Programming Basics In This Chapter. . . .
Ċ Introduction Ċ Using Boolean Instructions Ċ Using Timers Ċ Using Counters Ċ Using the Accumulator
19
Page 188
9–2 Programming Basics
Introduction This chapter describes some basic programming concepts used with the DL305 CPUs. It doesn’t provide detailed information on each instruction, but instead shows how you can use the most basic elements of the instruction set. If you have quite a bit of PLC programming experience, you may already know some of the information. However, we suggest you at least read the portion that discusses the accumulator operation. The accumulator is used in many different operations. This chapter provides an overview of the following programming concepts. 1. Boolean Instructions 2. Timer Instructions 3. Counter Instructions 4. Shift Register Instruction 5. Accumulator Instructions
Programming Basics
Detailed examples of all categories of instructions are included in Chapters 11 & 12. The DL305 CPUs can be programmed with the DirectSOFT PC-based programming package, or by using the DL305 handheld programmer. There is a separate manual available for each of these products. If your are not familiar with the chosen programming device we recommend you use the appropriate programming device manual along with this manual to program your DL305 system. The following examples will help you understand how DL305 instructions are put together to create a program solution.
Page 189
9–3 Programming Basics
Using Boolean Instructions Do you ever wonder why so many PLC manufacturers always quote the scan time for a 1K boolean program? Simple. Most all programs utilize many boolean instructions. These are typically very simple instructions designed to join input and output contacts in various series and parallel combinations. Since the DirectSOFT package allows you to use graphic symbols to build the program, you don’t absolutely have to know the boolean equivalents of the instructions. However, it may be helpful at some point, especially if you ever have to troubleshoot the program with a Handheld Programmer. The following paragraphs show how these boolean instructions are used to build simple ladder programs. END Statement
All DL305 programs require an END statement as the last instruction. This tells the CPU this is the end of the program. Any instructions placed after the END statement will not be executed. (This can be useful in some cases. See Chapter 13 for an example.) 000
020
All programs must have and END statement
OUT
END
Simple Rungs
You use a contact to start rungs that contain both contacts and coils. The boolean instruction that does this is called a Store or, STR instruction. The output point is represented by the Output or, OUT instruction. The following example shows how to enter a single contact and a single output coil. DirectSOFT Example 020 OUT
STR 000 OUT 020 END
END
Normally Closed Contact
Normally closed contacts are also very common. This is accomplished with the Store Not or, STRN instruction. The following example shows a simple rung with a normally closed contact. DirectSOFT Example 000
Handheld Mnemonics 020 OUT
END
STRN 000 OUT 020 END
Programming Basics
000
Handheld Mnemonics
Page 190
9–4 Programming Basics
Contacts in Series
Use the AND instruction to join two or more contacts in series. The following example shows two contacts in series and a single output coil. DirectSOFT Example 000
Handheld Mnemonics
001
020 OUT
STR 000 AND 001 OUT 020 END
END
Midline Outputs
Sometimes it is necessary to use midline outputs to get additional outputs that are conditional on other contacts. The following example shows how you can use the AND instruction to continue a rung with more conditional outputs. DirectSOFT Example 000
Handheld Mnemonics 020
001
OUT 021
002
OUT 003
STR 000 AND 001 OUT 010 AND 002 OUT 021 AND 003 OUT 022 END
022 OUT
END
Programming Basics
Parallel Elements
You may also join contacts in parallel. The OR instruction allows you to do this. The following example shows two contacts in parallel and a single output coil. DirectSOFT Example 000
Handheld Mnemonics 020 OUT
001
END
STR 000 OR 001 OUT 020 END
Page 191
9–5 Programming Basics
Joining Series Branches in Parallel
Quite often it is necessary to join several groups of series elements in parallel. The Or Store (ORSTR) instruction allows this operation. The following example shows a simple network consisting of series elements joined in parallel. DirectSOFT Example 000
Handheld Mnemonics 020
001
OUT 002
003
END
STR 000 AND 001 STR 002 AND 003 ORSTR OUT 020 END
Quite often it is also necessary to join one or more parallel branches in series. The Joining Parallel Branches in Series And Store (ANDSTR) instruction allows this operation. The following example shows a simple network with contact branches in series with parallel contacts. DirectSOFT Example 000
001
Handheld Mnemonics 020 OUT
002
STR 000 STR 001 OR 002 ANDSTR OUT 020 END
END
Comparative Boolean
In the following example when the value in counter C600 is equal to the constant value 1234, output 020 will energize.
C600
K1234
020 OUT
The DL330P also provides Comparative Boolean instructions, but they are greater than and less than instructions instead of equal and not equal.
Programming Basics
Many applications require comparisons of data values. This is especially true in applications that use counters. Some PLC manufacturers make it really difficult to do a simple comparison of a counter value and a constant or register. The DL330 and DL340 CPUs provide Comparative Boolean instructions that allow you to quickly and easily solve this problem. Comparative Boolean evaluates two 4-digit values using boolean contacts. The valid evaluations are equal and not equal.
