For the Siemens ET 200B

Page 77

Status and Error Diagnostics

Configuration Error

If a configuration telegram contains an error, only the 3-byte ID-related diagnostics (bytes 6, 7, 8) is returned and no device-related diagnostics. If the configuration telegram contains an error, the structure of ID-related diagnostics is as follows:

7 6 5 4 3 Byte 7

Byte 8

Figure 5-7

0 0 0 0

Bit No.

Message:

Possible IDs:

Slot 4 defective Slot 5 defective Slot 6 defective Slot 7 defective Slot 8 defective

8AI, 4AI, 4AO, 1AI, 1AO 1AI, 1AO 1AI, 1AO 1AI, 1AO 1AI

7 2 1 0 0 0 0 0 0

5

Bit No.

Message:

Possible IDs:

Slot 9 defective Slot 10 defective Slot 11 defective

1AI 1AI 1AI

Structure of ID-related Diagnostics for Analog ET 200B (Bytes 7, 8) in the Event of an Error in the Configuration Telegram

Note If there is an error in the configuration telegram, the configured slots of the analog ET 200B module the configurations of which are errored are shown. If the error in the configuration telegram is general (e.g. wrong length), the value FFH is returned for bytes 7 and 8.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

5-17

Page 78

Status and Error Diagnostics

5.3.8

Structure of Device-Related Diagnostics (Analog ET 200B)

Introduction

The device-related diagnostics for an analog ET 200B shows you the error reported by the ET 200B. The header indicates the length of device-related diagnostics. (see Figure 5-2, bytes 9 to 28) Note Chapter 8 contains a discussion of ”Supplementary Bits” in the section dealing with analog value representation: these bits contain additional diagnostics information.

The structure of the device-related diagnostics for configuration of analog modules with the latest type file version SIxxxxBE.200 is described below. If you configure with the type file SIxxxxAE.200, please turn to Appendix E.2.

5 Header (Byte 9)

The analog ET 200B modules contain the following information in the ”Header (device-related diagnostics)” byte:

Byte 9

7 0 0

0 Bit No.

Length of device-related diagnostics incl. byte 9 (depending on number of channels used): 0DH ... 14H: 4/8AI (13 to 20 bytes) 0DH ... 10H: 4AI, 4AO (13 to 16 bytes) 08H: process alarm for 4/8AI, 4AI Code for device-related diagnostics Figure 5-8

5-18

Structure of the Header (Device-Related Diagnostics) for Analog ET 200B (Byte 9)

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 79

Status and Error Diagnostics

Device-Related Diagnostics

Device-related diagnostics of the analog ET 200B modules comprises a maximum of 19 bytes:

01H: Code for diagnostics alarm 02H: Code for process alarm

Byte 10

Process alarm

Byte 11

Diagnostics alarm

Slot of module with pro- Slot of module cess alarm (4) with diagnostics (4) Byte 12

Bytes 13 to ... . . .

Figure 5-9

Bytes 13 to 16 Table 5-8 Byte Bit

1

00H: reserved

00H: reserved

... Byte 16 Process alarm data (see Table 5-8)

... Byte 28 Diagnostics alarm data (see Tables 5-8 to 5-10)

Structure of Device-Related Diagnostics for Analog ET 200B (Bytes 10 to 28)

Table 5-8 shows the structure and contents of bytes 13 to 16.

Bytes 13 to 16 for Diagnostics and Process Alarms Byte 10 = 01H (Diagnostics Alarm)

Byte 10 = 02H (Process Alarm)

0

Module defect

Channel 0 Upper limit value overshoot (4/8AI, 4AI)

1

Internal error

Channel 1 Upper limit value overshoot (4/8AI1)

13

2

External error

(³ Tab. 5-9)

Channel 2 Upper limit value overshoot (4/8AI1, 4AI)

3

Channel error

Channel 3 Reserved

4

Reserved

Channel 4 Reserved

5

Reserved

Channel 5 Reserved

6

Parameterization missing

Channel 6 Reserved

7

Incorrect parameters in module

Channel 7 Reserved

FFH: End-ofcycle alarm (4/8AI)

