Page 1 of Control Technologies RCM2030, Siemens RCM2030 and Texas Instruments RCM2030 Manual

Manual · Control Technologies

Control Technologies RCM2030, Siemens RCM2030 and Texas Instruments RCM2030 Manual

Manual2 pagesPDF 243 KB

Both pages are below, each with its text.

Download the PDF243 KB

Covers · 3 models

The models it covers

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

Control Technology (CTI) product bulletin 062-00321-012, dated 11/30/05, for the 2030 / 2030-L / 2032 8-point relay contact modules for the Series 500 I/O base. It explains what sets the three models apart, how to key the slot and wire the outputs and coil supply, the load and inrush limits, and the specifications of each model.

What it is
Relay output module with eight isolated Form C relay outputs for the Series 500 I/O base p. 1
Intended loads
Model 2030: high current applications such as switching motor starters p. 1
Load rating
Model 2030: 500mA - 6A resistive per point; load voltage 15VAC/15VDC to 240VAC/150VDC; in-rush 64A for 2mS p. 2
Relay coil supply
Model 2030: external 24VAC/VDC ±10%, 160mA nominal p. 2
Isolation
1500 Vrms channel-to-channel and channel-to-backplane p. 2
Backplane power
1 Watt typical, 2 Watts max. from the I/O base p. 1, 2
Fuses
Model 2030: eight 8 Amp 8AGC fuses p. 2
Switching rate
Model 2030: 25/second at 100mA p. 2
Environment
Operating 0° to 60°C (32° to 140°F); storage -40° to 85°C; 5% to 95% humidity, non-condensing p. 2
Connections
Detachable connectors on the top and bottom of the module p. 1
2030L version
2030L: low current loads such as analog and TTL signals; 1 to 500mA per point; external 24VDC ±10% coil supply, 70mA p. 1, 2
2032 version
2032: 125VDC (nominal) low level current; no external supply; 1mA - 250 mA resistive @ 125VDC p. 1, 2

What this manual walks you through

  • Keying the I/O base slot for the module p. 1
  • Wiring the output connectors p. 1
  • Checking the I/O base power budget p. 1
  • Finding the maximum resistive load for a given voltage p. 2
  • Allowing for inrush current by type of load p. 2
  • Connecting the external relay coil power supply p. 2

Good to know

  • Modules made before 1-14-87 use a different keying; when replacing an older 2030/2030L, key the slot properly to avoid damaging the I/O base. p. 1
  • Exceeding the load shown in the graphs shortens contact life or damages the contacts. p. 2
  • Inrush current together with switching frequency can weld the contacts. p. 2
  • For switching voltages above 30VDC, the graph on page 2 applies. p. 2

Questions this manual answers

Does the RCM2030 relay module need an external power supply?

Yes. The 2030 and 2030L need a separate external relay coil supply (24VAC/VDC ±10% for the 2030); only the 2032 does without. p. 2

How much current can each RCM-2030 output switch?

The Model 2030 handles 500mA to 6A resistive per point, at 15VAC/15VDC up to 240VAC/150VDC. p. 2

What is the difference between the 2030, 2030L and 2032?

The 2030 is for high current loads such as motor starters, the 2030L for low current analog and TTL signals, and the 2032 for 125VDC low level loads. p. 1

What fuses does the RCM-2030 use?

Eight 8 Amp 8AGC fuses. p. 2

Which PLC I/O base does the RCM-2030 fit?

The Series 500 I/O base; the modules plug directly into it and respond to Series 500 instructions. p. 1

The file

Size and text

Pages2
PDF243 KB
TextText from the PDF itself.

Every page · 2

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Control Technologies RCM2030, Siemens RCM2030 and Texas Instruments RCM2030 Manual

The text of page 1, from the PDF itself

SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES FOR CONSUMER PRODUCTS, SO THE ABOVE LIMITATIONS OR EXCLUSIONS MAY NOT APPLY TO YOU. THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH MAY VARY FROM STATE TO STATE.

Repair Policy In the event that the Product should fail during or after the warranty period, a Return Material Authorization number (RMA) can be requested verbally or in writing from CTI main offices. Whether this equipment is in or out of warranty, a Purchase Order number provided to CTI when requesting the RMA number will aid in expediting the repair process. The RMA number that is issued and your Purchase Order number should be referenced on the returning equipment's shipping documentation. Additionally, if under warranty, proof of purchase date and serial number must accompany the returned equipment. The current repair and/or exchange rates can be obtained by contacting CTI's main office at 1-800-537-8398.

2030 / 2030-L / 2032 8-Point Relay Contact Modules

Other CTI Series 500 Modules CTI manufactures a number of I/O modules and peripherals for the TI500 series PLCs.