Page 192
9–6 Programming Basics
Combination Networks
You can combine the various types of series and parallel branches to solve most any application problem. The following example shows a simple combination network. 000
002
005
020 OUT
001
003
004
006
END
Boolean Stack
There are limits to how many elements you can include in a rung. This is because the DL305 CPUs use an 8-level boolean stack to evaluate the various logic elements. The boolean stack is a temporary storage area that solves the logic for the rung. Each time you enter a STR instruction, the instruction is placed on the top of the boolean stack. Any other instructions on the boolean stack are pushed down a level. The AND, OR, ANDSTR, and ORSTR instructions combine levels of the boolean stack when they are encountered. Since the boolean stack is only eight levels, an error will occur if the CPU encounters a rung that uses more than the eight levels of the boolean stack.
Programming Basics
All of you software programmers may be saying, “I use DirectSOFT, so I don’t need to know how the stack works.” Not quite true. Even though you can build the network with the graphic symbols, the limits of the CPU are still the same. If the stack limit is exceeded when the program is compiled, an error will occur.
Page 193
9–7 Programming Basics
The following example shows how the boolean stack is used to solve boolean logic.
000
STR
STR
001
ORSTR
AND 004
020 OUT
STR
002 AND 003
005
Output
ANDSTR
OR
STR 000
STR 001
STR 002
AND 003
1
1
STR 001
1
STR 002
1
002 AND 003
2
2
STR 000
2
STR 001
2
STR 001
3
3
3
STR 000
3
STR 000
4
4
4
4
5
5
5
5
6
6
6
6
7
7
7
7
8
8
8
8
STR 000
ORSTR
AND 004
OR 005
1
001 OR (002 AND 003)
1
004 AND [001 OR (002 AND 003)]
1
NOT 005 OR 004 AND [001 OR (002 AND 003)]
2
STR 000
2
STR 000
2
STR 000
3
3 S S
3 S S
8
8
1
000 AND (NOT 005 OR 004) AND [001 OR (002 AND 003)]
2 3 S S
8
8
Programming Basics
ANDSTR
S S
Page 194
9–8 Programming Basics
Using Timers Timers are used to time an event for a desired length of time. The single input timer will time as long as the input is on. When the input changes from on to off the timer current value is reset to 0. Timers normally time in tenth of a second intervals, but you can turn on Special Relay 770 to change the timers to hundredth of a second intervals. There is discrete bit associated with each timer to indicate the current value is equal to or greater than the preset value. The timing diagram below shows the relationship between the timer input, associated discrete bit, current value, and timer preset. 001
TMR
T600 K30
Input 001
Timer preset T600
Timer
Programming Basics
T600 Contact Current Value
0
10
20
30
40
50
60
0
020 OUT
Page 195
9–9 Programming Basics
Using Counters Counters are used to count events. There are two types of counters. S Regular Up counters S Stage counters (used with the RLL PLUS instructions) The up counter has two inputs, a count input and a reset input. The maximum count value is 9999. The timing diagram below shows the relationship between the counter input, counter reset, associated discrete bit, current value, and counter preset. 0
1
2
3
4
5
6
7
8
001
CNT
001
C600 K3
Up 002
Reset 002
Counter preset CT600 1
Current Value
2
3
4
0
The stage counter has a count input and is reset by the RST instruction. This instruction is used with the RLL PLUS instructions. The maximum count value is 9999. The timing diagram below shows the relationship between the counter input, associated discrete bit, current value, counter preset and reset instruction. 0
1
2
3
4
5
6
7
8
Up
001
1
2
3
4
0
Programming Basics
RST CT
SGCNT C600 K3
Counter preset
CT600 Current Value
001
Page 196
9–10 Programming Basics
Using the Accumulator
Copying Data to and from the Accumulator
The accumulator in the DL305 series CPUs is a 16 bit register which is used as a temporary storage location for data being copied or manipulated in some manor. For example, you have to use the accumulator to perform math operations such as add, subtract, multiply, etc. Since there are 16 bits, you can use up to a 4-digit BCD number. The accumulator is reset to 0 at the end of every CPU scan. The Data Store (DSTR) and Data Out (DOUT) instructions and their variations are used to copy data from a register location to the accumulator, or to copy data from the accumulator to a register location. In the following example, when input 000 is on the value (7502) in R402 and R403 is loaded into the accumulator using the Data Store (F50) instruction. The value in the accumulator is output to data registers R404 and R405 using the Data Out (F60) instruction. DirectSOFT Display 000
R 403
R 402
7
0
2
2
Accumulator
0
2
5
DSTR (F50) R 402 7
5
0
DOUT (F60) R 404 7
5
R405
R404
You probably noticed it took two registers to hold a 4-digit BCD number. This is because each BCD digit requires four binary bit positions.
Programming Basics
Since the accumulator is 16 bits and register locations are 8 bits, there are variations of the DSTR and DOUT instructions that allow you to copy a single register, or even half of a register (4 bits) either to or from the accumulator. The following example shows how you could use the DSTR3 and DOUT2 instructions to copy the lower 4 bits from register 5 to the upper 4 bits of register 16. (These registers correspond to I/O points and Control Relays respectively.) DirectSOFT Display 000 DSTR3 (F53) R 005 Load the lower 4 bits in register 5 into the lower 4 bits of the accumulator DOUT2 (F62) R 016 Output the lower 4 bits of the accumulator to the upper 4 bits of R16
R005
The upper 4 bits (*) of R5 are not loaded into the accumulator 0
0
The upper 4 bits (*) of R400 are not altered
*
8
0
8
8
*
R016
Accumulator