5–7 I/O Module Selection & Wiring Guidelines

Load Device Common

Device Common

Sourcing Field Device Sourcing Field Device

Sinking Output Module

Device Input Current Flow Device Input

Module Output

I/O Module Selection Criteria

Configuration #6 DL305 DC Current Sinking Output Module

Module Output Current Flow

Load

Current Flow

Module Common

+ – DC Supply

Configuration #7 DL305 DC Current Sourcing Output Module Load Device Common

Device Common

Sinking Field Device Sinking Field Device

Sourcing Output Module

Device Input Current Flow Device Input

Module Output Module Output

Current Flow

Load

+

DC Supply

Current Flow

Module Common

I/O Module Selection & Wiring Guidelines

–

Page 108

5–8 I/O Module Selection Criteria

I/O Module Selection & Wiring Guidelines

Configuration #8 DL305 AC/DC Current Sink/Source (Relay) Output Module Load Device Common

Field Device

Relay Output Module

Device Input –

+

Or

Module Output Module Common

+ – DC Supply Load Device Common

Field Device

Device Input Module Output

Module Common AC Supply

Configuration #9 DL305 AC Output Module Load Device Common

Field Device

Device Input

AC Output Module Module Output Module Common

AC Supply

I/O Module Selection & Wiring Guidelines

Load Device Common

Field Device

Device Input Module Output

Module Common AC Supply

Page 109

5–9 I/O Module Selection & Wiring Guidelines

NPN Field Device Example

24VDC + – +

I/O Module Selection Criteria

Solid State Field Device Wiring to DC Input Modules

D3–08ND2 Input Module

Sensor

Input

Output

–

+

–

Optical Isolator

Common

(NPN) Current Sinking Field Device Current Sourcing Configuration

PNP Field Device Example D3–16NE3 Input Module

24VDC + – +

Sensor

Common

Output Input

–

Current Sinking Input Module

I/O Module Selection & Wiring Guidelines

(PNP) Current Sourcing Field Device

Optical Isolator

Page 110

5–10 I/O Module Selection Criteria

I/O Module Selection & Wiring Guidelines

Derating Characteristics The DL305 input and output module operating specifications change depending on ambient temperature. The I/O specifications have a derating chart for each module which shows functionality in respect to ambient temperature. The example below shows a derating curve for a D3–08ND2 discrete input module where the operating specifications do not change within the specified temperature operating range. Points 8

6

4

2

0 0 32

10 50

20 68

30 86

40 104

50 122

60°C 140° F

Ambient Temperature (°C/°F)

The example below shows a derating curve for a D3–16TD–1 discrete output module where the operating specifications are affected depending on ambient temperature. Points 16 0.25A 0.35A

12

I/O Module Selection & Wiring Guidelines

8 0.5A 4

0 0 32

10 50

20 68

30 86

40 104

Ambient Temperature (°C/°F)

50 122

60°C 140° F

Page 111

5–11 I/O Module Selection & Wiring Guidelines

General Considerations

The following information is to give you a general idea on how to wire the different types of modules in the DL305 system. For specific information on wiring a particular module refer to the specification sheet in the appropriate I/O chapter. Consider the following guidelines when connecting the field wring. 1. There is a maximum AWG the modules can accept. You can uses a smaller AWG than is noted in the table below. Module type Maximum AWG 8 point

12

16 point

16

I/O Module Selection Criteria

I/O Wiring Guidelines

2. Always use a continuous length of wire, do not combine wires to attain a desired length. 3. Use the shortest possible cable length. 4. Use wire trays for routing where possible 5. Avoid running wires near high energy wiring. 6. Avoid running input wiring in close proximity to output wiring where possible. 7. To minimize voltage drops when wires must run a long distance , consider using multiple wires for the return line. 8. Avoid running DC wiring in close proximity to AC wiring where possible. 9. Avoid creating sharp bends in the wires. Wiring the Different There are three main types of module faces for the DL305 I/O. These module faces are: lift covers over terminal blocks, flip covers over terminal blocks and D–shell Module Types compatible sockets. If the module you are using has a cover you can remove the cover either by lifting from the bottom or by flipping the door open. Some of the modules have removable terminal blocks. These modules can be recognized by the squeeze tabs on the top and bottom of the terminal block. To remove the terminal block, press the squeeze tabs and pull the block away from the module. WARNING: For some modules, field device power may still be present on the terminal block even though the PLC system is turned off. To minimize the risk of electrical shock, check all field device power before you remove the connector.

Squeeze Tab

Removable Cover

Squeeze Tab Removable Terminal Block

I/O Module Selection & Wiring Guidelines

D-shell Connector

Page 112

5–12 I/O Module Selection Criteria

I/O Module Selection & Wiring Guidelines

Fuse Protection To help avoid blowing the internal module fuses, we suggest you add external fuses to your I/O wiring. A fast blow fuse with a lower current rating than the I/O module fuse can be added to each common. Or, you can add a fuse with a rating of slightly less than the maximum current per output point to each output. Refer to the I/O module specification sheets to find the maximum current per point or per common for output modules. Adding the external fuse does not guarantee the prevention of module damage, but it will provide added protection. External Fuse Example

External Fuses (shown with DIN Rail, Fuse Blocks)

I/O Module Selection & Wiring Guidelines

WARNING: For modules which have soldered-in or non-replaceable fuses, we recommend that you return the module to us and let us replace your blown fuse(s) since the module fuses are attached to the board and disassembling the module will void your warranty.

