Page 307

12–13

RLL PLUS Instruction Set Comparative Boolean Instructions

Store Not If Greater Than Counter (STR NOT CNT) DL330P Only

The Store Not If Greater Than instruction begins a new rung or additional branch in a rung with a normally closed comparative counter contact. The contact will be on if the specified counter CT aaa t B bbbb. Operand Data Type

D3–330 Range

CTaaa

B bbbb

CT aaa

B bbbb

D3–340 Range

D3–330P Range

B aaa bbbb aaa bbbb aaa

Counters

CT

––

––

––

––

600–677 bbbb ––

Data registers

R

––

––

––

––

––

400–577

Constant

K

––

––

––

––

––

0–9999

In the following Store If Greater Than or Equal To example, when CT602 w the value in R404 the contact will turn on and output 014 will energize. DirectSOFT Display CT602

R404

Handheld Programmer Keystrokes 014 OUT

STR R

CNT 4

SHF 0

6 4

0 ENT

OUT

SHF

1

4

ENT

2

ENT

In the following Store Not If Greater Than example, when CT602 t the constant value 4620 the contact will turn on and output 020 will energize. DirectSOFT Display CT602

K4620

Handheld Programmer Keystrokes 020 OUT

STR SHF

NOT 4

CNT 6

SHF 2

6 0

OUT

SHF

2

0

ENT

0 ENT

2

ENT

RLLPLUS Instructions

The Store If Greater Than or Equal To instruction begins a new rung or additional branch in a rung with a normally open comparative counter contact. The contact will be on if the specified counter CT aaa w B bbbb.

Instruction Set

Store If Greater Than or Equal To Counter (STR CNT) DL330P Only

Page 308

RLLPLUS Instructions

Instruction Set

12–14

RLL PLUS Instruction Set Comparative Boolean Instructions

Or If Greater Than or Equal To Timer (OR TMR) DL330P Only

The Or If Greater Than or Equal To instruction connects a normally open comparative timer contact in parallel with another contact. The contact will be on if the specified timer T aaa w B bbbb.

Or Not If Greater Than Timer (OR NOT TMR) DL330P Only

The Or Not If Greater Than instruction connects a normally closed comparative timer contact in parallel with another contact. The contact will be on if the specified timer T aaa t B bbbb. Operand Data Type

D3–330 Range

T aaa

B bbbb

T aaa

B bbbb

D3–340 Range

D3–330P Range

B aaa bbbb aaa bbbb aaa

Timers

T

––

––

––

––

600–677 bbbb ––

Data registers

R

––

––

––

––

––

400–577

Constant

K

––

––

––

––

––

0–9999

In the following Or If Greater Than or Equal To example, when input contact 001 is on or T602 w the value 1234 the contact will turn on and output 014 will energize. DirectSOFT Display

Handheld Programmer Keystrokes 014

001

OUT T602

K1234

STR OR SHF

SHF TMR 1

1 SHF 2

ENT 6 3

0 4

OUT

SHF

1

4

ENT

2 ENT

ENT

In the following Or Not If Greater Than example, when input contact 003 is on or T602 the value in R404 the contact will turn on and output 020 will energize. DirectSOFT Display

Handheld Programmer Keystrokes 020

003

OUT T602

R404

STR OR R

SHF NOT 4

3 TMR 0

ENT SHF 4

6 ENT

OUT

SHF

2

0

ENT

0

2

ENT

Page 309

12–15

RLL PLUS Instruction Set Comparative Boolean Instructions

The Or If Greater Than or Equal To instruction connects a normally open comparative counter contact in parallel with another contact. The contact will be on if the specified counter CT aaa w B bbbb.

Or Not If Greater Than Counter (OR NOT CNT) DL330P Only

The Or Not If Greater Than instruction connects a normally closed comparative counter contact in parallel with another contact. The contact will be on if the specified counter CT aaa t B bbbb.

CT aaa

D3–330 Range

B bbbb

B bbbb

D3–340 Range

D3–330P Range

B aaa bbbb aaa bbbb aaa

Counters

CT

––

––

––

––

600–677 bbbb ––

Data registers

R

––

––

––

––

––

400–577

Constant

K

––

––

––

––

––

0–9999

In the following Or If Greater Than or Equal To example, when input contact 007 is on or CT602 w the value in R404 the contact will turn on and output 014 will energize. DirectSOFT Display

Handheld Programmer Keystrokes 014

007

OUT CT602

R404

STR OR R

SHF CNT 4

7 SHF 0

ENT 6 4

0 ENT

OUT

SHF

1

4

ENT

2

ENT

In the following Or Not If Greater Than example, when input contact 003 is on or CT602 t the constant value 4620 the contact will turn on and output 020 will energize. DirectSOFT Display

Handheld Programmer Keystrokes 020

003

OUT CT602

K4620

STR OR SHF

SHF NOT 4

3 CNT 6

ENT SHF 2

6 0

OUT

SHF

2

0

ENT

0 ENT

2

ENT

RLLPLUS Instructions

Operand Data Type

CT aaa

Instruction Set

Or If Greater Than or Equal To Counter (OR CNT) DL330P Only

Page 310

RLLPLUS Instructions

Instruction Set

12–16

RLL PLUS Instruction Set Comparative Boolean Instructions

And If Greater Than or Equal To Timer (AND TMR) DL330P Only

The And If Greater Than or Equal To instruction connects a normally open comparative timer contact in series with another contact. The contact will be on if the specified timer T aaa w B bbbb.

