DL305 User Manual, pages 97 to 106

Pages 97 to 106 of 356

The original document is the PDF (3.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the GE DL330 / D3-330, Fanuc DL330 / D3-330 and GE Fanuc DL330 / D3-330

Page 97

4–29 Bases, Expansion Bases, and I/O Configuration

24V Power Required in mA

External Power Source Required

D3–232–DCU

500

0

0

Optional 5VDC @ 500mA

D3–422–DCU

500

0

0

Optional 5VDC @ 500mA

F3–UNICON

0

0

0

(24 VDC or 5 VDC) @ 100mA

F3–AB128–R

0

205

0

None

F3–AB128–T

0

205

0

None

F3–AB128

0

90

0

None

F3–AB64

0

90

0

None

D3–08SIM

0

10

112

None

D3–HSC

0

70

0

None

D3–PWU

800

0

0

Optional 5VDC @ 800mA

D3–HP

50

50

0

Optional

D3–HPP

50

50

0

Optional

Communications and Networking

ASCII BASIC Modules

Bases and Expansion Bases

9V Power Required in mA

Bases and Expansion Bases

5V Power Required in mA

Specialty Modules

Programming

Bases, Expansion Bases and I/O Configuration

Page 98

4–30

Bases and Expansion Bases

Bases and Expansion Bases

Bases, Expansion Bases, and I/O Configuration

Power Budget Calculation Example Base #

The following example shows how to calculate the power budget for the DL305 system. Module Type

5 VDC (mA)

9 VDC (mA)

24 VDC (mA) and/or Auxiliary Base Power Source 24 VDC Output (mA)

1 Base Used

D3–05B

1400

800

500

Slot 1

D3–330

+ 300

+ 50

+

0

Slot 2

D3–16NE3

+

0

+ 130

+

0

Slot 3

D3–16NE3

+

0

+ 130

+

0

Slot 4

F3–16TA–1

+

0

+ 160

+

0

Slot 5

F3–16TA–1

+

0

+ 160

+

0

D3–232–DCU

+ 500

+

+

0

Slot 6 Slot 7 Slot 8 Slot 9 Slot 10

Bases, Expansion Bases and I/O Configuration

Other

Maximum power required Remaining Power Available

800 1400 – 800 = 600 800 – 630

0

630 = 170 500 – 0

0 = 500

1. Using the tables at the beginning of the Power Budgeting section of this chapter fill in the information for the Base, CPU, I/O modules, and any other devices that will use system power including devices that use the 24 VDC output. Pay special attention to the current supplied by the base which you have selected since they do differ. Devices which fall into the “Other” category are devices such as the Data Communications Unit and the Handheld programmer which plug onto the CPU. 2. Add the current columns starting with slot 1 and put the total in the row labeled “Maximum power required”. 3. Subtract the row labeled “Maximum power required” from the row labeled “Base Used”. Place the difference in the row labeled “Remaining Power Available”. 4. If “Maximum Power Required” is greater than “Base Used” in any of the three columns, the power budget will be exceeded. It will be unsafe to use this configuration and you will need to restructure your base/module configuration.

Page 99

4–31 Bases, Expansion Bases, and I/O Configuration

Base #

This blank chart is provided for you to copy and use in your power budget calculations.

Module Type

5 VDC (mA)

9 VDC (mA)

24 VDC (mA) and/or Auxiliary Base Power Source 24 VDC Output (mA)

Bases and Expansion Bases

Power Budget Calculation Worksheet

Base Used Bases and Expansion Bases

Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8 Slot 9 Slot 10 Other

Remaining Power Available 1. Using the tables at the beginning of the Power Budgeting section of this chapter fill in the information for the Base, CPU, I/O modules, and any other devices that will use system power including devices that use the 24 VDC output. Pay special attention to the current supplied by the base which you have selected since they do differ. Devices which fall into the “Other” category are devices such as the Data Communications Unit and the Handheld programmer which plug onto the CPU. 2. Add the current columns starting with slot 1 and put the total in the row labeled “Maximum power required”. 3. Subtract the row labeled “Maximum power required” from the row labeled “Base Used”. Place the difference in the row labeled “Remaining Power Available”. 4. If “Maximum Power Required” is greater than “Base Used” in any of the three columns, the power budget will be exceeded. It will be unsafe to use this configuration and you will need to restructure your base/module configuration.

Bases, Expansion Bases and I/O Configuration

Maximum power required

Page 100

This page is a scan with no text; see it in the PDF.

Page 101

I/O Module Selection & Wiring Guidelines In This Chapter. . . .

