Page 315

Analog Modules and Old Type Files

Introduction

E

You do not need the information in this chapter unless you want to replace old analog modules that you configured with the type file SIxxxxAE.200 under COM ET 200 Windows with the new analog modules (order numbers: see Appendix F) described in this manual. If you use the type file SIxxxxBE.200 for configuring under COM ET 200 Windows, you can ignore this chapter (see also Table 4-1).

Compatibility

You can easily replace old analog modules with the new analog modules without having to reconfigure and parameterize the modules. You can also configure the new analog modules with the type file SIxxxxAE.200 under COM ET 200 Windows. When configured with SIxxxxAE.200, the new modules behave like the old analog modules they replace with regard to configuration and diagnostics.

Type Files

The names of the type files needed for COM ET 200 Windows are listed in Appendix A.1.

In this Chapter

The two type-file versions SIxxxxAE.200 and SIxxxxBE.200 evince differences with regard to configuration, parameterization and diagnostics information. In case you do not have access to the previous edition of this manual, the points in which the newer version of the type file differs from the SIxxxxAE.200 are described below. In Section

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c you will find on Page

E.1

Status and error indication by LEDs

E-2

E.2

Structure of device-related diagnostics (analog ET 200B)

E-3

E.3

Configuration options

E-7

E.4

Parameters for the analog modules

E-8

E-1

Page 316

Analog Modules and Old Type Files

E.1

Status and Error Indication by LEDs

Introduction

The table below explains the error indications for analog ET 200B modules for configuration with the type file SIxxxxAE.200.

Error Indication, Analog ET 200B

The table below explains the meanings of the signals provided by the LEDs on analog ET 200B modules.

Table E-1 LED RUN Off

LEDs on Analog ET 200B Modules and their Meanings LED BF Off

LED DIA Off

Meaning

Remedy

Voltage not applied to module.

Check the power supply. Check that the electronics block is correctly mounted on the terminal block.

Lit (green)

Off

Off

Module is on the PROFIBUS- DP and is exchanging data.

Lit (green)

Lit (red) or off

Lit (red)

An error has occurred on the module (e.g. wire break, measuring range overshot)

Read the diagnostics buffer to identify the error, see Sections 5.3 and E.2

If there is no diagnostics information in the buffer, check parameterization to ascertain whether the diagnostics alarm and corresponding channel diagnostics have been enabled. Lit (green)

Flashing (red)

Off

Either

Module has not received a parameterizationtelegram, or telegram is incorrect.

Check the configuration in the DP master (station number, station type).

Check the configuration.

or

Incorrect bus protocol or

Module has received incorrect configuration data.

E

Lit (green)

Flashing (red)

Lit (red)

Module has received incorrect Check parameterization and parameterization or configura- configuration tion data.

Lit (green)

Flashes once (red)

Off

Module is powering up.

-

Lit (green)

Lit (red)

No significance

Baud rate matching in progress.

Check the PROFIBUS-DP connection.

Check the DP master.

E-2

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 317

Analog Modules and Old Type Files

E.2

Structure of Device-Related Diagnostics (Analog ET 200B)

Introduction

The structure of device-related diagnostics for configuring the analog modules with the type file SIxxxxAE.200 is described below. In essence, this section is comparable with Section 5.3.8 of this manual. All other information on slave diagnostics with the IM 308-C applies as described in Section 5 above. No ID-related diagnostics are displayed for configuration with SIxxxxAE.200.

Diagnostics Alarm, Process Alarm

Analog modules configured with SIxxxxAE.200 do not support alarms (diagnostics alarm, process alarm).

Device-Related Diagnostics

The device-related diagnostics for an analog ET 200B shows you the error reported by the ET 200B. The header indicates the length of device-related diagnostics. (see Figure 5-2) Note Chapter 8 contains a discussion of ”Supplementary Bits” in the section dealing with analog value representation: these bits contain additional diagnostics information.

Header (Byte 6)

The analog ET 200B modules contain the following information in the ”Header (device-related diagnostics)” byte.

Byte 6

7 0 0

0 Bit No.

Length of device-related diagnostics incl. byte 6: 13H (19 Byte): 4/8AI 0FH (15 bytes): 4AI, 4AO Code for device-related diagnostics Figure E-1

Structure of the Header (Device-Related Diagnostics) for Analog ET 200B

E

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

E-3

Page 318

Analog Modules and Old Type Files

Device-Related Diagnostics

Device-related diagnostics of the analog ET 200B modules comprises a maximum of 18 bytes:

Byte 7 Byte 8 Bytes 9 to 24

Figure E-2

Bytes 9 to 12 Table E-2 Byte

9 (³ Tab. E-3)

10

00H: Reserved 00H: Reserved . . .