And Not If Greater Than Timer (AND NOT TMR) DL330P Only

The And Not If Greater Than instruction connects a normally closed comparative timer contact in series with another contact. The contact will be on if the specified timer T aaa t B bbbb. Operand Data Type

D3–330 Range

T aaa

B bbbb

T aaa

B bbbb

D3–340 Range

D3–330P Range

B aaa bbbb aaa bbbb aaa

Timers

T

––

––

––

––

600–677 bbbb ––

Data registers

R

––

––

––

––

––

400–577

Constant

K

––

––

––

––

––

0–9999

In the following And If Greater Than or Equal To example, when input contact 001 is on and T602 w the value 1234 the contact will turn on and output 014 will energize. DirectSOFT Display 001

Handheld Programmer Keystrokes T602

K1234

014 OUT

STR AND SHF

SHF TMR 1

1 SHF 2

ENT 6 3

0 4

OUT

SHF

1

4

ENT

2 ENT

ENT

In the following Store Not If Greater Than example, when input contact 003 is on and T602 t the value in R404 the contact will turn on and output 020 will energize. DirectSOFT Display 003

Handheld Programmer Keystrokes T602

R404

020 OUT

STR AND R

SHF NOT 4

3 TMR 0

ENT SHF 4

6 ENT

OUT

SHF

2

0

ENT

0

2

ENT

Page 311

12–17

RLL PLUS Instruction Set Comparative Boolean Instructions

The And If Greater Than or Equal To instruction connects a normally open comparative counter contact in series with another contact. The contact will be on if the specified counter CT aaa w B bbbb.

And Not If Greater Than Counter (AND NOT CNT) DL330P Only

The And Not If Greater Than instruction connects a normally closed comparative counter contact in series with another contact. The contact will be on if the specified counter CT aaa t B bbbb. D3–330 Range

B bbbb

CT aaa

B bbbb

D3–340 Range

D3–330P Range

B aaa bbbb aaa bbbb aaa

Counters

CT

––

––

––

––

600–677 bbbb ––

Data registers

R

––

––

––

––

––

400–577

Constant

K

––

––

––

––

––

0–9999

In the following Or If Greater Than or Equal To example, when input contact 007 is on and CT602 w the value in R404 the contact will turn on and output 014 will energize. DirectSOFT Display 007

Handheld Programmer Keystrokes CT602

R404

014 OUT

STR AND R

SHF CNT 4

7 SHF 0

ENT 6 4

0 ENT

OUT

SHF

1

4

ENT

2

ENT

In the following Or Not If Greater Than example, when input contact 003 is on and CT602 t the constant value 4620 the contact will turn on and output 020 energize. DirectSOFT Display 003

Handheld Programmer Keystrokes CT602

K4620

020 OUT

STR AND SHF

SHF NOT 4

3 CNT 6

ENT SHF 2

6 0

OUT

SHF

2

0

ENT

0 ENT

2

ENT

RLLPLUS Instructions

Operand Data Type

CT aaa

Instruction Set

And If Greater Than or Equal To Counter (AND CNT) DL330P Only

Page 312

12–18

RLL PLUS Instruction Set Timer, Counter, and Shift Register Instructions

RLLPLUS Instructions

Instruction Set

Timer, Counter, and Shift Register Instructions Timer (TMR) DL330P Only

The Timer instruction used in the DL330P CPU provides a single input timer with a 0.1 second increment (0–999.9 seconds) in the normal operating mode, or a 0.01 second increment (0–99.99 seconds) in the fast timer mode with relay 770 on. The timer will time up to the maximum value (999.9 or 99.99) as long as the input logic remains on, once the input logic turns off the timer will reset to 0. There is no timer bit associated with this timer. Comparative boolean instructions must be used to monitor the current value of this timer. Operand Data Type

Time

TMR

D3–330 Range

D3–340 Range aaa aaa aaa

––

––

600–677

T aaa

D3–330P Range

In the following Timer example when input contact 000 is on timer 600 will time up. When input contact 000 goes off the timer will reset to zero. The comparative instruction will monitor the current value of the timer and energize when the current value of the timer is greater than or equal to the constant K30. DirectSOFT Display

