Important Note on Wiring
The following notes are important as regards the wiring of the ET 200B-32DI and ET 200B-32DI 0.2 ms:
The terminals for PE on the 4-tier terminal block are not connected to the PE connection of terminal block TB2-4/DC.
L5+ and terminals 33 ... 64 are interconnected, as are M5 and terminals 65 ... 96.
The two L5+ terminals are also internally interconnected. Fuse
7-24
The 24 V sensor supply is protected by fuse F1 (2.5 A) in the terminal blocks. Nevertheless, make sure that the current does not exceed the specifications in the technical data for the electronics block.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 111
Digital Modules
Technical Data
The technical data of electronics blocks ET 200B-32DI and ET 200B-32DI 0.2 ms is listed in the tables below.
Technical specifications
Inputs
Baud rates* for 6ES7 131-0BL10-0XB0 and 6ES7 131-0BL00-0BL0
Number of inputs
Bus protocol for 6ES7 131-0BL10-0XB0 and 6ES7 131-0BL00-0XB0
9.6/19.2/93.75/187.5/500/ 1500/3000/6000/ 12000 kbaud
PROFIBUS-DP
FREEZE capability for 6ES7 131-0BL10-0XB0 and 6ES7 131-0BL00-0XB0
Yes
Galvanic isolation to SINEC L2-DP
Yes
Power losses
Typ. 4.8 W
Weight (EB and TB)
Approx. 800 g (28 oz.)
Dimensions (EB and TB: W x H x D)
235 x 130 x 60 mm (9.17 x 5.07 x 2.34 in.)
32
Galvanic isolation to inter- No nal electronic circuits Input voltage Rated value For “0” signal For “1” signal
24 V DC – 30 V to 5 V 13 V to 30 V
Input current for “1” signal
Typ. 4 mA for 24 V Min. 2 mA
Delay of inputs for 6ES7 131-0BL00-0XB0
3 ms
Delay of inputs for 6ES7 131-0BL10-0XB0
0.2 ms
Connection of 2-wire BERO Quiescent current Connection of mechanical switches Cable length of sensors Unshielded
Possible
* v 1.5 mA Possible
Max. 100 m (328 ft.)
In operation with the IM 308-B, the maximum baud rate is 1500 kbaud.
Diagnostics functions Voltage monitoring
Green “RUN” LED
Bus monitoring SINEC L2-DP
Red “BF” LED
Status of inputs
Green LEDs
Supply voltage for inputs, sensor supply and internal logic Supply logic (L5+) Rated value Permissible range Value for t < 0.5 s
24 V DC 18.5 to 30.2 V 35 V
Current consumption from L5+ Logic Typ. 70 mA Sensors Max. 1 A I2 t (for inrush current)
< 0.05 A2s
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
7-25
7
Page 112
Digital Modules
7.3.3
Electronics Block ET 200B-16DO (6ES7 132-0BH01-0XB0)
Characteristics
The ET 200B-16DO electronics block has the following characteristics:
16 outputs, non-floating Load voltage: 24 V DC Output current: 12
0.5 A, 4
2A
Suitable for solenoid valves and DC contactors. Possible terminal blocks: TB1/DC, TB1-4/DC, TB3/DC Dimensional Drawing
See Figure 7-18 for the precise dimensions.
7
Figure 7-26 Front Elevation: ET 200B-16DO (6ES7 132-0BH01-0XB0)
7-26
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 113
Digital Modules
Block Diagram
Simplified diagram of potential for the ET 200B-16DO and TB1/DC or TB3/DC:
ET 200B-16DO
24 V
PROFIBUS-DP
5V 24 V Logic
5V
8x
8x
Supply Q0: 0...7 L1+ L2+ L3+ M Q1: 0...7 Interface between electronics block and terminal block
X1 TB1/DC or TB3/DC
Station number selection
Suppr. logic STOP/RUN switch
Connection PROFIBUS-DP M
Out.
L1+ L2+ L3+ M
Ground PE
Screw for grounding (see Sec. 3.4)
Digital outputs
24 V supply
Figure 7-27 Block Diagram: ET 200B-16DO (6ES7 132-0BH01-0XB0) and TB1/DC or TB3/DC
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
7-27
7
Page 114
Digital Modules
Block Diagram
Simplified diagram of the potential for the ET 200B-16DO and TB1-4/DC:
ET 200B-16DO
24 V
PROFIBUS-DP
5V 24 V Logic
5V
8x
8x
Supply Q0: 0...7 L1+ L2+ L3+ M Q1: 0...7 Interface between electronics block and terminal block
X1 TB1-4/DC
Connection PROFIBUS-DP
7
Suppr. logic STOP/RUN switch
Station number selection Out.
L1+L2+ L3+ M
M Ground PE PE
Screw for grounding (see Sec. 3.4)
Digital outputs
24 V supply
Figure 7-28 Block Diagram: ET 200B-16DO (6ES7 132-0BH01-0XB0) and TB1-4/DC
7-28
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 115
Digital Modules
Pin Assignment
Table 7-5
The table below shows the pin assignment of the terminal blocks for ET 200B-16DO. For the sake of clarity, the table also shows the terminal numbering of the terminal blocks, taking the TB1-4/DC by way of example.
Pin Assignment of Terminal Blocks TB1/DC, TB1-4/DC and TB3/DC for ET 200B-16DO (6ES7 132-0BH01-0XB0)
Terminal numbering TB1-4/DC
Terminal tier 1
Terminal tier 2 not used (internally jumpered)
Terminal tier 41
Ground (internally jumpered, connected to M1, M2, M3)
PE (internally jumpered, but not connected to PE screw)
1
Q0: Output .0*
17
2
Q0: Output .1*
18
3
Q0: Output .2
19
35
4
Q0: Output .3
20
36
5
Q0: Output .4
21
37
6
Q0: Output .5
22
38
7
Q0: Output .6
23
39
8
Q0: Output .7
24
40
9
Q1: Output .0*
25
41
10
Q1: Output .1*
26
42
11
Q1: Output .2
27
43
12
Q1: Output .3
28
44
13
Q1: Output .4
29
45
14
Q1: Output .5
30
46
15
Q1: Output .6
31
47
16
Q1: Output .7
32
48
–
L1+ Voltage supply L1+ for channel group Q0: .0 to .7
M1 Ground supply M1 for channel group Q0: .0 to .7
–
L2+ Voltage supply L2+ for channel group Q1: .0 to .7
M2 Ground supply M2 for channel group Q1: .0 to .7
*
33
Terminal tier 3
34
7
PE (internally jumpered, but not connected to PE screw)
The maximum load for these outputs is 2A, the maximum load for all other outputs is 0.5 A.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
7-29
Page 116
Digital Modules
Table 7-5
Pin Assignment of Terminal Blocks TB1/DC, TB1-4/DC and TB3/DC for ET 200B-16DO (6ES7 132-0BH01-0XB0), continued Terminal tier 2
Terminal tier 3
–
L3+ Voltage supply, internal logic
M3 Ground connection, internal logic
–
L3+ Voltage supply, internal logic
M3 Ground connection, internal logic
Terminal tier 1
1
Terminal tier 41 PE (internally jumpered but not connected to PE screw)
TB1-4/DC only
Important Note on Wiring
The following notes are important as regards the wiring of the ET 200B-16DO:
The terminals for PE on the 4-tier terminal block are not connected to the PE connection of terminal block TB1-4/DC.
L1+, L2+ and L3+ are not interconnected. M1, M2, M3 and terminals 33 ... 48 are internally interconnected. The two L3+ terminals are internally interconnected.
7
7-30
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c