15

Ċ I/O Selection Considerations Ċ Sinking and Sourcing Circuits Ċ DL305 Input Module Configuration Chart Ċ DL305 Output Module Configuration Chart Ċ Configuration #1 DL305 DC Current Sourcing Input Module Ċ Configuration #2 DL305 DC Current Sinking/Sourcing Input Module Ċ Configuration #3 DL305 DC Current Sinking Input Module Ċ Configuration #4 DL305 AC/DC Input Module Ċ Configuration #5 DL305 AC Input Module Ċ Configuration #6 DL305 DC Current Sinking Output Module Ċ Configuration #7 DL305 DC Current Sourcing Output Module Ċ Configuration #8 DL305 AC/DC Current Sink/Source (Relay) Output Module Ċ Configuration #9 DL305 AC Output Module Ċ Solid State Field Device Wiring to DC Input Modules Ċ Derating Characteristics Ċ I/O Wiring Guidelines Ċ Fuse Protection

Page 102

5–2 I/O Module Selection Criteria

I/O Module Selection & Wiring Guidelines

I/O Selection Considerations I/O Module Selection

The DL305 product family offers various types of I/O modules for interfacing many different field devices to the PLC system. There are several electrical characteristics that should be considered when choosing the proper I/O module for a field device or for obtaining required system performance. Electrical characteristics for discrete input modules and discrete output modules are discussed in Chapters 6 and 7. The DL305 family also offers several specialized modules such as analog, ASCII BASIC modules, network interface modules, high speed counter modules, etc. These modules have their own manuals, so if you are using them you should supplement this manual with the manual specifically designed for the special module.

Sinking and Sourcing Circuits

I/O Module Selection & Wiring Guidelines

The charts on the following page supply information on the current sinking and current sourcing configurations using DL305 discrete I/O modules. If you have a question about the type of device required to connect to a particular module please refer to the following charts. The charts show nine common input and output module configurations. Match the module part number you are considering to the applicable configuration(s) to ensure the module type will work in your application. For additional clarification we have included nine diagrams depicting the configurations listed in the charts. These diagrams show the module category, type of device and how they are connected to each other. The diagrams and two examples of wiring a solid state switch to an input module follow the charts on the next page.

Page 103

5–3 I/O Module Selection & Wiring Guidelines

DL305 Input Module Type

Config #1 DC Current Sourcing Input

D3–08ND2

✔

D3–16ND2–1

✔

D3–16ND2–2

✔

D3–16ND2F

✔

Config #2 DC Current Sink/Sourcing Input

Config #3 DC Current Sinking Input

Config #4 AC/DC Input

Config #5 AC Input

I/O Module Selection Criteria

DL305 Input Module Configuration Chart

✔

F3–16ND3F D3–08NA–1

✔

D3–08NA–2

✔

D3–16NA

✔

D3–08NE3

✔

✔

✔

✔

✔

D3–16NE3

✔

✔

✔

✔

✔

DL305 Output Module Configuration Chart DL305 Output Module Type D3–08TD1

Config #6 DC Current Sinking Output

Config #9 AC Output

✔ ✔

D3–08TD2 D3–16TD1–1

✔

D3–16TD1–2

✔

D3–16TD2

Config #7 Config #8 DC Current Sourcing AC/DC Current Output Sink/Sourcing Output

✔ ✔

D3–08TA–1

✔

D3–08TA–2

✔

F3–16TA–1

✔

D3–16TA–2

✔

D3–08TR

✔

F3–08TRS–1

✔

F3–08TRS–2

✔

D3–16TR

✔

D3–04TAS

✔

I/O Module Selection & Wiring Guidelines

F3–08TAS

Page 104

5–4 I/O Module Selection Criteria

I/O Module Selection & Wiring Guidelines

Configuration #1 DL305 DC Current Sourcing Input Module

Device Common

Device Common

Sinking Field Device Sinking Field Device

Sourcing Input Module

Device Output Current Flow Device Output

Module Input Current Flow

Current Flow –

+

DC Supply

Module Input

Module Common

Note: Some modules may have their own internal power supply and do not require an external supply as shown here. See individual input voltage specifications to find out power supply requirements.

Configuration #2 DL305 DC Current Sinking/Sourcing Input Module

Device Common

Sourcing Field Device

Sink/Source Input Module

Device Output Current Flow

Current Flow +

Module Input

Module Common

}

Current Sinking Input Configuration

–

I/O Module Selection & Wiring Guidelines

DC Supply

Device Common

Sinking Field Device

Device Output Current Flow

Current Flow – + DC Supply

REV A–1

Module Input

Module Common

}

Current Sourcing Input Configuration

Page 105

5–5 I/O Module Selection & Wiring Guidelines

Device Common

Device Common

Sourcing Field Device Sourcing Field Device

Sinking Input Module

Device Output Current Flow Device Output

Module Input Module Input

Current Flow

Current Flow +

I/O Module Selection Criteria

Configuration #3 DL305 DC Current Sinking Input Module

Module Common

–

DC Supply

Configuration #4 DL305 AC/DC Input Module

Device Common

Field Device

AC/DC Input Module

Device Output –

+

Or

Module Input

Module Common

+ – DC Supply

Field Device

Device Output Module Input

Module Common AC Supply

I/O Module Selection & Wiring Guidelines

Device Common

Page 106

5–6 I/O Module Selection Criteria

I/O Module Selection & Wiring Guidelines

Configuration #5 DL305 AC Input Module

Device Common

Field Device

Device Output

AC Input Module Module Input

Module Common AC Supply

Device Common

Field Device

Device Output Module Input

Module Common

I/O Module Selection & Wiring Guidelines

AC Supply