Handheld Programmer Keystrokes

000

T600

TMR K30

T600 014 OUT

STR TMR STR SHF

SHF SHF TMR 3

0 6 SHF 0

ENT 0 6 ENT

0 0

OUT

SHF

1

4

ENT

ENT 0

ENT

Timing Diagram

0

1

2

3

4

5

6

7

0

10

20

30

40

50

60

8 seconds

000

014 Current Value

0

1/10 seconds

Page 313

12–19

RLL PLUS Instruction Set Timer, Counter, and Shift Register Instructions

The Counter instruction used in the DL330P CPU provides a single input counter with a counting range of 0–9999. The counter will count up to 9999 and stop. The Reset Counter instruction must be used to reset this counter. There is no counter bit associated with this counter, so comparative boolean instructions must be used to monitor the current value of this counter. Operand Data Type

D3–330 Range

D3–340 Range

D3–330P Range aaa aaa aaa

––

––

600–677

CNT

C aaa

In the following Counter example when input contact 000 transitions from off to on counter 600 will increment by one. When input contact 001 is on the Reset Counter instruction will reset the counter to 0. The comparative instruction will monitor the current value of the counter and energize when the current value of the counter - the constant K2. DirectSOFT Display

Handheld Programmer Keystrokes

000

001

C600

STR CNT STR RST

SHF SHF SHF CNT

0 6 1 SHF

ENT 0 ENT 6

RST

STR SHF

CNT 2

SHF ENT

6

014

OUT

SHF

1

4

ENT

CNT

C600

C600

K2

0

ENT

0

0

ENT

0

2

ENT

OUT

0

1

2

3

4

5

6

7

8

0

014 Current Value RST CT

1

2

3

4

0

RLLPLUS Instructions

Counter

COUNT

Instruction Set

Counter (CNT) DL330P Only

Page 314

Instruction Set

12–20

RLL PLUS Instruction Set Timer, Counter, and Shift Register Instructions

Reset Counter (RST) DL330P Only

The Reset Counter instruction used in the DL330P CPU provides a reset for the counter instruction. One counter or a range of counters can be reset.

Operand Data Type

RLLPLUS Instructions

Counters

Optional memory range C aaa C bbb RST

D3–330 Range

D3–340 Range

D3–330P Range aaa bbbb aaa bbbb aaa bbbb

––

––

––

––

600–677

600–677

In the following Reset Counter example when input contact 001 is on the Reset Counter instruction will reset counter 600. DirectSOFT Display

000

001

Handheld Programmer Keystrokes CNT

C600

C600 RST

STR CNT STR RST

SHF SHF SHF CNT

0 6 1 SHF

ENT 0 ENT 6

0

ENT

0

0

ENT

Page 315

12–21

RLL PLUS Instruction Set Timer, Counter, and Shift Register Instructions

The Shift Register instruction shifts data through a predefined number of control relays. There are 77 control relays which can be used for internal control relays or shift register bits. There is no limit to the number of shift registers which can be used in a program, however the total number of bits used cannot exceed 77. The Shift Register has three input contacts. S Data, determines the value (1 or 0) that will enter the register S Clock, shifts the bits one position on each low to high transition S Reset, resets the Shift Register to all zeros.

DATA

Instruction Set

Shift Register (SR) DL330P Only

SR From aaa

CLOCK To bbb RESET

RLLPLUS Instructions

With each off to on transition of the clock input, the bits which make up the shift register block are shifted by one bit position and the status of the data input is placed into the starting bit position of the shift register. The direction of the shift depends on the entry in the From and To fields. From 160 to 167 would define a shift right block of eight bits to be shifted from bit left to right. From 167 to 160 would define a shift left block of eight bits, but would shift from right to left. The maximum size of the shift register block is limited to 77 bits. There is no minimum block size. Operand Data Type

Shift Register Bits

D3–330 Range

D3–340 Range

D3–330P Range aaa bbbb aaa bbbb aaa bbbb

––

––

––

––

160–174 200–277

160–174 200–277

Page 316

Instruction Set

12–22

RLL PLUS Instruction Set Timer, Counter, and Shift Register Instructions

In the following example, when the clock input transitions from low to high the value in the Data input is placed in the first bit position of the shift register and the successive successive bits are shifted to the right. When the Reset input transitions from low to high the entire shift register is set to zeros. DirectSOFT Display 000

Data Input

001

SR

From

160

To

167

Clock Input

002

RLLPLUS Instructions

Handheld Programmer Keystrokes

Reset Input

Inputs on Successive Scans Data

Clock

Reset

1

1

0

0

1

0

0

1

0

1

1

0

0

1

0

0

0

1

STR STR STR SET SHF

SHF SHF SHF RST 1

0 1 2 SHF 6

6 ENT

0 determines the direction of the shift

Shift Register Bits 160

ENT ENT ENT 1 7

167

ENT