The text of a manual · part 36 of 41
SIMATIC ET 200B Distributed I/O Station Manual: C Parameterization Telegram
Pages 287 to 300 of 344, from SIMATIC ET 200B Distributed I/O Station Manual
The original document is the PDF (2.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens ET 200B
Page 287
C
Parameterization Telegram
Applicability
If you use configuration software such as COM ET 200 or STEP 7, you can ignore this chapter.
In this Chapter
If you parameterize ET 200B modules via a parameterization telegram for example with CP 5431 as DP master, you can consult this chapter for details of how to structure the parameterization telegram for the various types of ET 200B module. Section
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Describes
Page
C.1
Structure of the parameterization telegram
C-2
C.2
Standard part of the parameterization telegram
C-3
C.3
Parameters for status
C-4
C.4
Parameters for analog input modules
C-5
C.5
Parameters for analog output module
C-10
C-1
Page 288
Parameterization Telegram
C.1
Structure of the Parameterization Telegram
Definition: Parameterization Telegram
All the parameterizable values of the ET 200B are stored in the parameterization telegram.
Structure for Digital Modules
No settings can be made for digital ET 200B modules via the parameterization telegram. 5 bytes must contain ”00H” by default. The structure of the parameterization telegrams for digital ET 200B modules is as follows:
Standard part (7 bytes)
See Section C.2
00H 00H 00H 00H 00H
5 bytes with 00H as default
Figure C-1 Structure of the Parameterization Telegram for Digital ET 200B modules
Structure for Analog Modules
In the case of analog ET 200B modules, you can use the parameterization telegram to define diagnostics response and set the defaults for analog value measurement or analog value output, as applicable. Structure of the parameterization telegram for analog ET 200B modules is as follows:
Standard part (7 bytes)
See Section C.2
Parameters for status (3 bytes)
See Section C.3
Parameters for analog modules (26 bytes)
See Sections C.4 and C.5
Figure C-2 Structure of the Parameterization Telegram for Analog ET 200B Modules
C
C-2
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 289
Parameterization Telegram
C.2
Standard Part of the Parameterization Telegram
Standard Part
The first 7 bytes of the parameterization telegram are standardized to EN 50170, Part 3, and their contents could be as follows:
Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6
08H 01H 06H 0BH 80H 1DH 00H
Station status Watchdog factor 1 Watchdog factor 2 Response delay TRDY Manufacturer ID, high byte; Manufacturer ID, low byte Group ID
Figure C-3 Standard Part of the Parameterization Telegram
C
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
C-3
Page 290
Parameterization Telegram
C.3
Parameters for Status
Parameters for Status
The next 3 bytes contain the status bytes. The meanings of the parameters are described in Figure C-4. The defaults for these three bytes are:
00H 60H 0DH: for 4/8AI and 4AI 00H 20H 0DH: for 4AO
Byte 7
7 6 5 4 3 2 1 0 Bit No. 0 0 0 Startbit monitoring ON Stopbit monitoring ON Watchdog base 0: 10 ms 1: 1 ms Fail-safe mode 0: Other DP master 1: DP master in SIMATIC S7/M7 Bit No.
6 5 Byte 8 0
0 0 0 0 0 Diagnostics alarm enable Process alarm enable
Byte 9 0 0
5 4 3 2 0 Bit No. 1 0 0: Operation with S7/M7-DP master 1: Operation with IM 308-C 0: Analog value representation in SIMATIC S5 format 1: Analog value representation in SIMATIC S7/M7 format 1: Bit is always ”1”
C
00: Complement of twos (4/8AI, 4AI) 01: Amount with sign (4/8AI, 4AI) 10: Binary (4AI) 11: Invalid entry Figure C-4 Parameters for Status
C-4
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 291
Parameterization Telegram
C.4
Parameters for Analog Input Modules
Parameters for 4/8AI and 4AI
The next bytes (bytes 10 to 35) contain the following parameters for ET 200B-4/8AI and ET 200B-4AI:
07H 5FH 04H 00H 02H
Byte 10 Byte 11 Byte 12 Byte 13 Byte 14 Byte 15 Byte 16
Diagnostics enable Wire break monitor enable 13H 5FH 04H 01H 0EH
Byte 17 Byte 18 Byte 19 Byte 20 Byte 21 Bytes 22 to 35
Block length S7 constant Slot Data record number Data record length
. . .
