SIMATIC ET 200B Distributed I/O Station Manual: 5 Status and Error Diagnostics, pages 69 to 76
Pages 69 to 76 of 344, from SIMATIC ET 200B Distributed I/O Station Manual
The original document is the PDF (2.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens ET 200B
Page 69
Status and Error Diagnostics
5.3.3
Structure of Slave Diagnostics
Introduction
A certain number of bytes is reserved per slave for slave diagnostics: the precise number of bytes reserved depends on the station type. Diagnostics of the ET 200B distributed I/O station is in compliance with EN 50170, Part 3. The basic structure of slave diagnostics is described below.
Digital ET 200B
The figure below shows the structure of slave diagnostics for digital ET 200B modules:
Byte 0 Byte 1 Byte 2
Station status 1 to 3 PROFIBUS-DP standard
Byte 3
Master station number - PROFIBUS-DP standard
Byte 4 Byte 5
High byte
Byte 6 Byte 7 Bytes 8 to 12
Header (device-related diagnostics) Device-related diagnostics
Figure 5-1
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Low byte
. . .
5
Manufacturer ID - PROFIBUS-DP standard
Free
Structure of Slave Diagnostics for Digital ET 200B
5-9
Page 70
Status and Error Diagnostics
Analog ET 200B
5
The figure below shows the structure of slave diagnostics for for analog ET 200B modules:
Byte 0 Byte 1 Byte 2
Station status 1 to 3 PROFIBUS-DP standard
Byte 3
Master station number - PROFIBUS-DP standard High byte
Byte 6 Byte 7 Byte 8
Header (ID-related diagnostics)
Byte 9 Bytes 9 to 28
Header (device-related diagnostics)
Figure 5-2
Requesting Slave Diagnostics
Low byte
ID-related diagnostics
. . .
Device-related diagnostics
Structure of Slave Diagnostics for Analog ET 200B
You can request slave diagnostics with the following function blocks: Table 5-3
5-10
Manufacturer ID PROFIBUS-DP standard
Byte 4 Byte 5
Function Blocks for Slave Diagnostics
PLC Family
Number
Name
SIMATIC S5 with IM 308-C
FB 192
FB IM308C
SIMATIC S7/M7
SFC 13
SFC “DPNRM_DG”
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 71
Status and Error Diagnostics
5.3.4
Structure of Station Status 1 to 3
Introduction
Station status 1 ... 3 provides an overview of the status of the ET 200B (see Figures 5-1 and 5-2, bytes 0 to 2).
Station Status 1 (Byte 0)
The table below shows the structure of station status 1: Table 5-4
Structure of Station Status 1 (Byte 0)
Bit
Station Status 2 (Byte 1)
Meaning
0
1: DP slave cannot be addressed by DP master.
1
1: DP slave not yet ready for data exchange.
2
1: Configuration data sent by DP master to DP slave does not match the structure of the DP slave.
3
1: Device-related diagnostics data is waiting.
4
1: Requested function is not supported by DP slave.
5
1: Implausible answer received from DP slave.
6
1: parameterization telegram is errored.
7
1: DP slave was parameterized by a DP master not the DP master which currently has access to the DP slave.
5
The table below shows the structure of station status 2: Table 5-5
Structure of Station Status 2 (Byte 1)
Bit
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Meaning
0
1: DP slave must be reparameterized.
1
1: A diagnostics message is waiting. The DP slave cannot resume operation until the error has been rectified (static diagnostics message).
2
1: Bit is always ”1” if DP slave having this station number exists.
3
1: Response monitoring is activated for this slave.
4
1: DP slave has received a ”FREEZE” control command.1
5
1: DP slave has received a ”SYNC” control command.1
6
0: Bit is always ”0”.
5-11
Page 72
Status and Error Diagnostics
Table 5-5
Bit
Meaning
7
1: DP slave is deactivated, i.e. slave has been removed from current processing.
1
Station Status 3 (Byte 2)
Structure of Station Status 2 (Byte 1), continued
Bit is not updated unless an extra diagnostics message changes.
Station status 3 is reserved and is not relevant as regards diagnostics of the DP slave. Its value is always 00H.
5
5-12
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 73
Status and Error Diagnostics
5.3.5
Structure of the Master Station Number and the Manufacturer ID
Introduction
The ”Master station number” diagnostics byte contains the station number of the DP master which parameterized the ET 200B. The ”Manufacturer ID” diagnostics byte describes the type of the ET 200B.
Master Station Number (Byte 3)
The master station number consists of one byte (see Figures 5-1 and 5-2): Table 5-6
Structure of the Master Station Number (Byte 3)
Bit
Meaning
0 to 7
Station number of the DP master which parameterized the DP slave and which has read and write access to the DP slave.