Keying the I/O Base Slot

TTL Output Module - The TTL-2017 is an 8 output TTL/ CMOS compatible output module capable of fully driving 10 TTL or CMOS loads per output. The TTL-2017 may be used to interface to board level computers, message displays, low level indicators, and stepper motors.

Any 2030 Series module may be inserted into any available slot in the I/O base. To prevent insertion of other types of modules, the slot selected must be keyed as shown in the diagram below. Use long nose pliers to insert keys in the I/O base slot.

2 x 4 Point Relay Contact Module - The RCM-2020 is a relay contact module with 8 outputs. The outputs are arranged in two isolated banks of 4 Form A relay contacts. Each individually fused contact has a capacity of 2 amps, sufficient to directly drive NEMA size 2 motor starters. Analog Input Module - The Model 2050 8-channel isolated analog input module translates analog input signals into an equivalent digital word. No external power supply or resistor required. The module accepts voltage and current inputs in bipolar or unipolar mode. Other features include fast 1 mSec update time, 1500VDC channel-to-channel isolation, and a digital filtering circuit. Analog Output Module - The Model 2060 8-channel isolated analog output module translates a digital word from the controller into equivalent analog outputs with 12-bit resolution. Features include fast 4mSec update time, 1500VDC channel-to-channel isolation, 0 - 10VDC or 0 20mA outputs. Voltage and current outputs are available simultaneously. 16 - Point Discrete Input Modules - The Models 2080, 2081, and 2082 16 - point discrete input modules each accept sixteen inputs to the series 500 I/O base. The Model 2080 accepts 120VAC or 130VDC inputs. The Model 2081 accepts 24V AC or DC inputs. The Model 2082 accepts 90 to 146VDC inputs. Features include isolation in groups of 4 outputs. The Model 2082 is ideal for power utility substations. 16 - Point Discrete Output Modules - The Models 2090 and 2091 16 - point discrete output modules provide sixteen AC/ DC outputs from the series 500 I/O base. The Model 2090 provides 120VAC outputs and the Model 2091 provides 24VDC outputs. Features include isolation in groups of 4 outputs with individually fused outputs. TCAM - The TCAM-5240 has been designed as a convenient panel mounted operator interface unit for use with PLC Models 520, 520C, 530, 530C, 530T, 545, 555, 560, 565, 565T. It provides the operator with the ability to monitor and adjust timers, counters, drums, and variable (V) memory values. The TCAM-5240 will also display discrete I/O states and word X/Y memory values.

Description

2000 Series I/O Product Bulletin

THE WARRANTY SET FORTH ABOVE IN THIS ARTICLE IS THE ONLY WARRANTY CTI GRANTS AND IT IS IN LIEU OF ANY OTHER IMPLIED OR EXPRESSED GUARANTY OR WARRANTY ON CTI PRODUCTS, INCLUDING WITHOUT LIMITATION, ANY WARRANTY OF MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR PURPOSE AND IS IN LIEU OF ALL OBLIGATIONS OR LIABILITY OF CTI FOR DAMAGES IN CONNECTION WITH LOSS, DELIVERY, USE OR PERFORMANCE OF CTI PRODUCTS OR INTERRUPTION OF BUSINESS, LOSS OF USE, REVENUE OR PROFIT. IN NO EVENT WILL CTI BE LIABLE FOR SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES.

The RCM-2030, 2030L, and 2032 Relay Contact Modules each provide eight isolated "Form C" relay outputs for the 500 Series I/O base. These modules plug directly into the 500 I/O base and respond to Series 500 instructions. The Model 2030 is designed for high current applications such as switching motor starters. The Model 2030L is designed for low current applications such as switching analog and TTL level signals. The Model 2032 is designed for 125VDC (nominal) low level current applications. The Model 2032 requires no external power supply, module power is taken directly from the I/O base backplane.

Installation

WARNING: Modules manufactured before 1-14-87 use a different keying configuration. If you replace an older Model 2030/2030L with a new module, make sure that the slot is properly keyed to prevent damage to the I/O base.

Wiring and Connecting the Output Connectors Outputs are available at the terminals of the detachable connectors on the top and bottom of each module. The diagram below illustrates the arrangement of connections for each output point.

I/O Base Power Requirements Each of the 2030 Series modules requires 2 watts (maximum) of power from the I/O base. Use this figure to verify that the base power supply capacity is not exceeded.

Control Technology Inc. Copyright ©2005 Control Technology Inc.

All Rights Reserved062-00321-01211/30/05

Siemens® is a registered trademark of Siemens AG

5734 Middlebrook Pike, Knoxville, TN 37921-5962 Phone: 865/584-0440 Fax: 865/584-5720 www.controltechnology.com

Page 2 of Control Technologies RCM2030, Siemens RCM2030 and Texas Instruments RCM2030 Manual

The text of page 2, from the PDF itself

Output Current Capacity

Inrush Current Capacity

The output resistive load capacity of the relay contacts used in the 2030 Series modules varies with the voltage. Use the graphs on this page to determine the maximum resistive load per point for any given voltage. Exceeding the given load will shorten the specified contact life or damage the contacts.