Page 113

Discrete Input Modules In This Chapter. . . .

16

Ċ Discrete Input Module Identification and Terminology Ċ D3-08ND2, 24 VDC Input Module Ċ D3-16ND2-1, 24 VDC Input Module Ċ D3-16ND2-2, 24 VDC Input Module Module Ċ D3-16ND2F, 24 VDC Fast Response Input Module Ċ F3-16ND3F, TTL/24 VDC Fast Response Input Module Ċ D3-08NA-1, 110 VAC Input Module Ċ D3-08NA-2, 220 VAC Input Module Ċ D3-16NA, 110 VAC Input Module Ċ D3-08NE3, 24 VAC/DC Input Module Ċ D3-16NE3, 24 VAC/DC Input Module Ċ D3-08SIM, Input Simulator

Page 114

6–2 Discrete Input Modules

Discrete Input Modules

Discrete Input Module Identification and Terminology This chapter contains I/O specification sheets for the discrete input modules. The diagram below shows the status indicator location for some of the most common discrete input modules. Discrete Input Module Status Indicators

Squeeze Tab

Squeeze Tab

Discrete Input Modules

Removable Cover

Color Coding of I/O The DL305 family of I/O modules has a color coding scheme to help you identify whether the module is an input module, an output module or a special module. This Modules is done through a color bar indicator located on the front of each module below the part number. The following color scheme is used. Color Bar

å

110VAC INPUT D3–16NA

I

I

0 1 2 3 C

0 1 2 3 4 5 6 7 C 0

4 5 6 7

0 1 2 3

4 5 6 7

II

Module Type Color Code Discrete/Analog Output Red Discrete/Analog Input Blue Other White

1 2 3 4 5 6 7

Input Module Selection

II

Your input module selection depends on the field devices used and system performance requirements. The input module specifications in this chapter list the information needed for choosing the correct module for a field device and to assure it meets the system requirements. The following list defines the specifications listed in this chapter.

Page 115

6–3 Discrete Input Modules

Commons Per Module

Number of commons per module and their electrical characteristics.

Input Voltage Range

The operating voltage range of the input circuit. DL305 input modules require either an internal or external power supply for the operating voltage. The base power supply will provide the internal voltage.

Peak Voltage

Maximum voltage allowed for the input circuit.

AC Frequency

AC modules are designed to operate within a specific frequency range. 60 Hz is the standard AC frequency in the U.S., 50 Hz is common in other countries.

ON Voltage Level

The voltage level at which the input point will turn ON.

OFF Voltage Level

The voltage level at which the input point will turn OFF.

Input Current

Typical operating current for an active (ON) input.

Input Impedance

Input impedance can be used to calculate input current for a particular operating voltage.

Minimum ON Current

The minimum current for the input circuit to operate reliably in the ON state.

Maximum OFF Current

The maximum current for the input circuit to operate reliably in the OFF state.

Base Power Required

Power from the base power supply is used by the DL305 input modules and varies between different modules. The guidelines for using module power is explained in the power budget configuration section in chapter 4.

OFF to ON Response

The time the module requires to process an OFF to ON state transition.

ON to OFF Response

The time the module requires to process an ON to OFF state transition.

Terminal Type

Indicates whether the terminal type is a removable or non-removable connector or terminal.

Status Indicators

LEDs indicate the ON/OFF status of an input point. These LEDs are electrically located on either the logic side or the field device side of the input circuit.

Weight

Indicates the weight of the module. (See Appendix D for a complete listing of DL305 component weights.)

Discrete Input Modules

Indicates number of input points per module and designates current sinking, current sourcing, or either. Discrete Input Modules

Inputs Per Module

Page 116

6–4 Discrete Input Modules

Discrete Input Modules

D3–08ND2, 24 VDC Input Module Inputs per module Commons per module Input voltage range Input voltage Peak voltage AC frequency ON voltage level OFF voltage level Input impedance Input current Minimum ON current Maximum OFF current

8 (current sourcing) 2 (internally connected) 18–36VDC Internally supplied 40 VDC N/A <3V >18 V 1.8 K ohm 12 mA Max 7 mA 3 mA

Base power required

9V 10 mA Max 24V 14mA/ON pt. (112 mA Max)

OFF to ON response ON to OFF response Terminal type Status indicators Weight

4–15 ms 4–15 ms Non–removable Field side 4.2 oz. (120 g)

Derating Chart for D3–08ND2 Points 24VDC INPUT

8

Discrete Input Modules

D3–08ND2

Internallly Connected

C1

0

4

1

5

2

6

3

7

6 4 2

0

1

C 1

2

3

0 1

4

5

2 3

6

7

4 5

0 0 32

Common

10 20 30 40 50 60 °C 50 68 86 104 122 140°F Ambient Temperature (°C/°F)

24VDC – +

Other 7 Circuits 9V

6 7

C2 C 2

Input

1.8k

Optical Coupler