Page 297
RLL PLUS Instruction Set Stage Instructions
12–3
Stage Instructions
Stage (SG) DL330P Only
The Stage instruction creates segments of a RLL PLUS program. Stages are activated by transitional logic, a jump or set stage executed from an active stage. Stages are de–activated one scan after transitional logic, a jump, or a reset stage instruction is executed. Data Type
Stages
SG
D3–330 Range
D3–340 Range aaaa aaaa aaaa
––
––
0–177
ISG
S aaa
SG
S aaa
D3–330P Range
RLLPLUS Instructions
The Initial Stage instruction is normally used as the first segment of a RLL PLUS program. Initial stages are activated when the CPU enters the run mode, this creates a starting point in the program. The Initial Stage can be made inactive by either jumping from it or resetting it. Multiple Initial Stages are allowed in a program.
Instruction Set
Initial Stage (ISG) DL330P Only
Page 298
12–4
RLL PLUS Instruction Set Stage Instructions
Instruction Set
The following example is a simple RLL PLUS program. This program utilizes the Initial Stage, Stage, and Jump instructions to create a structured program. DirectSOFT Display
ISG
Handheld Programmer Keystrokes
S0
000
010 OUT
001
S2 SET
RLLPLUS Instructions
005
S1 JMP
SG
S1
002
011 OUT
SG
S2
006
012 OUT
007
S1
S0 JMP
ISG STR
SHF SHF
0 0
ENT ENT
OUT STR SET
SHF SHF SG
1 1 SHF
0 ENT 2
STR JMP SG STR
SHF SG SHF SHF
5 1 1 2
ENT ENT ENT ENT
OUT SG STR
SHF SHF SHF
1 2 6
1 ENT ENT
ENT
OUT STR AND JMP
SHF SHF SG SG
1 7 1 0
2 ENT ENT ENT
ENT
ENT ENT
Page 299
RLL PLUS Instruction Set Stage Instructions
Not Jump (NOT JMP) DL330P Only
The Not Jump instruction allows the program to transition from an active stage which contains the jump instruction to another which is specified in the instruction. The jump will occur when the input logic is false. The active stage that contains the Not Jump will be de–activated 1 scan after the Not Jump instruction is executed. Data Type
Stages
SG
SG aaa JMP
SG aaa NJMP
RLLPLUS Instructions
The Jump instruction allows the program to transition from an active stage which contains the jump instruction to another which is specified in the instruction. The jump will occur when the input logic is true. The active stage that contains the Jump will be de–activated 1 scan after the Jump instruction is executed.
Instruction Set
Jump (JMP) DL330P Only
12–5
D3–330 Range
D3–340 Range aaaa aaaa
D3–330P Range aaaa
––
––
0–177
Page 300
12–6
RLL PLUS Instruction Set Stage Instructions
Instruction Set
The following example is a simple RLL PLUS program. This program utilizes the Initial Stage, Stage, Jump, and Not Jump instructions to create a structured program. DirectSOFT Display
Handheld Programmer Keystrokes
ISG
ISG STR
SG SHF
SHF 0
0 ENT
ENT
OUT STR JMP
SHF SHF SG
1 1 SHF
0 ENT 1
ENT
JMP SG STR
NOT SHF SHF
SG 1 002
SHF ENT ENT
2
OUT STR JMP
SHF SHF SG
1 3 SHF
1 ENT 2
ENT
SG STR OUT STR
SHF SHF SHF SHF
2 4 1 5
ENT ENT 2 ENT
JMP
SG
SHF
0
S0
000
010 OUT
001
S1 JMP
RLLPLUS Instructions
S2 NJMP
SG
S1
002
011 OUT
003
S2 JMP
SG
S2
004
012 OUT
005
S0 JMP
ENT
ENT
ENT ENT
ENT
Page 301
RLL PLUS Instruction Set Stage Instructions
The Store instruction begins a new rung or additional branch in a rung with a normally open stage contact. Status of the contact will be the same state as the associated Stage memory location.
