For the Siemens ET 200B

Page 283

Configuration Telegram

B

Applicability

If you use configuration software such as COM ET 200 or STEP 7, you can ignore this chapter.

In this Chapter

If you address ET 200B modules via a configuration telegram for example with CP 5431 as DP master, you can consult this chapter for details of how to structure the configuration telegram for the various types of ET 200B module.

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

B-1

Page 284

Configuration Telegram

Structure for Digital Modules

Table B-1

The configuration telegram for digital modules consists of 2 bytes. The structure of the configuration telegram for digital ET 200B modules is as follows:

Structure of the Configuration Telegram for Digital ET 200B Modules Byte n

Slot

See Table B-2

Slot 1 - Output area of the digital module (byte 0) Slot 2 - Input area of the digital module (byte 1)

IDs for Digital ET 200B Table B-2

IDs for Digital ET 200B Modules

Digital Module

B

Table B-2 contains all IDs (hexadecimal) for the digital ET 200B modules.

Order Number

ID

Consistency

Byte 0 Slot 0

Byte 1 Slot 1

Address Scope (Bytes) O

Address Area

I

ET 200B-16DI

6ES7 131-0BH00-0XB0

00

11

Byte

–

2 digital

ET 200B-32DI

6ES7 131-0BL00-0XB0

00

13

Byte

–

4 digital

ET 200B-32DI 0.2ms

6ES7 131-0BL10-0XB0

ET 200B-16DO

6ES7 132-0BH00-0XB0

21

00

Byte

2

– digital

ET 200B-16DO/2A

6ES7 132-0BH10-0XB0

21

00

Byte

2

– digital

ET 200B-32DO

6ES7 132-0BL00-0XB0

23

00

Byte

4

– digital

ET 200B-8DI/8DO

6ES7 133-0BH00-0XB0

20

10

Byte

1

1 digital

ET 200B-8DI/8DO HWA

6ES7 133-0BH10-0XB0

21

10

Byte

2

1 digital

ET 200B-16DI/16DO

6ES7 133-0BL00-0XB0

21

11

Byte

2

2 digital

ET 200B-24DI/8DO

6ES7 133-0BN00-0XB0

20

12

Byte

1

3 digital

ET 200B-24DI/8DO 0.2ms

6ES7 133-0BN10-0XB0

ET 200B-8RO

6ES7 132-0GF00-0XB0

20

00

Byte

1

– digital

ET 200B-16DI-AC

6ES7 131-0HF00-0XB0

00

11

Byte

–

2 digital

ET 200B-16DO-AC

6ES7 132-0HF00-0XB0

21

00

Byte

2

– digital

ET 200B-16RO-AC

6ES7 132-0HH00-0XB0

21

00

Byte

2

– digital

ET 200B-8DI/8RO-AC

6ES7 133-0HH00-0XB0

20

10

Byte

1

1 digital

B-2

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 285

Configuration Telegram

Structure for Analog Modules

The length of the configuration telegram for analog modules depends on the type of configuration. The structure of the configuration telegrams for analog ET 200B modules is as follows:

Table B-3

Structure of the Configuration Telegram for Analog ET 200B Modules Slot

Byte n n+1 n+2 n+3 n+4

Slot 1 (virtual only) (n = 0)

04

00

00

AD

C4

Slot 2 (virtual only) (n = 5)

04

00

00

9B

40

Slot 3 (virtual only) (n = 10)

04

00

00

8F

C0

Slots 4 to 11 – input and output areas of the analog module (n = 15, n = 20, ... n = 50)

IDs for Analog ET 200B

See Table B-4

Table B-4 contains all IDs (hexadecimal) for the analog ET 200B modules Table B-4

IDs for Analog ET 200B Modules Byte1

Analog Module (Order No.: 6ES7 ...)

Slot

ET 200B-4/8AI

Configuration for entire module (8AI):

n

4

43 n+1

47

Configuration by channels (1

ET 200B-4AI

00

15

C5

AI to 8

AI):

40

00

15

C2

5 to 11

43

40

00

95

C2

00

15

C4

AI to 4

AI):

Configuration for entire module (4AI): 43

43

4

43

40

00

15

C2

5 to 7

43

40

00

95

C2

00

25

D0

AO to 4

AO):

Configuration for entire module (4AO): 4

83

43

Configuration by channels (1

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c n+4

43

Configuration by channels (1

1 n+3

4

4

ET 200B-4AO n+2

4

83

40

00

25

D0

5 to 7

83

40

00

A5

D0 n = 15: slot 4 ... n = 50: slot 11

B-3

B

Page 286

Configuration Telegram

Example of a Configuration Telegram

You want to configure an ET 200B-4AO with two output channels (channels 0 and 1). The configuration telegram consists of 25 bytes, as follows:

04 00 00 AD C4 04 00 00 9B 40 04 00 00 8F C0 83 40 00 25 D0 83 40 00 A5 D0 virtual slot 1 virtual slot 2 virtual slot 3

4AO. channel 0 slot 4

4AO. channel 1 slot 5

B

B-4

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c