SIMATIC ET 200B Distributed I/O Station Manual: E Analog Modules and Old Type Files
Pages 315 to 324 of 344, from SIMATIC ET 200B Distributed I/O Station Manual
The original document is the PDF (2.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens ET 200B
Page 315
Analog Modules and Old Type Files
Introduction
E
You do not need the information in this chapter unless you want to replace old analog modules that you configured with the type file SIxxxxAE.200 under COM ET 200 Windows with the new analog modules (order numbers: see Appendix F) described in this manual. If you use the type file SIxxxxBE.200 for configuring under COM ET 200 Windows, you can ignore this chapter (see also Table 4-1).
Compatibility
You can easily replace old analog modules with the new analog modules without having to reconfigure and parameterize the modules. You can also configure the new analog modules with the type file SIxxxxAE.200 under COM ET 200 Windows. When configured with SIxxxxAE.200, the new modules behave like the old analog modules they replace with regard to configuration and diagnostics.
Type Files
The names of the type files needed for COM ET 200 Windows are listed in Appendix A.1.
In this Chapter
The two type-file versions SIxxxxAE.200 and SIxxxxBE.200 evince differences with regard to configuration, parameterization and diagnostics information. In case you do not have access to the previous edition of this manual, the points in which the newer version of the type file differs from the SIxxxxAE.200 are described below. In Section
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c you will find on Page
E.1
Status and error indication by LEDs
E-2
E.2
Structure of device-related diagnostics (analog ET 200B)
E-3
E.3
Configuration options
E-7
E.4
Parameters for the analog modules
E-8
E-1
Page 316
Analog Modules and Old Type Files
E.1
Status and Error Indication by LEDs
Introduction
The table below explains the error indications for analog ET 200B modules for configuration with the type file SIxxxxAE.200.
Error Indication, Analog ET 200B
The table below explains the meanings of the signals provided by the LEDs on analog ET 200B modules.
Table E-1 LED RUN Off
LEDs on Analog ET 200B Modules and their Meanings LED BF Off
LED DIA Off
Meaning
Remedy
Voltage not applied to module.
Check the power supply. Check that the electronics block is correctly mounted on the terminal block.
Lit (green)
Off
Off
Module is on the PROFIBUS- DP and is exchanging data.
Lit (green)
Lit (red) or off
Lit (red)
An error has occurred on the module (e.g. wire break, measuring range overshot)
Read the diagnostics buffer to identify the error, see Sections 5.3 and E.2
If there is no diagnostics information in the buffer, check parameterization to ascertain whether the diagnostics alarm and corresponding channel diagnostics have been enabled. Lit (green)
Flashing (red)
Off
Either
Module has not received a parameterizationtelegram, or telegram is incorrect.
Check the configuration in the DP master (station number, station type).
Check the configuration.
or
Incorrect bus protocol or
Module has received incorrect configuration data.
E
Lit (green)
Flashing (red)
Lit (red)
Module has received incorrect Check parameterization and parameterization or configura- configuration tion data.
Lit (green)
Flashes once (red)
Off
Module is powering up.
-
Lit (green)
Lit (red)
No significance
Baud rate matching in progress.
Check the PROFIBUS-DP connection.
Check the DP master.
E-2
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 317
Analog Modules and Old Type Files
E.2
Structure of Device-Related Diagnostics (Analog ET 200B)
Introduction
The structure of device-related diagnostics for configuring the analog modules with the type file SIxxxxAE.200 is described below. In essence, this section is comparable with Section 5.3.8 of this manual. All other information on slave diagnostics with the IM 308-C applies as described in Section 5 above. No ID-related diagnostics are displayed for configuration with SIxxxxAE.200.
Diagnostics Alarm, Process Alarm
Analog modules configured with SIxxxxAE.200 do not support alarms (diagnostics alarm, process alarm).
Device-Related Diagnostics
The device-related diagnostics for an analog ET 200B shows you the error reported by the ET 200B. The header indicates the length of device-related diagnostics. (see Figure 5-2) Note Chapter 8 contains a discussion of ”Supplementary Bits” in the section dealing with analog value representation: these bits contain additional diagnostics information.
Header (Byte 6)
The analog ET 200B modules contain the following information in the ”Header (device-related diagnostics)” byte.
Byte 6
7 0 0
0 Bit No.
Length of device-related diagnostics incl. byte 6: 13H (19 Byte): 4/8AI 0FH (15 bytes): 4AI, 4AO Code for device-related diagnostics Figure E-1
Structure of the Header (Device-Related Diagnostics) for Analog ET 200B
E
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
E-3
Page 318
Analog Modules and Old Type Files
Device-Related Diagnostics
Device-related diagnostics of the analog ET 200B modules comprises a maximum of 18 bytes:
Byte 7 Byte 8 Bytes 9 to 24
Figure E-2
Bytes 9 to 12 Table E-2 Byte
9 (³ Tab. E-3)
10
00H: Reserved 00H: Reserved . . .