Store Not Stage (STR NOT SG) DL330P Only
The Store Not instruction begins a new rung or additional branch in a rung with a normally closed stage contact. Status of the contact will be opposite the state of the associated stage memory location.
Stages
SG
SG aaa
D3–330 Range
D3–340 Range aaaa aaaa aaaa
––
––
0–177
RLLPLUS Instructions
Data Type
SG aaa
Instruction Set
Store Stage (STR SG) DL330P Only
12–7
D3–330P Range
In the following Store example, when stage contact 000 is on, output 010 will energize. DirectSOFT Display SG 000
Handheld Programmer Keystrokes 010 OUT
STR OUT
SG SHF
SHF 1
0 0
ENT ENT
In the following Store Not example, when stage contact 000 is off output 010 will energize. DirectSOFT Display SG 000
Handheld Programmer Keystrokes 010 OUT
STR OUT
NOT SHF
SG 1
SHF 0
0 ENT
ENT
Page 302
RLLPLUS Instructions
Instruction Set
12–8
RLL PLUS Instruction Set Stage Instructions
Or Stage (OR SG) DL330P Only
Or Not Stage (OR NOT SG) DL330P Only
The Or instruction logically ors a normally open stage contact in parallel with another contact in a rung. The status of the contact will be the same state as the associated stage memory location.
SG aaa
The Or Not instruction logically ors a normally closed stage contact in parallel with another contact in a rung. The status of the contact will be opposite the state of the associated stage memory location. Data Type
Stages
SG
SG aaa
D3–330 Range
D3–340 Range
D3–330P Range aaaa aaaa aaaa
––
––
0–177
In the following Or example, when input 000 or stage contact 001 is on output 010 will energize. DirectSOFT Display 000
Handheld Programmer Keystrokes 010 OUT
STR OR OUT
SHF SG SHF
0 SHF 1
ENT 1 0
ENT ENT
SG 001
In the following Or Not example, when input 000 is on or stage contact 001 is off output 010 will energize. DirectSOFT Display
000
Handheld Programmer Keystrokes 010 OUT
SG 001
STR OR OUT
SHF NOT SHF
0 SG 1
ENT SHF 0
1 ENT
ENT
Page 303
RLL PLUS Instruction Set Stage Instructions
The And instruction logically ands a normally open stage contact in series with another contact in a rung. The status of the contact will be the same state as the associated stage memory location.
And Not Stage (AND NOT SG) DL330P Only
The And Not instruction logically ands a normally closed stage contact in series with another contact in a rung. The status of the contact will be opposite the state of the associated stage memory location.
Stages
SG
SG aaa
D3–330 Range
D3–340 Range aaaa aaaa aaaa
–
–
0–177
RLLPLUS Instructions
Data Type
SG aaa
D3–330P Range
In the following And example, when input 000 and stage contact 001 is on output 010 will energize. DirectSOFT Display 000
Handheld Programmer Keystrokes SG 001
010 OUT
STR AND OUT
SHF SG SHF
0 SHF 1
ENT 1 0
ENT ENT
In the following And Not example, when input 000 is on and stage contact 001 is off output 010 will energize. DirectSOFT Display 000
Handheld Programmer Keystrokes SG 001
010 OUT
Instruction Set
And Stage (AND Stage) DL330P Only
12–9
STR AND OUT
SHF NOT SHF
0 SG 1
ENT SHF 0
1 ENT
ENT
Page 304
RLLPLUS Instructions
Instruction Set
12–10
RLL PLUS Instruction Set Stage Instructions
Set (SET) DL330P Only
The Set instruction sets or turns on a output or a consecutive range of outputs. Once the output is set it will remain on until it is reset using the Reset instruction. It is not necessary for the input controlling the Set instruction to remain on. The Set instruction is sometimes known as a latch. The Reset instruction is used to reset the output.