Diagnostics data (see Tables E-2 to E-5)

Structure of Device-Related Diagnostics for Analog ET 200B (Bytes 7 to 24)

Table E-2 shows the structure and contents of bytes 9 to 12.

Diagnostics Data, Bytes 9 to 12 Bit

Meaning

Byte

Bit

Meaning

0

Diagnostics message waiting

0

Wrong ET 200B station type

1

Internal error

1

Reserved

2

External error, e.g. wire break

2

Reserved

3

Channel error

3

Reserved

4

Reserved

11

4

Reserved

5

Reserved

5

Reserved

6

Reserved

6

Reserved

7

Incorrect parameters in module

7

Reserved

0 to 3

Module class

0

Reserved

1

Reserved

2

EPROM error (4AI)

3

Reserved

4

ADC/DAC error (4AO)

0101 Analog module

12

4

Channel information waiting

5

Reserved

5

Reserved

6

Reserved

6

Reserved

7

Reserved

7

Reserved

E

E-4

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 319

Analog Modules and Old Type Files

Possible Values, Byte 9

The possible values for byte 9 are as follows:

Table E-3

Possible Values for Byte 9

Value

Bit 3 Bit 2 Bit 1 Bit 0

Meaning

00H

0

0

0

0

No error

03H (83H)

0

0

1

1

Internal error, no channel error; (incorrect parameters in the module)

0BH (8BH)

1

0

1

1

Internal error, channel error; (incorrect parameters in the module)

0DH

1

1

0

1

External error, channel error

1

1

1

1

Summation error of all the above errors; (incorrect parameters in the module)

0FH (8FH)

Bytes 13 to 16 Table E-4

Table E-4 shows the structure and contents of bytes 13 to 16.

Bytes 13 to 16 for Diagnostics Alarm

Byte

Bit

Meaning

Remark

13

0 to 7

Channel type

71H 73H

4/8AI, 4AI 4AO

14

0 to 7

Number of diagnostics bits output per channel by a module.

08H

4/8AI, 4AI, 4AO

15

0 to 7

Number of channels of a module.

04H 08H

4AI, 4AO 4/8AI

Channel error vector:

16

17 to 241 1

0

Channel error, channel 0

4/8AI, 4AI, 4AO

1

Channel error, channel 1

4/8AI, 4AI, 4AO

2

Channel error, channel 2

4/8AI, 4AI, 4AO

3

Channel error, channel 3

4/8AI, 4AI, 4AO

4

Channel error, channel 4

4/8AI

5

Channel error, channel 5

4/8AI

6

Channel error, channel 6

4/8AI

7

Channel error, channel 7

4/8AI

-

Channel-specific errors see Table E-5

The number of bytes depends on the number of channels in the module.

E

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

E-5

Page 320

Analog Modules and Old Type Files

Analog Channel

Table E-5 shows the assignment of the diagnostics byte for an analog input or analog output channel. Table E-5 Byte

Bit 0 1

Diagnostics Byte for an Analog Input/Analog Output Channel Analog Input Channel (4/8AI, 4AI)

Configuration/parameterization error Common-mode error (4/8AI only)

2 as of 17

1

3 4

Analog Output Channel (4AO)

”0” (Reserved)

”0” (Reserved) ”0” (Reserved)

Ground short-circuit

Wire-break/feed-current monitoring: measuring transducer/Pt 1001

5

”0” (Reserved)

”0” (Reserved)

6

Measuring range undershoot

”0” (Reserved)

7

Measuring range overshoot

”0” (Reserved)

In the case of the ET 200B-4/8AI, a ”wire break” error is superimposed on commonmode and measuring-range errors occurring at the same time (common-mode and measuring-range errors are not signaled).

E

E-6

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 321

Analog Modules and Old Type Files

E.3

Configuration Options

Type File

The information in this section applies to the type file SIxxxxAE.200.

IDs

Table E-6 shows the possible IDs for configuring analog modules with COM ET 200 Windows. Single channel addressing is not possible with the type file SIxxxxAE.200.

Table E-6

Possible IDs for Configuring Input and Output and Areas

Module

Order Number

Slot 0

Length

ET 200B-4/8AI

6ES7 134-0KH01-0XB0

8AI

8

Word All channels are transferred.1

ET 200B-4AI

6ES7 134-0HF01-0XB0

4AI

4

Word All channels are transferred.1

ET 200B-4AO

6ES7 135-0HF01-0XB0

4AO

4

Word All channels are transferred.1

1

Format

Meaning

The address assigned is the start address for the entire module

E

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

E-7

Page 322

Analog Modules and Old Type Files

E.4

Parameters for Analog Modules

Parameters for ET 200B-4/8AI

Table 8-9 shows all the parameters for parameterizing the ET 200B-4/8AI with COM ET 200 Windows. You can set these parameters for the ET 200B-4/8AI if you use the type file SI801AAE.200.