5 Manufacturer ID (Bytes 4, 5)
The manufacturer ID consists of two bytes (see Figures 5-1 and 5-2): Table 5-7
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Structure of the Manufacturer ID (Bytes 4, 5)
Byte 4
Byte 5
Manufacturer ID for
00H
01H
ET 200B-16DI
6ES7 131-0BH00-0XB0
00H
02H
ET 200B-16DO
6ES7 132-0BH01-0XB0
00H
03H
ET 200B-8RO
6ES7 132-0GF00-0XB0
00H
04H
ET 200B-32DI
6ES7 131-0BL00-0XB0
00H
05H
ET 200B-16DO/2A
6ES7 131-0BH11-0XB0
00H
0AH
ET 200B-16DI/16DO
6ES7 133-0BL00-0XB0
00H
0BH
ET 200B-8DI/8DO
6ES7 133-0BH01-0XB0
00H
0CH
ET 200B-32DI 0.2ms
6ES7 131-0BL10-0XB0
00H
0DH
ET 200B-32DO
6ES7 132-0BL01-0XB0
00H
0EH
ET 200B-24DI/8DO 0.2ms 6ES7 133-0BN11-0XB0
00H
0FH
ET 200B-24DI/8DO
6ES7 133-0BN01-0XB0
00H
10H
ET 200B-8DI/8DO HWA
6ES7 133-0BH10-0XB0
00H
19H
ET 200B-16DI-AC
6ES7 131-0HF00-0XB0
00H
1AH
ET 200B-16DO-AC
6ES7 132-0HF00-0XB0
00H
1CH
ET 200B-16RO-AC
6ES7 132-0HH00-0XB0
00H
1DH
ET 200B-8DI/8RO-AC
6ES7 133-0HH00-0XB0
80H
18H
ET 200B-4AO
6ES7 135-0HF01-0XB0
80H
19H
ET 200B-4AI
6ES7 134-0HF01-0XB0
80H
1AH
ET 200B-4/8AI
6ES7 134-0KH01-0XB0
5-13
Page 74
Status and Error Diagnostics
5.3.6
Structure of Device-Related Diagnostics (Digital ET 200B)
Introduction
The device-related diagnostics for digital ET 200B modules indicate whether inputs or outputs are defective. The header indicates the length of the devicerelated diagnostics. (see Figure 5-1, bytes 6 and 7) Note Device-related diagnostics requires an ET 200B station with diagnostics capability. ET 200B stations which do not have diagnostics capability have the value ”07H” in the header and the remaining bytes are reserved.
5 Header (Byte 6)
Digital ET 200B modules have the value 07H in the ”Header (device-related diagnostics)” byte.
Byte 6
7 0 Bit No. 0 0 0 0 0 1 1 1
Length of device-related diagnostics incl. byte 6 (= 7 bytes) Code for device-related diagnostics Figure 5-3
Device-Related Diagnostics (Byte 7)
Structure of the Header (Device-Related Diagnostics) for Digital ET 200B (Byte 6)
The device-related diagnostics of digital ET 200B modules with diagnostics capability consists of one byte (see Figure 5-1):
7 6 5 4 3 2 1 0
Bit No.
Byte 7 CG = Channel group CG 0: Overload: output short-circuit to M CG 0: Fuse defective: no load voltage CG 1: Overload: output short-circuit to M CG 1: Fuse defective: no load voltage CG 2: Overload: output short-circuit to M CG 2: Fuse defective: no load voltage CG 3: Overload: output short-circuit to M CG 3: Fuse defective: no load voltage Figure 5-4
5-14
Structure of Device-Related Diagnostics for Digital ET 200B (Byte 7)
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 75
Status and Error Diagnostics
Channel Group
Note the following as regards evaluation of device-related diagnostics: Note The channel group of an ET 200B digital module always takes up one byte in the S5 address space of the CPU (corresponding to 8 inputs or 8 outputs), irrespective of the galvanic isolation of the module (grouping). Example: ET 200B-16DO/2A (galvanic isolation in groups of 4) Channel group 0 corresponds to Q0: outputs .0 ... .7. Potential group 0 corresponds to Q0: outputs .0 ... .3.
5
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
5-15
Page 76
Status and Error Diagnostics
5.3.7
Structure of ID-related Diagnostics (Analog ET 200B)
Introduction
ID-related diagnostics shows which module in which slot is defective. The header indicate the length of ID-related diagnostics. (see Figure 5-2, bytes 6 to 8)
Header (Byte 6)
Analog ET 200B modules have the value 43H in the ”Header (ID-related diagnostics)” byte.
Byte 6
5
7 0 Bit No. 0 1 0 0 0 0 1 1
Length of ID-related diagnostics incl. byte 6 (= 3 bytes) Code for ID-related diagnostics Figure 5-5
ID-related Diagnostics (Bytes 7, 8)
Structure of the Header (ID-related Diagnostics) for Analog ET 200B (Byte 6)
The ID-related diagnostics of analog ET 200B modules consists of two bytes (see Figure 5-2):
Byte 7
3 7 0 0 0 0 0 1 0 0 0
Bit No.
Module in slot 4 defective (08H)
Byte 8 Figure 5-6
7 0 0 0 0 0 0 0 0 0
Bit No.
Structure of ID-related Diagnostics for Analog ET 200B (Bytes 7, 8)
Note Irrespective of the configuration of the analog ET 200B module (slots 4 to 11), slot 4 is always flagged as defective in a diagnostics message!
5-16