Reset (RST) DL330P Only
The Reset instruction resets or turns off an output or a consecutive range of outputs. Once the output is reset it is not necessary for the input to remain on. The Reset instruction is sometimes known as an unlatch instruction. Data Type
Optional memory range aaa aaa SET
Optional memory range aaa aaa RST
D3–330 Range
D3–340 Range aaaa aaaa
D3–330P Range aaaa
Outputs
––
––
000–177 700–767
Control Relays
––
––
160 – 167 170 – 174 200 – 277
In the following Set example, when input location 005 is on, outputs 20–37 will be set on. DirectSOFT Display 005
Handheld Programmer Keystrokes 020
037
SET
STR SET SHF
SHF SHF 3
5 2 7
ENT 0 ENT
ENT
In the following Reset example, when input location 006 is on, outputs 020–37 will be reset to the off state. DirectSOFT Display 006
Handheld Programmer Keystrokes 020 037 RST
STR RST SHF
SHF SHF 3
6 2 7
ENT 0 ENT
ENT
Page 305
RLL PLUS Instruction Set Stage Instructions
Reset Stage (RST SG) DL330P Only
The Reset instruction resets or turns off a stage or a consecutive range of stages. Once the stage(s) is reset it is not necessary for the input to remain on.
Data Type
Stage
Optional memory range SG aaa aaa SET SG
Optional memory range SG aaa aaa RST SG
D3–330 Range
D3–340 Range aaa aaa aaa
––
––
000–177
RLLPLUS Instructions
The Set Stage instruction sets or turns on a stage or a consecutive range of stages. Once the stage is set it will remain on until a transition is made to another stage or the stage is reset using the Reset Stage instruction. It is not necessary for the input controlling the Set Stage instruction to remain on.
D3–330P Range
In the following Set Stage example, when input 000 is on, stages 30–47 will be set on. DirectSOFT Display 000
Handheld Programmer Keystrokes 030 047 SETSG
STR SET SHF
SHF SG 4
0 SHF 7
ENT 3 ENT
0
ENT
In the following Reset Stage example, when input 003 is on, stages 30–47 will be reset off. DirectSOFT Display 003
Handheld Programmer Keystrokes 030 047 RSTSG
Instruction Set
Set Stage (SET SG) DL330P Only
12–11
STR RST SHF
SHF SG 4
3 SHF 7
ENT 3 ENT
0
ENT
Page 306
12–12
RLL PLUS Instruction Set Comparative Boolean Instructions
RLLPLUS Instructions
Instruction Set
Comparative Boolean Instructions Store If Greater Than or Equal To Timer (STR TMR) DL330P Only
The Store If Greater Than or Equal To instruction begins a new rung or additional branch in a rung with a normally open comparative timer contact. The contact will be on if the specified timer T aaa w B bbbb.
Store Not IF Greater Than Timer (STR NOT TMR) DL330P Only
The Store Not If Greater Than instruction begins a new rung or additional branch in a rung with a normally closed comparative timer contact. The contact will be on if the specified timer T aaa t B bbbb. Operand Data Type
D3–330 Range
T aaa
B bbbb
T aaa
B bbbb
D3–340 Range
D3–330P Range
B aaa bbbb aaa bbbb aaa bbbb
Timers
T
––
––
––
––
600–677
––
Data registers
R
––
––
––
––
––
400–577
Constant
K
––
––
––
––
––
0–9999
In the following Store If Greater Than or Equal To example, when T602 w the value 1538 the contact will turn on and output 014 will energize. DirectSOFT Display T602
K1538
Handheld Programmer Keystrokes 014 OUT
STR SHF
TMR 1
SHF 5
6 3
0 8
OUT
SHF
1
4
ENT
2 ENT
ENT
In the following Store Not If Greater Than example, when T602 t the value in R404 the contact will turn on and output 020 will energize. DirectSOFT Display T602
R404
Handheld Programmer Keystrokes 020 OUT
STR R
NOT 4
TMR 0
SHF 4
6 ENT
OUT
SHF
2
0
ENT
0
4
ENT