The text of a manual · part 12 of 41
SIMATIC ET 200B Distributed I/O Station Manual: 5 Status and Error Diagnostics, pages 77 to 82
Pages 77 to 82 of 344, from SIMATIC ET 200B Distributed I/O Station Manual
The original document is the PDF (2.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens ET 200B
Page 77
Status and Error Diagnostics
Configuration Error
If a configuration telegram contains an error, only the 3-byte ID-related diagnostics (bytes 6, 7, 8) is returned and no device-related diagnostics. If the configuration telegram contains an error, the structure of ID-related diagnostics is as follows:
7 6 5 4 3 Byte 7
Byte 8
Figure 5-7
0 0 0 0
Bit No.
Message:
Possible IDs:
Slot 4 defective Slot 5 defective Slot 6 defective Slot 7 defective Slot 8 defective
8AI, 4AI, 4AO, 1AI, 1AO 1AI, 1AO 1AI, 1AO 1AI, 1AO 1AI
7 2 1 0 0 0 0 0 0
5
Bit No.
Message:
Possible IDs:
Slot 9 defective Slot 10 defective Slot 11 defective
1AI 1AI 1AI
Structure of ID-related Diagnostics for Analog ET 200B (Bytes 7, 8) in the Event of an Error in the Configuration Telegram
Note If there is an error in the configuration telegram, the configured slots of the analog ET 200B module the configurations of which are errored are shown. If the error in the configuration telegram is general (e.g. wrong length), the value FFH is returned for bytes 7 and 8.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
5-17
Page 78
Status and Error Diagnostics
5.3.8
Structure of Device-Related Diagnostics (Analog ET 200B)
Introduction
The device-related diagnostics for an analog ET 200B shows you the error reported by the ET 200B. The header indicates the length of device-related diagnostics. (see Figure 5-2, bytes 9 to 28) Note Chapter 8 contains a discussion of ”Supplementary Bits” in the section dealing with analog value representation: these bits contain additional diagnostics information.
The structure of the device-related diagnostics for configuration of analog modules with the latest type file version SIxxxxBE.200 is described below. If you configure with the type file SIxxxxAE.200, please turn to Appendix E.2.
5 Header (Byte 9)
The analog ET 200B modules contain the following information in the ”Header (device-related diagnostics)” byte:
Byte 9
7 0 0
0 Bit No.
Length of device-related diagnostics incl. byte 9 (depending on number of channels used): 0DH ... 14H: 4/8AI (13 to 20 bytes) 0DH ... 10H: 4AI, 4AO (13 to 16 bytes) 08H: process alarm for 4/8AI, 4AI Code for device-related diagnostics Figure 5-8
5-18
Structure of the Header (Device-Related Diagnostics) for Analog ET 200B (Byte 9)
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 79
Status and Error Diagnostics
Device-Related Diagnostics
Device-related diagnostics of the analog ET 200B modules comprises a maximum of 19 bytes:
01H: Code for diagnostics alarm 02H: Code for process alarm
Byte 10
Process alarm
Byte 11
Diagnostics alarm
Slot of module with pro- Slot of module cess alarm (4) with diagnostics (4) Byte 12
Bytes 13 to ... . . .
Figure 5-9
Bytes 13 to 16 Table 5-8 Byte Bit
1
00H: reserved
00H: reserved
... Byte 16 Process alarm data (see Table 5-8)
... Byte 28 Diagnostics alarm data (see Tables 5-8 to 5-10)
Structure of Device-Related Diagnostics for Analog ET 200B (Bytes 10 to 28)
Table 5-8 shows the structure and contents of bytes 13 to 16.
Bytes 13 to 16 for Diagnostics and Process Alarms Byte 10 = 01H (Diagnostics Alarm)
Byte 10 = 02H (Process Alarm)
0
Module defect
Channel 0 Upper limit value overshoot (4/8AI, 4AI)
1
Internal error
Channel 1 Upper limit value overshoot (4/8AI1)
13
2
External error
(³ Tab. 5-9)
Channel 2 Upper limit value overshoot (4/8AI1, 4AI)
3
Channel error
Channel 3 Reserved
4
Reserved
Channel 4 Reserved
5
Reserved
Channel 5 Reserved
6
Parameterization missing
Channel 6 Reserved
7
Incorrect parameters in module
Channel 7 Reserved
FFH: End-ofcycle alarm (4/8AI)
For the ET 200B-4/8AI, only the combination of single channel addressing and parameterization of channel group 0 for resistance measurement (Pt 100, Ni 100, R) entails display of ”Upper/lower limit value overshoot” for channel 1. In all other cases (i.e. module addressing and single channel addressing and parameterization of channel group 0 for other than resistance measurement (Pt 100, Ni 100, R), ”Upper/lower limit value overshoot” is displayed for channel 2.