For the ET 200B-4/8AI, only the combination of single channel addressing and parameterization of channel group 0 for resistance measurement (Pt 100, Ni 100, R) entails display of ”Upper/lower limit value overshoot” for channel 1. In all other cases (i.e. module addressing and single channel addressing and parameterization of channel group 0 for other than resistance measurement (Pt 100, Ni 100, R), ”Upper/lower limit value overshoot” is displayed for channel 2.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

5-19

5

Page 80

Status and Error Diagnostics

Table 5-8

Bytes 13 to 16 for Diagnostics and Process Alarms, continued

Byte Bit 0 to 3

Byte 10 = 01H (Diagnostics Alarm) Module class

0101

Analog module

Byte 10 = 02H (Process Alarm) Channel 0 Lower limit value overshoot (4/8AI, 4AI)

00H: Reserved

Channel 1 Lower limit value overshoot (4/8AI1) Channel 2 Lower limit value overshoot (4/8AI1, 4AI)

14

5 15

16

Channel 3 Reserved 4

Channel information available

Channel 4 Reserved

5

Reserved

Channel 5 Reserved

6

Reserved

Channel 6 Reserved

7

Reserved

Channel 7 Reserved

0

Wrong ET 200B station type

00H: Reserved

00H: Reserved

1

Reserved

2

Reserved

3

Reserved

4

Reserved

5

Reserved

6

Reserved

7

Reserved

0

Reserved

00H: Reserved

00H: Reserved

1

Reserved

2

EPROM error (4AI)

3

Reserved

4

ADC/DAC error (4AO)

5

Reserved

6

Process alarm lost (4/8AI, 4AI)

7

Reserved

Possible Values, Byte 13 Table 5-9 Value

In a diagnostics alarm the possible values of byte 13 are as follows:

Possible Values for Byte 13 in Diagnostics Alarm Bit 3 Bit 2 Bit 1 Bit 0

Meaning

00H

0

0

0

0

No error

03H (83H)

0

0

1

1

Internal error, no channel error; (incorrect parameters in the module)

0BH (8BH)

1

0

1

1

Internal error, channel error; (incorrect parameters in the module)

0DH

1

1

0

1

External error, channel error

0FH (8FH)

1

1

1

1

Summation error of all above errors; (incorrect parameters in the module)

5-20

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 81

Status and Error Diagnostics

Bytes 17 to 28 (Diagnostics Alarm) Table 5-10

Table 5-10 shows the structure and contents of bytes 17 to 28 (for diagnostics alarm only).

Bytes 17 to 28 for Diagnostics Alarm

Byte

Bit

Meaning

Remark

17

0 to 7

Channel type

71H 73H

4/8AI, 4AI 4AO

18

0 to 7

Number of diagnostics bits output per channel by a module.

08H

4/8AI, 4AI, 4AO

19

0 to 7

Number of channels of a module.

01H to 04H 01H to 08H

4AI, 4AO 4/8AI

Channel error vector:

20

21 to 281 1

0

Channel error, channel 0

4/8AI, 4AI, 4AO

1

Channel error, channel 1

4/8AI, 4AI, 4AO

2

Channel error, channel 2

4/8AI, 4AI, 4AO

3

Channel error, channel 3

4/8AI, 4AI, 4AO

4

Channel error, channel 4

4/8AI

5

Channel error, channel 5

4/8AI

6

Channel error, channel 6

4/8AI

7

Channel error, channel 7

4/8AI

-

Channel-specific errors

See Table 5-11

5

The number of bytes depends on the number of channels in the module.

Analog Channel

Table 5-11 shows the assignment of the diagnostics byte for an analog input or analog output channel. Table 5-11 Byte

Bit 0 1

Diagnostics Byte for an Analog Input/Analog Output Channel Analog Input Channel (4/8AI, 4AI)

Configuration/parameterization error Common-mode error (4/8AI only)

2 y 21

1

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

3 4

Analog Output Channel (4AO)

”0” (reserved)

”0” (reserved) ”0” (reserved)

Ground short-circuit

Wire-break/feed-current monitoring: meas. transducer/Pt 100/Ni 100/R1

5

”0” (reserved)

”0” (reserved)

6

Measuring range overshoot

”0” (reserved)

7

Measuring range overshoot

”0” (reserved)

In the case of the ET 200B-4/8AI, a ”wire break” error is superimposed on commonmode and measuring-range errors occurring at the same time (common-mode and measuring-range errors are not signaled).

5-21

Page 82

Status and Error Diagnostics

5

5-22

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c