For the GE DL330 / D3-330, Fanuc DL330 / D3-330 and GE Fanuc DL330 / D3-330

Page 27

1–7 Getting Started

Getting Started

DC OUTPUT

RELAY OUTPUT

AC OUTPUT

8pt 5–24 VDC 16pt 5–24 VDC

4 pt 8pt 16pt 16pt

8pt 8pt 8pt 16pt

110–220 VAC 110–220 VAC 12–220VAC 15–220VAC

4A/pt 5A/pt 10A/pt 2A/pt

ANALOG 4ch 8ch 16ch 2ch 4ch 8ch

INPUT INPUT INPUT OUTPUT OUTPUT TEMPERATURE TRANSDUCER INPUT 8ch THERMOCOUPLE INPUT

SPECIALTY CPUs Bridge CPU to connect to host w/OPTOMUX Driver Bridge CPU w/FACTS Extended Basic Programming Bridge CPU to connect to High-speed PAMUX compatible host

SPECIALTY MODULES / UNITS 8pt INPUT Simulator 1pt High Speed Counter PROM Writer Unit Filler Module

NETWORKING RS232C Data Communication Unit RS422 Data Communication Unit MODBUS Slave Module MODBUS Slave Module w/Radio Modem Universal connector: RS232C / RS422/485 Convertor

Page 28

1–8 Getting Started

Getting Started

DirectLOGIC Part Numbering System As you examine this manual, you’ll notice there are many different products available. Sometimes it is difficult to remember the specifications for any given product. However, If you take a few minutes to understand the numbering system, it may save you some time and confusion. The charts below show how the part numbering systems work for each product category. Part numbers for accessory items such as cables, batteries, memory cartridges etc. are typically an abbreviation of the description for the item.

CPUs Specialty CPUs Product family

D4-

440DC

-1

D3-

05B

DC

D4-

16

N

D

2

D3-

16

N

D

2

D2/F2 D3/F3 D4/F4

Class of CPU / Abbreviation

230...,330...,430...

Denotes a differentiation between Similar modules

–1, –2, –3, –4

Bases Product family

D2/F2 D3/F3 D4/F4

Number of slots Type of Base

##B DC or empty

Discrete I/O DL205 Product family

D2/F2

DL305 Product family

D3/F3

DL405 Product family

D4/F4

Number of points

04/08/12/16/32

Input

N

Output

T

Combination AC

C A

DC

D

Either

E

Relay Current Sinking

R 1

Current Sourcing

2

Current Sinking/Sourcing High Current

3 H

Isolation

S

Fast I/O Denotes a differentiation between Similar modules

F –1, –2, –3, –4

F -1

Page 29

1–9 Getting Started

DirectLOGIC Part Numbering System (cont.) F3-

DL205 Product family

D2/F2

DL305 Product family

D3/F3

DL405 Product family

D4/F4

Number of channels

02/04/08/16

Input (Analog to Digital)

AD

Output (Digital to Analog)

DA

Combination Isolated

AND S

Denotes a differentiation between Similar modules

–1, –2, –3, –4

04

AD

S

Getting Started

Analog I/O

-1

Altermate example of Analog I/O using abbreviations F3-

08

THM

Communication and Networking,

D4-

DCM

DCM (Data Communication Module)

Special I/O and Devices

D3-

HSC

HSC (High Speed Counter)

D3-

HPP

HPP (RLL PLUS Handheld Programmer)

F4-

CP

128

Programming DL205 Product family

D2/F2

DL305 Product family

D3/F3

DL405 Product family

D4/F4

Name Abbreviation see example

CoProcessors and ASCII BASIC Modules DL205 Product family

D2/F2

DL305 Product family

D3/F3

DL405 Product family

D4/F4

CoProcessor

CP

ASCII BASIC

AB

64K memory

64

128K memory

128

512K memory Radio modem

512 R

Telephone modem

T

-n note: -n indicates thermocouple type such as: J, K, T, R, S or E

- R

Page 30

1–10 Getting Started

Getting Started

A Few Steps to a Successful System Step1: Review the Installation Guidelines

You should always make safety your first priority in any system application. Chapter 2 provides several guidelines that will help provide a safer, more reliable system. This chapter also includes wiring guidelines for the various system components.

Step 2: Understand the CPU Setup Procedures

The CPU is the heart of your automation system. Make sure you take the time to understand the various features and setup requirements.