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
5-19
5
Page 80
Status and Error Diagnostics
Table 5-8
Bytes 13 to 16 for Diagnostics and Process Alarms, continued
Byte Bit 0 to 3
Byte 10 = 01H (Diagnostics Alarm) Module class
0101
Analog module
Byte 10 = 02H (Process Alarm) Channel 0 Lower limit value overshoot (4/8AI, 4AI)
00H: Reserved
Channel 1 Lower limit value overshoot (4/8AI1) Channel 2 Lower limit value overshoot (4/8AI1, 4AI)
14
5 15
16
Channel 3 Reserved 4
Channel information available
Channel 4 Reserved
5
Reserved
Channel 5 Reserved
6
Reserved
Channel 6 Reserved
7
Reserved
Channel 7 Reserved
0
Wrong ET 200B station type
00H: Reserved
00H: Reserved
1
Reserved
2
Reserved
3
Reserved
4
Reserved
5
Reserved
6
Reserved
7
Reserved
0
Reserved
00H: Reserved
00H: Reserved
1
Reserved
2
EPROM error (4AI)
3
Reserved
4
ADC/DAC error (4AO)
5
Reserved
6
Process alarm lost (4/8AI, 4AI)
7
Reserved
Possible Values, Byte 13 Table 5-9 Value
In a diagnostics alarm the possible values of byte 13 are as follows:
Possible Values for Byte 13 in Diagnostics Alarm Bit 3 Bit 2 Bit 1 Bit 0
Meaning
00H
0
0
0
0
No error
03H (83H)
0
0
1
1
Internal error, no channel error; (incorrect parameters in the module)
0BH (8BH)
1
0
1
1
Internal error, channel error; (incorrect parameters in the module)
0DH
1
1
0
1
External error, channel error
0FH (8FH)
1
1
1
1
Summation error of all above errors; (incorrect parameters in the module)
5-20
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 81
Status and Error Diagnostics
Bytes 17 to 28 (Diagnostics Alarm) Table 5-10
Table 5-10 shows the structure and contents of bytes 17 to 28 (for diagnostics alarm only).
Bytes 17 to 28 for Diagnostics Alarm
Byte
Bit
Meaning
Remark
17
0 to 7
Channel type
71H 73H
4/8AI, 4AI 4AO
18
0 to 7
Number of diagnostics bits output per channel by a module.
08H
4/8AI, 4AI, 4AO
19
0 to 7
Number of channels of a module.
01H to 04H 01H to 08H
4AI, 4AO 4/8AI
Channel error vector:
20
21 to 281 1
0
Channel error, channel 0
4/8AI, 4AI, 4AO
1
Channel error, channel 1
4/8AI, 4AI, 4AO
2
Channel error, channel 2
4/8AI, 4AI, 4AO
3
Channel error, channel 3
4/8AI, 4AI, 4AO
4
Channel error, channel 4
4/8AI
5
Channel error, channel 5
4/8AI
6
Channel error, channel 6
4/8AI
7
Channel error, channel 7
4/8AI
-
Channel-specific errors
See Table 5-11
5
The number of bytes depends on the number of channels in the module.
Analog Channel
Table 5-11 shows the assignment of the diagnostics byte for an analog input or analog output channel. Table 5-11 Byte
Bit 0 1
Diagnostics Byte for an Analog Input/Analog Output Channel Analog Input Channel (4/8AI, 4AI)
Configuration/parameterization error Common-mode error (4/8AI only)
2 y 21
1
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
3 4
Analog Output Channel (4AO)
”0” (reserved)
”0” (reserved) ”0” (reserved)
Ground short-circuit
Wire-break/feed-current monitoring: meas. transducer/Pt 100/Ni 100/R1
5
”0” (reserved)
”0” (reserved)
6
Measuring range overshoot
”0” (reserved)
7
Measuring range overshoot
”0” (reserved)
In the case of the ET 200B-4/8AI, a ”wire break” error is superimposed on commonmode and measuring-range errors occurring at the same time (common-mode and measuring-range errors are not signaled).
5-21
Page 82
Status and Error Diagnostics
5
5-22
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c