Block length S7 constant Slot Data record number Data record length Parameters for analog value measurement
For bytes 15, 16
See Figure C-6
For bytes 22 to 35
See Figure C-7
Figure C-5 Parameters for Analog Input Modules 4/8AI, 4AI
Channel (Group)
The parameters listed on the following pages refer to channel groups for ET 200B-4/8AI and to channels for ET 200B-4AI. Table C-1 shows the assignment of terminals to channels and channel groups. Table C-1
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Assignment of Terminals to Channel (Groups)
Channel (Group) n
4/8AI
Channel (group) 0
Channel group 0 (terminals 0.1/0.2, 0.3/0.4)
Channel 0 (terminals 0.1/0.2)
Channel (group) 1
Channel group 1 (terminals 1.1/1.2, 1.3/1.4)
Channel 1 (terminals 1.1/1.2)
Channel (group) 2
Channel group 2 (terminals 2.1/2.2, 2.3/2.4)
Channel 2 (terminals 2.1/2.2)
Channel (group) 3
Channel group 3 (terminals 3.1/3.2, 3.3/3.4)
Channel 3 (terminals 3.1/3.2)
4AI
C
C-5
Page 292
Parameterization Telegram
Bytes 15, 16
Figure C-6 shows the contents of bytes 15 and 16. You activate a parameter by setting the corresponding bit to”1”.
Byte 15
3 2 1 0 Bit No. 7 0 0 0 0 Diagnostics enable, channel (group) 0 Diagnostics enable, channel (group) 1 Diagnostics enable, channel (group) 2 Diagnostics enable, channel (group) 3
Byte 16
3 2 1 0 7 0 0 0 0 Diagnostics enable, wire break, channel (group) 0 Diagnostics enable, wire break, channel (group) 1 Diagnostics enable, wire break, channel (group) 2 Diagnostics enable, wire break, channel (group) 3
Figure C-6 Bytes 15 and 16 for Analog Input Modules 4/8AI, 4AI
C
C-6
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 293
Parameterization Telegram
Bytes 22 to 35
Figure C-7 shows the structure of bytes 22 to 35. You activate a parameter by setting the corresponding bit to”1”. Note Representation of the limit values corresponds to analog value representation. Always bear the limit ranges in mind when setting the limit values.
2
7 6 Byte 22
0 0 0
0 0 0
End-of-cycle alarm 4/8AI Diagnostics alarm enable Limit-value alarm enable 7 6 5 4 3 2 1 0 Byte 23
Byte 24 Byte 25 Byte 26 Byte 27
Integration time, 4/8AI only; 4AI: byte 23 = 00H Channel group 0 Channel group 1 See Table C-2 Channel group 2 Channel group 3 7 4 3 0 Measurement channel (group) 0 Measurement channel (group) 1 Measurement channel (group) 2 Measurement channel (group) 3
Measurement: range Measurement: type Byte 28 Byte 29 Byte 30 Byte 31 Byte 32 Byte 33 Byte 34 Byte 35 *
High byte Low byte High byte Low byte High byte Low byte High byte Low byte
See Table C-3 Upper limit value, channel 0 Lower limit value, channel 0 Upper limit value, channel 2 (channel 1*) Lower limit value, channel 2 (channel 1*)
For the ET 200B-4/8AI, only the combination of single channel addressing and parameterization of channel group 0 for resistance measurement (Pt 100, Ni 100, R) entails display of ”Upper/lower limit value overshoot” for channel 1. In all other cases (i.e. module addressing and single channel addressing and parameterization of channel group 0 for other than resistance measurement (Pt 100, Ni 100, R), ”Upper/lower limit value overshoot” is displayed for channel 2.
Figure C-7 Bytes 22 and 35 for Analog Input Modules 4/8AI, 4AI
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
C-7
C
Page 294
Parameterization Telegram
Integration Time
Table C-2 contains the codings for the various integration times that you can set per channel group in byte 23 for the 4/8AI (see Figure C-7). Table C-2
Type of Measurement and Measuring Ranges
Codings for the Integration Times of the 4/8AI
Integration Time
Coding
2.5 ms
2#00
16.7 ms
2#01
20 ms
2#10
100 ms
2#11
Table C-3 lists all measuring ranges of the analog input modules. The table shows the codings for the type of measurement plus the codings for the corresponding measuring ranges. You must enter the codings for the desired measuring range in bytes 24 to 27 (see Figure C-7). Table C-3
Codings for the Measuring Ranges of the Analog Input Modules
Measurement: Type
Coding (Bits 0 to 3)
Deactivated
2#0000
Deactivated
Voltage
2#0001
80 mV 250 mV 500 mV
2.5 V
1.25 V 10 V
(4/8AI) (4/8AI) (4/8AI) (4/8AI) (4AI) (4AI) (4AI) (4AI)
2#0001 2#0010 2#0011 2#0100 2#0101 2#0110 2#0100 2#1001
Current
2#0010
0 ... 20 mA 4 ... 20 mA 20 mA
(4AI) (4AI) (4AI)
2#0010 2#0011 2#0100
Resistance
2#0100
48 W 150 W 300 W 600 W
(4/8AI) (4/8AI) (4/8AI) (4/8AI)
2#0001 2#0010 2#0100 2#0110
Pt 100 standard range Ni 100 standard range
(4/8AI) 2#0010 (4/8AI) 2#0011
C Thermal resis2#1000 tance + linearization
C-8
Measuring Range1
Coding (Bits 4 to 7)
2#0000
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 295
Parameterization Telegram
Table C-3
Codings for the Measuring Ranges of the Analog Input Modules, continued
Measurement: Type Thermal elements with linearization
1
Coding (Bits 4 to 7) 2#1110
Measuring Range1 Type N [NiCrSi – NiSi] (4/8AI) Type E [NiCr – CuNi] (4/8AI) Type J [Fe – CuNi IEC] (4/8AI) Type L [Fe – CuNi DIN] (4/8AI) Type T [Cu – CuNi IEC] (4/8AI) Type K [NiCr – Ni] (4/8AI) Type U [Cu – CuNi DIN] (4/8AI)
Coding (Bits 0 to 3) 2#0001 2#0010 2#0101 2#0110 2#0111 2#1000 2#1001
The measuring ranges apply only to the modules in parentheses.