Step 3: Understand the I/O System Configurations

It is important to understand how the I/O system can be configured. You have two different types of systems. S Local System S Local Expansion System It is also important to understand how the system Power Budget is calculated. This can affect your I/O placement and/or configuration options.

Step 4: Review the I/O Selection Criteria

There are many considerations involved when you select your I/O modules. Take time to understand how the various types of electrical connections can affect your choice of I/O modules.

Step 5: Determine the I/O Module Specifications and Wiring Characteristics

There are many different I/O modules available with the DL305 system. Chapters 6 and 7 provide the specifications and wiring diagrams for the discrete I/O modules. NOTE: Specialty modules have their own manuals and are not included in this manual

Emergency Stop

030 020 010 000 to to to to 037 027 017 007 130 120 to to 137 127

110 100 to to 117 107

C P U

060 050 040 to to to 067 057 047 160 150 140 to to to 167 157 147

DL305

DL305

Page 31

1–11 Getting Started

Step 7: Review the Programming Concepts

Step 8: Choose the Instructions

Before you begin to enter a program, it is very helpful to understand how the DL305 system processes information. This involves not only program execution steps, but also involves the various modes of operation and memory layout characteristics.

All control systems differ in some areas. The DL305 CPUs offer two different types of programming. RLL programming available for all the DL305 CPUs, uses conventional ladder diagram type solutions for many application problems. RLL PLUS is available for the DL330P CPU. This method of programming greatly reduces the program design time and makes program troubleshooting and machine startup considerably easier. Once you have installed the system and understand the theory of operation, you can choose from a diverse instruction set to implement your application.

Power up

Getting Started

Step 6: Understand the System Operation

Initial Mode Setting

Initialize memory

RLL Programming output 010 input 000

RLL PLUS (flowchart) Programming ISG S0

SG S1

J

TMR

T1 K 30 CNT

CT3 K10

Step 9: Understand the Maintenance and Troubleshooting Procedures

Many things can happen on the factory floor. Switches fail, batteries need to be replaced, etc. In most cases, the majority of the troubleshooting and maintenance time is spent trying to locate the problem. Chapter 13 provides some information that will help you quickly identify problems, so you can look like a hero if you take time to understand them.

Page 32

This page is a scan with no text; see it in the PDF.

Page 33

Installation and Safety Guidelines In This Chapter. . . .

Ċ Safety Guidelines Ċ Panel Design Specifications Ċ Component Dimensions Ċ Base Mounting Dimensions Ċ Installing Components in the Base Ċ I/O Wiring

12

Page 34

2–2 Installation and Safety Guidelines

WARNING: Providing a safe operating environment for personnel and equipment is your responsibility and should be your primary goal during system planning and installation. Automation systems can fail and may result in situations that can cause serious injury to personnel or damage to equipment. Do not rely on the automation system alone to provide a safe operating environment. You should use external electromechanical devices, such as relays or limit switches, that are independent of the PLC system to provide protection for any part of the system that may cause personal injury or damage. Every automation application is different, so there may be special requirements for your particular application. Make sure you follow all National, State, and local government requirements for the proper installation and use of your equipment. Plan for Safety

The best way to provide a safe operating environment is to make personnel and equipment safety part of the planning process. You should examine every aspect of the system to determine which areas are critical to operator or machine safety. If you are not familiar with PLC system installation practices, or your company does not have established installation guidelines, you should obtain additional information from the following sources. • NEMA, The National Electrical Manufacturers Association, located in Washington, D.C., publishes many different documents that discuss standards for industrial control systems. You can order these publications directly from NEMA. Some of these include: ICS 1, General Standards for Industrial Control and Systems ICS 3, Industrial Systems ICS 6, Enclosures for Industrial Control Systems • NEC, The National Electrical Code provides regulations concerning the installation and use of various types of electrical equipment. Copies of the NEC Handbook can often be obtained from your local electrical equipment distributor or your local library. S Local and State Agencies, many local governments and state governments have additional requirements above and beyond those described in the NEC Handbook. Check with your local Electrical Inspector or Fire Marshall office for information.

Safety Techniques

The publications mentioned provide many ideas and requirements for system safety. At a minimum, you should follow these regulations. Also, you should use the following techniques, which may help reduce the risk of safety concerns. • Orderly system shutdown sequence in the PLC control program. • System power disconnects (guard limits, emergency stop switches, etc.)