Diagnostics data (see Tables E-2 to E-5)
Structure of Device-Related Diagnostics for Analog ET 200B (Bytes 7 to 24)
Table E-2 shows the structure and contents of bytes 9 to 12.
Diagnostics Data, Bytes 9 to 12 Bit
Meaning
Byte
Bit
Meaning
0
Diagnostics message waiting
0
Wrong ET 200B station type
1
Internal error
1
Reserved
2
External error, e.g. wire break
2
Reserved
3
Channel error
3
Reserved
4
Reserved
11
4
Reserved
5
Reserved
5
Reserved
6
Reserved
6
Reserved
7
Incorrect parameters in module
7
Reserved
0 to 3
Module class
0
Reserved
1
Reserved
2
EPROM error (4AI)
3
Reserved
4
ADC/DAC error (4AO)
0101 Analog module
12
4
Channel information waiting
5
Reserved
5
Reserved
6
Reserved
6
Reserved
7
Reserved
7
Reserved
E
E-4
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 319
Analog Modules and Old Type Files
Possible Values, Byte 9
The possible values for byte 9 are as follows:
Table E-3
Possible Values for Byte 9
Value
Bit 3 Bit 2 Bit 1 Bit 0
Meaning
00H
0
0
0
0
No error
03H (83H)
0
0
1
1
Internal error, no channel error; (incorrect parameters in the module)
0BH (8BH)
1
0
1
1
Internal error, channel error; (incorrect parameters in the module)
0DH
1
1
0
1
External error, channel error
1
1
1
1
Summation error of all the above errors; (incorrect parameters in the module)
0FH (8FH)
Bytes 13 to 16 Table E-4
Table E-4 shows the structure and contents of bytes 13 to 16.
Bytes 13 to 16 for Diagnostics Alarm
Byte
Bit
Meaning
Remark
13
0 to 7
Channel type
71H 73H
4/8AI, 4AI 4AO
14
0 to 7
Number of diagnostics bits output per channel by a module.
08H
4/8AI, 4AI, 4AO
15
0 to 7
Number of channels of a module.
04H 08H
4AI, 4AO 4/8AI
Channel error vector:
16
17 to 241 1
0
Channel error, channel 0
4/8AI, 4AI, 4AO
1
Channel error, channel 1
4/8AI, 4AI, 4AO
2
Channel error, channel 2
4/8AI, 4AI, 4AO
3
Channel error, channel 3
4/8AI, 4AI, 4AO
4
Channel error, channel 4
4/8AI
5
Channel error, channel 5
4/8AI
6
Channel error, channel 6
4/8AI
7
Channel error, channel 7
4/8AI
-
Channel-specific errors see Table E-5
The number of bytes depends on the number of channels in the module.
E
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
E-5
Page 320
Analog Modules and Old Type Files
Analog Channel
Table E-5 shows the assignment of the diagnostics byte for an analog input or analog output channel. Table E-5 Byte
Bit 0 1
Diagnostics Byte for an Analog Input/Analog Output Channel Analog Input Channel (4/8AI, 4AI)
Configuration/parameterization error Common-mode error (4/8AI only)
2 as of 17
1
3 4
Analog Output Channel (4AO)
”0” (Reserved)
”0” (Reserved) ”0” (Reserved)
Ground short-circuit
Wire-break/feed-current monitoring: measuring transducer/Pt 1001
5
”0” (Reserved)
”0” (Reserved)
6
Measuring range undershoot
”0” (Reserved)
7
Measuring range overshoot
”0” (Reserved)
In the case of the ET 200B-4/8AI, a ”wire break” error is superimposed on commonmode and measuring-range errors occurring at the same time (common-mode and measuring-range errors are not signaled).
E
E-6
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 321
Analog Modules and Old Type Files
E.3
Configuration Options
Type File
The information in this section applies to the type file SIxxxxAE.200.
IDs
Table E-6 shows the possible IDs for configuring analog modules with COM ET 200 Windows. Single channel addressing is not possible with the type file SIxxxxAE.200.
