Page 197

9–11 Programming Basics

Changing the Accumulator Data

Instructions that change or manipulate data in some way also use the accumulator. The result of the change resides in the accumulator. The original data that was being changed is cleared from the accumulator. In the following example, when input 000 is on the value in R000 and R010 is loaded into the accumulator using the Data Store 5 (F55) instruction. The bit pattern in the accumulator is shifted to the left 4 bit positions using the Shift Left (F80) instruction. Notice how the result resides in the accumulator. The value in the accumulator is copied to data registers R404 and R405 using the Data Out (F60) instruction. DirectSOFT Display 000

R 010

R 000

6

3

9

5

DSTR5 (F55) R 000 Load the value in registers R0 and R10 into the accumulator 7

6

0

1

I/O Points 100-107 5 4 3 2 1 0 1

0

1

0

Acc.

1

S S

Shifted out of accumulator

SHFL (F80) K4

0

7

6

0

0

I/O Points 000-007 5 4 3 2 1 0 1

1

0

1

0

1

S S

15 14 13 12 11 10 9

8

7

6 5

4 3

2

1

0

1

1

0

1

1

0

0

0

0

0

1

0

0

1

0

0

Shift the value in the accumulator 4 bits to the left 776 will be ON after the shift 777 will be OFF after the shift

9

DOUT (F60) R 404 Copy the value in the accumulator to registers R404 and R405

3

R 405

5

0

R 404

776 Shifted a “1” out of Accumulator 777

Programming Basics

Accumulator equals zero after shift

Page 198

9–12 Programming Basics

Accumulator Operations

The following table lists several instructions that utilize the accumulator. Not all instructions allow you to use all the different memory types. Chapters 11 & 12 provide details on these instructions. Memory Areas

Category

Data Load

Programming Basics

4-digit BCD Const.

Shift Register Coils

Description

I/O

CRs

DSTR (F50)

Load a 4-digit constant or a 2-bytes of register data into the accumulator

DSTR 1 (F51)

Load 1-byte of register data into the accumulator

DSTR 2 (F52)

Load the upper 4 bits of a register into the lower 4 bits of the accumulator

DSTR 3 (F53)

Load the lower 4 bits of a register into the upper 4 bits of the accumulator

DSTR 5 (F55)

Load the digital values of 16 I/O points (2 bytes) into the accumulator

DOUT (F60)

Write the accumulator to 2 sequential registers

DOUT 1 (F61)

Write the lower byte of the accumulator to a register

DOUT 2 (F62)

Write the lower 4 bits of the accumulator to the upper 4 bits of a register

DOUT 3 (F63)

Write the lower 4 bits of the accumulator to the lower 4 bits of a register

DOUT 5 (F65)

Write the contents of the accumulator to a 16-point output module (2 bytes)

CMP (F70)

Compare a 2-byte BCD reference or a 4-digit BCD constant to the accumulator

ADD (F71)

Add a 2-byte BCD reference or a 4-digit BCD constant to the accumulator

SUBTRACT (F72)

Subtract a 2-byte BCD reference or a 4-digit BCD constant from the accumulator

MULTIPLY (F73)

Multiply a 2-byte BCD reference or a 4-digit BCD constant by the value in the accumulator

DIVIDE (F74)

Divide the accumulator by a 2-byte BCD reference or a 4-digit BCD constant

Mnemonic

Data Out

Math

Current Values

Data Register, Memory Type available for use with the instruction X, Not available

Page 199

9–13 Programming Basics

Memory Areas

Category

Bit Manipulation

Data Conversion

Fault Detection

Current Values

4-digit BCD Const.

Shift Register Coils

Description

I/O

CRs

Data Register

DAND (F75)

Performs a bit “AND” on a 2-byte reference or a 4-digit BCD constant and the bits in the accumulator

DOR (F76)

Performs a bit “OR” on a 2-byte reference or a 4-digit BCD constant and the bits in the accumulator

SHIFT RIGHT (F80)

Shifts the contents of the accumulator to the right a specified number of times. 1 – 15 bits can be shifted.

SHIFT LEFT (F81)

Shifts the contents of the accumulator to the left a specified number of times. 1 – 15 bits can be shifted.

DECODE (F82)

Decodes the first 4 bits of the accumulator into a decimal number.

ENCODE (F83)

Encodes an accumulator bit into a 4-bit code that represents the decimal number (0–15).

INV (F84)

Logically inverts the contents of the accumulator (1 to 0, 0 to 1).

BCD–BIN (F85)

Converts the accumulator value from BCD to Binary

BIN–BCD (F86)

Converts the accumulator value from Binary to BCD

FAULT (F20)

Sends a 4-digit BCD number, from a 2-byte reference or a constant, to the programmer display

Mnemonic, Memory Type available for use with the instruction X, Not available Programming Basics

Page 200

This page is a scan with no text; see it in the PDF.

Page 201

RLL PLUS Programming Basics In This Chapter. . . .