C
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
C-9
Page 296
Parameterization Telegram
C.5
Parameters for Analog Output Module
Parameters for 4AO
The next bytes (bytes 10 to 35) contain the following parameters for ET 200B-4AO:
07H 5FH 04H 00H 02H
Byte 10 Byte 11 Byte 12 Byte 13 Byte 14 Byte 15 Byte 16
Diagnostics enable Reserved 13H 5FH 04H 01H 0EH
Byte 17 Byte 18 Byte 19 Byte 20 Byte 21 Byte 22 to 35
Block length S7 constant Slot Data record number Data record length
. . .
Block length S7 constant Slot Data record number Data record length Parameters for analog value output
For bytes 15, 16
See Figure C-9
For bytes 22 to 35
See Figure C-10
Figure C-8 Parameters for Analog Output Module 4AO
Channel
In the tables on the next pages, the parameters for ET 200B-4AO apply to channels. Table C-4 shows the assignment of terminals to channels Table C-4
Assignment of Terminals to Channels Channel n
C
C-10
Terminals on 4AO
Channel 0
Terminals 0.1/0.2
Channel 1
Terminals 1.1/1.2
Channel 2
Terminals 2.1/2.2
Channel 3
Terminals 3.1/3.2
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 297
Parameterization Telegram
Bytes 15, 16
Figure C-9 shows the contents of bytes 15 and 16. You activate a parameter by setting the corresponding bit to”1”.
Byte 15
7 0 0 0 0
0 Bit No.
Diagnostics enable, channel 0 Diagnostics enable, channel 1 Diagnostics enable, channel 2 Diagnostics enable, channel 3
Byte 16
7 0 0 0 0 0 0 0 0 0
Not relevant
Figure C-9 Bytes 15 and 16 for Analog Output Module 4AO
C
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
C-11
Page 298
Parameterization Telegram
Bytes 22 to 35
Figure C-10 shows the structure of bytes 22 to 35. You activate a parameter by setting the corresponding bit to”1”.
Byte 22
7 6 0 0 0 0 0 0 0 0 Diagnostics alarm enable
Byte 23
7 3 2 1 0 0 0 0 0
Dummy value; keep last value
Channel 0 Channel 1 Channel 2 Channel 3 7 Byte 24 Byte 25 Byte 26 Byte 27
4 3
0 Output, channel 0 Output, channel 1 Output, channel 2 Output, channel 3
Output: range Output: type Byte 28 Byte 29 Byte 30 Byte 31 Byte 32 Byte 33 Byte 34 Byte 35
0 = Dummy value 1 = Keep last value
High byte Low byte High byte Low byte High byte Low byte High byte Low byte
See Table C-5 Dummy value channel 0 Dummy value channel 1 Dummy value channel 2 Dummy value channel 3
Figure C-10 Bytes 22 to 35 for Analog Output Module 4AO
Note
C
Representation of the dummy values corresponds to analog value representation. Bear the applicable range limits in mind when setting the dummy values.
C-12
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 299
Parameterization Telegram
Type of Output and Output Ranges
Table C-5 lists all output ranges of the analog output module. The table shows the codings for the type of output plus the codings for the corresponding output ranges. You must enter the codings for the desired output range in bytes 24 to 27 (see Figure C-10). Table C-5
Codings for Output Ranges of the Analog Output Module
Output: Type
Coding (Bits 4 to 7)
Output Range
Coding (Bits 0 to 3)
Deactivated
2#0000
Deactivated
2#0000
Voltage
2#0001
0 to 10 V 10 V
2#1000 2#1001
Current
2#0010
0 to 20 mA 4 to 20 mA 20 mA
2#0010 2#0011 2#0100
C
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
C-13
Page 300
Parameterization Telegram
C
C-14
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c