Installation and Safety Guidelines

Installation and Safety Guidelines

Installation and Safety Guidelines

Safety Guidelines

Page 35

2–3 Installation and Safety Guidelines

Orderly System Shutdown

The first level of protection should be included in the PLC control program, which can be used to identify machine problems. You should analyze your application and identify any shutdown sequences that must be performed. These types of problems are usually things such as jammed parts, etc. that do not pose a risk of personal injury or equipment damage.

Turn off Saw

Jam Detect

System Power Disconnect

RST Retract Arm

Use E-Stop and Master Relay E STOP Guard Limit Switch

Power On

Emergency Stop

Guard Limit

Master Relay

Master Relay Contacts Master Relay Contacts

To disconnect PLC Power

Master Relay Contacts

Output Module

Saw Arbor

To disconnect output module power

After an Emergency shutdown or any other type of power interruption, there may be requirements that must be met before the PLC control program can be restarted. For example, there may be specific register values that must be established (or maintained from the state prior to the shutdown) before operations can resume. In this case, you may want to use retentive memory locations, or include constants in the control program to ensure a known starting point.

Installation and Safety Guidelines

You should also use electromechanical devices, such as master control relays and/or limit switches, to prevent accidental equipment startup at an unexpected time. These devices should be installed in such a manner to prevent any machine operations from occurring. For example, if the machine has a jammed part the PLC control program can turn off the saw blade and retract the arbor. However, since the operator must open the guard to remove the part, you should also include a bypass switch that disconnects all system power any time the guard is opened. You should also provide a quick method of manually disconnecting all system power. This should be accomplished with a mechanical device that is clearly labeled as an Emergency switch.

Installation and Safety Guidelines

RST

WARNING: The control program should not be the only form of protection for any problems that may result in a risk of personal injury or equipment damage.

Page 36

2–4 Installation and Safety Guidelines

Installation and Safety Guidelines

Installation and Safety Guidelines

Installation and Safety Guidelines

Panel Design Specifications It is important to design your panel properly to help ensure the DL305 products operate within their environmental and electrical limits. Proper installation of your DL305 system requires an in-depth understanding of electrical control systems. The system installation should comply with the appropriate electrical codes and standards for your area. It is important that your system also conforms to the operating standards for the application to insure proper performance. The DL305 equipment should only be installed by personnel familiar with electrical/industrial applications. The DL305 installation should provide proper ventilation, spacing, and grounding to ensure the equipment will operate as specified. The diagram on the next page references the items in the following list. 1. The bases should be mounted horizontally to provide proper ventilation. 2. There should be a minimum of 7.2” (183mm) and a maximum of 13.75” (350mm) between bases. 3. A minimum clearance of 2” (50mm) between the base and the top, bottom and right side of the cabinet should be provided. 4. A minimum clearance of 3” (75mm) between the base and the left side of the cabinet should be provided. 5. There must be a minimum of 2” clearance between the panel door and the nearest DL305 component. 6. The ground terminal on the DL305 base must be connected to a single point ground. Copper stranded wire should be used for this connection to achieve a low impedance. Copper eye lugs should be crimped and soldered to the ends of the stranded wire to assure good surface contact. You should also remove anodized finishes and use copper lugs and star washers at termination points. A rule of thumb is to achieve a 0.1 ohm of DC resistance between the DL305 base and the single point of ground. 7. There must be a single point of ground (i.e. copper bus bar) for all devices in the panel requiring an earth ground return. The single point of ground must be connected to the panel ground termination. The panel ground termination must be connected to earth ground. For this connection you should use #12 AWG stranded copper wire as a minimum. Minimum wire sizes, color coding, and general safety practices should comply with appropriate electrical codes and standards for your area. A good common ground reference (Earth ground) is essential for proper operation of the DL305. The DL305 system and components are designed to operate with a common ground reference. There are several methods of providing an adequate common ground reference. These methods include: a) Installing a ground rod as close to the panel as possible. b) Connection to the incoming power system ground. 8. Installations where the ambient temperature may approach the lower or upper limits of the specifications should be evaluated properly. To do this place a temperature probe in the panel, close the door and operate the system until the ambient temperature has stabilized. If the ambient temperature is not within the operating specification for the DL305 system, measures such as installing a cooling/heating source must be taken to get the ambient temperature within the DL305 operating specifications.