The type of load combined with its inrush current characteristics, together with switching frequency can cause contact welding. For loads with inrush current, measure the steady state current and inrush current to determine the proper application. Examples of typical loads, and the inrush current they create are shown in the chart below: Type of Load

Inrush Current

Resistive load Solenoid load

Steady state current 10 to 20 times steady state current

Motor load Incandescent lamp load

5 to 10 times steady state current 10 to 15 times steady state current

Mercury lamp load

Approx. 3 times steady state current

Sodium vapor lamp load Capacitive load

1 to 3 times steady state current 20 to 40 times steady state current

Transformer load 5 to 10 times steady state current

Relay Control Coil External Power Supply

Model 2030 Switching Capacity

The Models 2030 and 2030L require a separate external relay control coil power supply. These external power supply connections are shown in the diagram below. The Model 2032 does not require an external relay coil control power supply.

Specifications Common to the 3 Modules Number of Output Points: 8 Type of Contacts: Form C Backplane Loading: 1 Watt (typical), 2 Watts (max.) Operating Temperature: 0° to 60°C (32° to 140°F) Storage Temperature: -40° to 85°C (-40° to 185°F) Relative Humidity: 5% to 95% (non-condensing)

Model 2030 Specifications Isolation: 1500 Vrms channel-to-channel, 1500 Vrms channel-to-backplane Relay Coil Control Voltage (externally supplied): 24VAC/VDC ±10% Nominal Supply Current: 160mA Switching Rate: 25/second at 100mA Maximum Contact Life: 2 x 105 @ 6 amp Load Voltage: Minimum: 15VAC/15VDC Maximum: 240VAC/150VDC* Current (Resistive) Per Output Point: 500mA - 6A In-rush Current: 64A for 2mS (see chart on page 2) Fuses: Eight 8 Amp 8AGC fuses *See graph on page 2 for information on switching voltages greater than 30VDC

Model 2030-L Specifications

Power Supply Connections

Model 2030L and 2032 Switching Capacity

Isolation: 1500 Vrms channel-to-channel, 1500 Vrms channel-to-backplane Relay Coil Control Voltage (externally supplied): 24VDC ±10% Nominal Supply Current: 70mA Switching Rate: 1/second at 100mA Maximum Contact Life: 5 x 105 @ 0.5 amp Load Voltage: Minimum: 0.5VDC/15VAC Maximum: 230VAC/150VDC* Current (Resistive) Per Output Point: 1 to 500mA In-rush Current: 4A for 2mS (see chart on page 2) *See graph on page 2 for information on switching voltages greater than 30VDC

Model 2032 Specifications Isolation: 1500 Vrms channel-to-channel, 1500 Vrms channel-to-backplane Switching Rate: 1/second at 100mA Maximum Contact Life: 5 x 105 @ 15 mA Load Voltage: Minimum: 0.5VDC/15VAC Maximum: 230VAC/150VDC Current Per Output Point*: Resistive: 1mA - 250 mA @ 125VDC Inductive: 1 mA - 125 mA @ 125 VDC In-rush Current: 4A for 2mS (see chart on page 2) Backplane Loading: 1 Watt (typical), 2 Watts (Max.) *See graph on page 2 for general de-rating curves

Limited Product Warranty CTI warrants that this CTI Industrial Product shall be free from defects in material and workmanship for a period of one (1) year after purchase from CTI or from an authorized CTI Industrial Distributor. This CTI Industrial Product will be newly manufactured from new and/or serviceable used parts which are equal to new in the Product. Should this CTI Industrial Product fail to be free from defects in material and workmanship at any time during this one (1) year warranty period, CTI will repair or replace (at its option) parts or Products found to be defective and shipped prepaid by the customer to a designated CTI service location along with proof of purchase date and associated serial number. Repair parts and replacement Product furnished under this warranty will be on an exchange basis and will be either reconditioned or new. All exchanged parts or Products will become the property of CTI. Should any Product or part returned to CTI hereunder be found by CTI to be without defect, CTI will return such Product or part to the customer. This warranty does not include repair of damage to a part or the Product resulting from: failure to provide a suitable environment as specified in applicable Product specifications, or damage caused by an accident, disaster, acts of God, neglect, abuse, misuse, transporation, alterations, attachments, accessories, supplies, non-CTI parts, non-CTI repairs or activities, or to any damage whose proximate cause was utilities or utility like services, or faulty installation or maintenance done by someone other than CTI. Control Technology Inc. reserves the right to make hanges to the Product in order to improve reliability, function, or design in the pursuit of providing the best possible Product. CTI assumes no responsibility for indirect or consequential damages resulting from the use or application of this equipment. Warranty continued on page 4.