Table E-7

Parameters for ET 200B-4/8AI (6ES7 134-0KH01-0XB0) Parameter

Explanation

Value Range

Diagnostics enable for channel group 0 (channels 0, 1)

Diagnostics messages enabled separately for each channel group: only for thermocouples, resistance thermometers (Pt 100, Ni 100) and voltage sensors 80 mV

Disable

Wire break monitoring enabled separately for each channel group

Disable

Diagnostics enable for channel group 1 (channels 2, 3)

Enable

Diagnostics enable for channel group 2 (channels 4, 5) Diagnostics enable for channel group 3 (channels 6, 7) Wire break monitoring enable for channel group 0 (channels 0, 1)

Enable

Wire break monitoring enable for channel group 1 (channels 2, 3) Wire break monitoring enable for channel group 2 (channels 4, 5) Wire break monitoring enable for channel group 3 (channels 6, 7) Integration time for module

Enter an optimum integration time for the A/D converter to help suppress noise voltage.

16.7 ms 20 ms

Measurement type and range for channel You can set the measurement type and range separately for each channel group group 0 (channels 0, 1) Measurement type and range for channel group 1 (channels 2, 3)

0.5 V 0.25 V 80 mV

For voltage measurement:

Measurement type and range for channel For resistance thermometer with linearization: Pt 100 standard range group 2 (channels 4, 5) For thermocouple with external reference junction: Type J with linearization Measurement type and range for channel Type L with linearization group 3 (channels 6, 7) Type K with linearization

E

Representation of measured values

Sets representation of the measured values for module

SIMATIC S5 SIMATIC S7

Measured value representation

Sets data format for analog value representation, SIMATIC S5

Complement of twos Amount with sign

:

E-8

Default

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

Page 323

Analog Modules and Old Type Files

Parameters for ET 200B-4AI

Table 8-40 shows all the parameters for parameterizing the ET 200B-4AI with COM ET 200 Windows. You can set these parameters for the ET 200B-4AI if you use the type file SI8019AE.200.

Table E-8

Parameters for ET 200B-4AI (6ES7 134-0HF01-0XB0) Explanation

Value Range

Diagnostics messages enabled separately for each channel

Disable

Wire break monitoring enabled separately for each channel for measuring range 4 ... 20 mA

Disable

Measurement type and range for channel 0

You can set the measurement type and range separately for each channel

Channel not activated

Measurement type and range for channel 1

For voltage measurement:

10 V

2.5 V 1.25 V

For current measurement:

20 mA 0 ... 20 mA 4 ... 20 mA

Representation of measured values

Sets representation of the analog measured values for module

SIMATIC S5 SIMATIC S7

Measured value representation

Sets data format for analog value representation, SIMATIC S5

Complement of twos Amount with sign Binary

Parameter Diagnostics enable for channel 0 Diagnostics enable for channel 1

Enable

Diagnostics enable for channel 2 Diagnostics enable for channel 3 Wire break monitoring enable for channel 0 Wire break monitoring enable for channel 1

Enable

Wire break monitoring enable for channel 2 Wire break monitoring enable for channel 3

Measurement type and range for channel 2 Measurement type and range for channel 3

:

Default

E

ET 200B Distributed I/O Station EWA 4NEB 812 6089-02c

E-9

Page 324

Analog Modules and Old Type Files

Parameters for ET 200B-4AO

Table 8-58 shows all the parameters for parameterizing the ET 200B-4AO with COM ET 200 Windows. You can set these parameters for the ET 200B-4AO if you use the type file SI8018AE.200.

Table E-9

Parameters for ET 200B-4AO (6ES7 135-0HF01-0XB0) Parameter

Diagnostics enable for channel 0 Diagnostics enable for channel 1

Explanation

Explanation

Diagnostics messages enabled separately for each channel

Disable Enable

Diagnostics enable for channel 2 Diagnostics enable for channel 3 Output type and range for channel 0

Type and range of output defined separately for each channel

Output type and range for channel 1

For voltage output:

10 V 0 ... 10 V

For current output:

20 mA 0 ... 20 mA 4 ... 20 mA

Sets representation of the analog values for module

SIMATIC S5 SIMATIC S7

Output type and range for channel 2 Output type and range for channel 3 Representation of output values

:

Default

E

E-10