Table E-6
Possible IDs for Configuring Input and Output and Areas
Module
Order Number
Slot 0
Length
ET 200B-4/8AI
6ES7 134-0KH01-0XB0
8AI
8
Word All channels are transferred.1
ET 200B-4AI
6ES7 134-0HF01-0XB0
4AI
4
Word All channels are transferred.1
ET 200B-4AO
6ES7 135-0HF01-0XB0
4AO
4
Word All channels are transferred.1
1
Format
Meaning
The address assigned is the start address for the entire module
E
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
E-7
Page 322
Analog Modules and Old Type Files
E.4
Parameters for Analog Modules
Parameters for ET 200B-4/8AI
Table 8-9 shows all the parameters for parameterizing the ET 200B-4/8AI with COM ET 200 Windows. You can set these parameters for the ET 200B-4/8AI if you use the type file SI801AAE.200.
Table E-7
Parameters for ET 200B-4/8AI (6ES7 134-0KH01-0XB0) Parameter
Explanation
Value Range
Diagnostics enable for channel group 0 (channels 0, 1)
Diagnostics messages enabled separately for each channel group: only for thermocouples, resistance thermometers (Pt 100, Ni 100) and voltage sensors 80 mV
Disable
Wire break monitoring enabled separately for each channel group
Disable
Diagnostics enable for channel group 1 (channels 2, 3)
Enable
Diagnostics enable for channel group 2 (channels 4, 5) Diagnostics enable for channel group 3 (channels 6, 7) Wire break monitoring enable for channel group 0 (channels 0, 1)
Enable
Wire break monitoring enable for channel group 1 (channels 2, 3) Wire break monitoring enable for channel group 2 (channels 4, 5) Wire break monitoring enable for channel group 3 (channels 6, 7) Integration time for module
Enter an optimum integration time for the A/D converter to help suppress noise voltage.
16.7 ms 20 ms
Measurement type and range for channel You can set the measurement type and range separately for each channel group group 0 (channels 0, 1) Measurement type and range for channel group 1 (channels 2, 3)
0.5 V 0.25 V 80 mV
For voltage measurement:
Measurement type and range for channel For resistance thermometer with linearization: Pt 100 standard range group 2 (channels 4, 5) For thermocouple with external reference junction: Type J with linearization Measurement type and range for channel Type L with linearization group 3 (channels 6, 7) Type K with linearization
E
Representation of measured values
Sets representation of the measured values for module
SIMATIC S5 SIMATIC S7
Measured value representation
Sets data format for analog value representation, SIMATIC S5
Complement of twos Amount with sign
:
E-8
Default
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
Page 323
Analog Modules and Old Type Files
Parameters for ET 200B-4AI
Table 8-40 shows all the parameters for parameterizing the ET 200B-4AI with COM ET 200 Windows. You can set these parameters for the ET 200B-4AI if you use the type file SI8019AE.200.
Table E-8
Parameters for ET 200B-4AI (6ES7 134-0HF01-0XB0) Explanation
Value Range
Diagnostics messages enabled separately for each channel
Disable
Wire break monitoring enabled separately for each channel for measuring range 4 ... 20 mA
Disable
Measurement type and range for channel 0
You can set the measurement type and range separately for each channel
Channel not activated
Measurement type and range for channel 1
For voltage measurement:
10 V
2.5 V 1.25 V
For current measurement:
20 mA 0 ... 20 mA 4 ... 20 mA
Representation of measured values
Sets representation of the analog measured values for module
SIMATIC S5 SIMATIC S7
Measured value representation
Sets data format for analog value representation, SIMATIC S5
Complement of twos Amount with sign Binary
Parameter Diagnostics enable for channel 0 Diagnostics enable for channel 1
Enable
Diagnostics enable for channel 2 Diagnostics enable for channel 3 Wire break monitoring enable for channel 0 Wire break monitoring enable for channel 1
Enable
Wire break monitoring enable for channel 2 Wire break monitoring enable for channel 3
Measurement type and range for channel 2 Measurement type and range for channel 3
:
Default
E
ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c
E-9
Page 324
Analog Modules and Old Type Files
Parameters for ET 200B-4AO
Table 8-58 shows all the parameters for parameterizing the ET 200B-4AO with COM ET 200 Windows. You can set these parameters for the ET 200B-4AO if you use the type file SI8018AE.200.
Table E-9
Parameters for ET 200B-4AO (6ES7 135-0HF01-0XB0) Parameter
Diagnostics enable for channel 0 Diagnostics enable for channel 1
Explanation
Explanation
Diagnostics messages enabled separately for each channel
Disable Enable
Diagnostics enable for channel 2 Diagnostics enable for channel 3 Output type and range for channel 0
Type and range of output defined separately for each channel
Output type and range for channel 1
For voltage output:
10 V 0 ... 10 V
For current output:
20 mA 0 ... 20 mA 4 ... 20 mA
Sets representation of the analog values for module
SIMATIC S5 SIMATIC S7
Output type and range for channel 2 Output type and range for channel 3 Representation of output values
:
Default
E
E-10