110

Ċ Introduction Ċ An Example Machine Ċ An RLL Solution Ċ An RLLā PLUS Solution Ċ Stage Instruction Execution Ċ Activating Stages Ċ Using Outputs in Stages Ċ Using Timers and Counters in Stages Ċ Using Data Instructions in Stages Ċ Using Comparative Contacts in Stages Ċ Parallel Branching Concepts Ċ Unusual Operations in Stages Ċ Two Ways to View RLLā PLUS Programs Ċ Designing a Program Using RLLā PLUS Instructions

Page 202

10–2

RLL PLUS Programming Basics

Introduction If you’ve ever been around some really accomplished RLL programmers you have probably been amazed at how easily they seem to be able to create programs of incredible complexity. Well, not everyone has years of experience in programming PLCs. Because of this the DL330P CPU has RLL PLUS instructions that make it considerably easier to design and create programming solutions. These instructions are especially useful to those of you who aren’t that familiar with the interlocking concepts commonly used in RLL programs. You can still use the normal instructions you’ve already seen, plus you only have to become familiar with a few new instructions that help you organize your program into manageable pieces. This programming method is similar to Sequential Function Chart programming and literally allows you to design a flowchart of the program operation sequence and load it into the CPU! You can expect to see several benefits by using this method. S Considerably reduced program design time. We’ve seen many, many cases where these few instructions have cut program design time by well over 50%. S Shorter, more simple programs. Later in this chapter we’ll show you why your programs sometimes end up being a lot larger than you first anticipated. The RLL PLUS instructions can help make your programs simple for everyone to understand. S Easier program troubleshooting. How many times have you tried to troubleshoot or modify a program that was written by someone else? If you’ve done this very often you know it’s not an easy task. This chapter will show you a few instructions that will also help with this problem as well. The following paragraphs discuss several RLL PLUS programming concepts. We’ll use a simple example to show you how to use the various types of instructions. Also, we’ll show you the equivalent program without RLL PLUS instructions to give you an idea of the differences between the two approaches.

RLLPLUS Programming Basics

NOTE: The DL330P has several instructions that do not operate quite the same as the equivalent instructions in the DL330 or DL340. If you want to take advantage of the benefits associated with the RLL PLUS instructions, make sure you also take time to review Chapter 12. This chapter discusses the instructions that are unique or different with the DL330P CPU.

Page 203

10–3

RLL PLUS Programming Basics

An Example Machine Machine Operation

Most any application can be described as a sequence of events. The PLC program merely makes sure the events are completed in a specific order. Not only does the program control normal operation, but it also has to allow for machine failures and emergency conditions. Consider a simple example. 1. The operator presses the start switch. 2. The machine checks for a part. If the part is present, the process continues. If not, the conveyor moves until a part is present. 3. The part is locked in place with a clamp. 4. The press stamps the part. 5. The clamp is unlocked and the finished piece is moved out of the press. 6. The process stops if the machine is in one-cycle mode, or the process continues if automatic mode is selected.

On/Off Switch Press Arm Part Part Detection Sensor

Clamp

Machine Flowchart The following diagram provides a flowchart of this operations sequence. The flowchart breaks the program into logical steps Wait for Start

Check for Part

Lock the clamp

Press the Part

Unlock clamp

Move Conveyor

Step 1

Step 2

Step 3

Step 4

Step 5

Step 6

Continuous One Cycle Check Mode Inputs Start Switch Part Present Part Locked Part Unlocked Lower Limit Upper Limit Conveyor Indexed One-Cycle Switch

Outputs 000 001 002 003 004 005 006 007

Clamp Press Conveyor

020 021 022

RLLPLUS Programming Basics

Step 7

Page 204

10–4

RLL PLUS Programming Basics

An RLL Solution

RLLPLUS Programming Basics

Why is RLL so popular? Simple. Before the PLC arrived control problems were generally solved with hardwired relays and switches. About 30 years ago people started experimenting with a way to make quick and easy changes without changing the actual panel wiring. Thus, the PLC was born. Since the people developing and using this new technology were familiar with the relay and switch solution, it made sense to have this new technology emulate something that was familiar to them. That’s why RLL programs emulate a relay panel solution. When you supply power to a relay panel the combination of contact and coil status determines what actions take place. Since the RLL program emulates the relay panel solution, the entire program is scanned left-to-right, top-to-bottom. The program executes the operations sequence when a certain combination of contacts are activated. This process is known as interlocking. Since many PLCs do not have instructions to help manage the operations sequence, the programmer has to make sure the program carries out the correct sequence by adding the required interlocks. One great thing about the RLL solution is the individual rungs are easy to understand. By examining the contacts you can easily determine if the output will be on or off.

Executes all rungs Left to Right, Top to bottom Run

1 Cycle

Stop

RUN OUT

160

163

011

160

Start 000 RUN

Part Present

160

001

MCS

Part Unlocked

Release Clamp

003

162

Clamp OUT 020

Clamp 020 Press

Lower Limit

Index Conveyor

Press Complete OUT

004

006

161

021 Press Complete 161 Part Locked

Lower Limit

Press Complete

002

004

161

Press OUT 021

Press 021 Press Complete

Upper Limit

Release Clamp OUT

161

005

162

MCR

Press Complete 161

Part Index Unlocked Conveyor

Run

003 Part Present

160

001

1 Cycle

Index Conveyor

007

006

006

Conveyor OUT 022

1 Cycle OUT 163

- Interlock

Many accomplished RLL programmers use things such as Master Control Relays and Subroutines to reduce the amount of interlocking required. However, these instructions can sometimes make the program more difficult to understand. There are several things you should notice about our simple press program. S Most all rungs use some amount of interlocking. S The number of interlocks is usually proportional to the number of tasks in the operations sequence. S Most of the instructions are devoted to processing the interlocks. (Plus, since the program is larger, it takes more time to process.) S It usually requires several attempts until a program is designed that is not susceptible to inadvertent activation and deactivation. S The program can be difficult to debug if you do not have a considerable amount of RLL programming experience.

Page 205

RLL PLUS Programming Basics

10–5

An RLL PLUS Solution The RLL PLUS instructions keep the simplicity of the contacts and coils while removing some of the problems associated with the enormous amount of interlocks. There are several RLL PLUS instructions, but the most often used are the Initial Stage (ISG), Stage (SG), and Jump (JMP) instructions. Here’s the example press program created using RLL PLUS instructions. There are two things you should notice. S

Control Relay interlocks are not required. S The program directly follows the flowchart of the press operation. How can this happen? Simple. The interlocks were added to the RLL program to keep the outputs from coming on at the improper time. This is because every rung of the RLL program was examined on every scan. The Stage instructions (and the logic between the Stage instruction and the next stage instruction) are not necessarily examined on every scan. Only stages that are on are examined. Each stage instruction has a status bit that is on when the stage is active, and off when the stage is inactive. On every scan the CPU examines which stage status bits are on and only examines the logic in those stages. If a stage is inactive, the CPU skips the logic between that stage and the next active stage. The following pages will talk about several different aspects of the CPU execution for the Stage Instructions. It will help to understand the pieces of an individual stage. Stage Nomenclature As we discuss the examples it will be necessary for you to understand the various pieces that can make up a program stage.

S S

Stages, a instruction that denotes a piece of the program Actions - an event in the program, such as an output, jump, or some other instruction. Transitions, the event that causes the program to move to the next stage.

ISG

Wait for start

S000 Start

S1 JMP

000 SG

Check for a part

S001

Part Present

S2 JMP

001 Part Present

S5 JMP

001 SG

Lock the clamp

S002

Part Locked

Clamp SET 020 S4 JMP

002 SG

Press the part

S003

Press Down 021 Lower Limit

S4 JMP

004 SG

Unlock the clamp

S004 Top Limit

Clamp RST 020

005 Part Unlocked

S5 JMP

003 SG

Index the conveyor

S005

Move Conveyor 022 Conveyor Moved

S6 JMP

006 SG

One cycle or automatic?

S006

One Cycle

S0 JMP

007 One Cycle 007

S1 JMP

RLLPLUS Programming Basics

S

Only executes logic in stages that are active

Page 206

10–6

RLL PLUS Programming Basics

Stage Instruction Execution Stage Instruction Numbering

Stages are numbered in octal, so you can’t have any stages with the numbers 8 or 9 in them. Notice the stages skipped from 7 to 10 since the numbers 8 and 9 are not used. There are 128 (decimal) stages available in the DL330P CPU, numbered 0 through 177. Since each stage has a unique status bit, you cannot have stages with the same address number. For example, since the example program already has a Stage1, we wouldn’t want to use that number again. There’s another advantage to having a status bit for each stage. This allows you to skip stage numbers as necessary. This is a good practice to follow because it makes it easier to insert stages later without affecting the appearance of the program flow. The stage numbers do not necessarily have to be numbered sequentially, but it can be extremely helpful to use sequential numbers if you are working with large programs. Also, the stages do not have to be entered sequentially with the programming device. For example, you could have Stage 100 be the first entry in the program. This is not a good programming practice, but since the CPU looks at the active status bits to determine which stages to execute, it doesn’t care where the stages are physically located in the program.

Octal Numbering

SG S007

SG S008

No Duplicate Numbers SG S001

SG S001

SG S010

SG S020

RLLPLUS Programming Basics

SG S030

Non-sequential Numbering SG S012

SG S001

SG S020

Only executes logic in stages that are active SG

Press the part

S003

Press Down 021 Lower Limit

S4 JMP

004 ISG

Wait for start

S000

S1 JMP

000 SG

Check for a part

S001

Part Present

S2 JMP

001 Part Present

The section on Designing an RLL PLUS Program at the end of this chapter provides guidelines for assigning numbers to the stage instructions.

SG S002

Skip Numbers if Necessary

Start

NOTE: Remember, machines do break. We recommend you use numbering that matches the machine flowchart. Also, we recommend you enter the program in the same order whenever possible. This will make troubleshooting much easier.

SG S010

001

S5 JMP