Page 37
2–5 Installation and Safety Guidelines
9. Device mounting bolts and ground braid termination bolts should be #10 copper bolts or equivalent. Tapped holes instead of nut–bolt arrangements should be used whenever possible. To assure good contact on termination areas impediments such as paint, coating or corrosion should be removed in the area of contact. 10. The DL305 systems are designed to be powered by 110 VAC , 220 VAC, or 24 VDC normally available throughout an industrial environment. Isolation transformers and noise suppression devices are not normally necessary, but may be helpful in eliminating/reducing suspected power problems.
2" 50mm min.
DL305 CPU Base
Ã
Â
Ç
Â
2" 50mm min.
À
Temperature Probe Power Source
Installation and Safety Guidelines
3" 75mm min.
É 7.2" - 13.75" 183 - 350mm
Installation and Safety Guidelines
DL305 Local Expasion Base
Á
À
2" 50mm min.
Â
Å
BUS Bar
Æ
Ä Earth Ground Note: there is a minimum of 2” (50mm) clearance between the panel door and the nearest DL305 component.
Panel Ground Terminal Panel
Component Chassis
´ Star Washers
Ground Braid Copper Lugs
´ Star Washers
Panel or Single Point Ground
Page 38
2–6 Installation and Safety Guidelines
Environmental Specifications
Environmental Specifications
•
Power Supply Specifications
•
Agency Approvals
S
Enclosure Selection and Component Dimensions
Specification
Rating
Storage temperature –4° F to 158° F (–20° C to 70° C)
Power Installation and Safety Guidelines
•
The following table lists the environmental specifications that generally apply to the DL305 system (CPU, Bases I/O modules). I/O module operation may fluctuate depending on the ambient temperature and your application. Please refer to the appropriate I/O module chapters for the temperature derating curves applying to specific modules.
Installation and Safety Guidelines
Installation and Safety Guidelines
In addition to the panel layout guidelines, there are other specifications that can affect the definition and installation of a PLC system. You should always consider the following areas whenever you install any PLC system.
Ambient operating temperature
32° F to 140° F (0° C to 60° C)
Ambient humidity
5% to 95% relative humidity (non–condensing)
Vibration resistance
MIL STD 810C, Method 514.2
Shock resistance
MIL STD 810C, Method 516.2
Noise immunity
NEMA (ICS3–304) 1 uS width rectangular wave
Atmosphere
No corrosive gases
The power source must be capable of suppling voltage and current complying with the base power supply specifications.
Specifications
D3–05B
D3–05BDC
D3–08B
D3–10B
Input Voltage Range
100–240 VAC +10% / –15% 47–63Hz
20.5–30 VDC <10% ripple
100–240 VAC +10% / –15% 47–63Hz
100–240 VAC +10% / –15% 47–63Hz
Base Power
70 VA max (46W)
48 Watts
70 VA max (57W)
70 VA max (57W)
Inrush Current max.
30A
30A
30A
30A
Dielectric Strength
1500VAC for 1 minute between terminals of AC P/S, Run output, Common, 24VDC
1500VAC for 1 minute between 24VDC input terminals and Run output
1500VAC for 1 minute between terminals of AC P/S, Run output, Common, 24VDC
2000VAC for 1 minute between terminals of AC P/S, Run output, Common, 24VDC
Insulation Resistance
>10MW at 500VDC
>10MW at 500VDC
>10MW at 500VDC
>10MW at 500VDC
Power Supply Output (Voltage Ranges and Ripple)
(5VDC) 4.75–5.25V less than 0.1V p–p
(5VDC) 4.75–5.25V less than 0.1V p–p
(5VDC) 4.75–5.25V less than 0.1V p–p
(5VDC) 4.75–5.25V less than 0.1V p–p
(9VDC) 8.5–13.5V less than 0.2 V p–p
(9VDC) 8.5–13.5V less than 0.2 V p–p
(9VDC) 8.0–12.0V less than 0.2 V p–p
(9VDC) 8.0–12.0V less than 0.2 V p–p
(24VDC) 20–28V less than 1.2V p–p
(24VDC) 20–28V less than 1.2V p–p
(24VDC) 20–28V less than 1.2V p–p
(24VDC) 20–28V less than 1.2V p–p
Consumption
Page 39
2–7 Installation and Safety Guidelines
Some applications require agency approvals. Typical agency approvals which your application may require are: • UL (Underwriters’ Laboratories, Inc.) • CSA (Canadian Standards Association) • FM (Factory Mutual Research Corporation) S CUL (Canadian Underwriters’ Laboratories, Inc.)
Enclosures
Your selection of a proper enclosure is important to ensure safe and proper operation of your DL305 system. Applications of DL305 systems vary and may require additional features. The minimum considerations for enclosures include: • Conformance to electrical standards • Protection from the elements in an industrial environment • Common ground reference • Maintenance of specified ambient temperature • Access to equipment • Security or restricted access S Sufficient space for proper installation and maintenance of equipment
Before installing your PLC system you will need to know the dimensions for the components in your system. The diagrams on the following pages provide the component dimensions and should be used to define your enclosure specifications. Remember to leave room for potential expansion. Appendix D provides the weights for each component.
Installation and Safety Guidelines
Component Dimensions
Installation and Safety Guidelines
Agency Approvals
Page 40
2–8 Installation and Safety Guidelines
11.41” 290mm
5 slot base
.94” 24mm
10.63” 270mm
Handheld Programer on side view of Base
3.54” 90mm
4.84” 123mm
4.41” 112mm 15.55” 395mm
8 slot base
5.35” 136mm
Installation and Safety Guidelines
14.76” 375mm
3.54” 90mm
4.84” 123mm
18.30” 465mm
10 slot base
17.51” 445mm
3.54” 90mm
Installation and Safety Guidelines
Installation and Safety Guidelines
4.84” 123mm
Handheld programmer cable
I/O Expander cable
4.92’ 1.5m
1.6’ 0.5m 1.15” 29.9 mm
1.37” 34.8mm
Handheld programmer
CPU
4.33” 110mm
3.86” 96mm
4.67” 118.6mm
4.65” 118mm
.94” 24mm
Page 41
2–9 Installation and Safety Guidelines
Component Dimensions Part 2 1.37” 34.8mm
4.65”/118nn – 8 I/O Pts 4.86”/123mm – 16 I/O Pts
I/O modules
3.86” 98mm
4.67” 118.6mm
Installation and Safety Guidelines
.55” 14mm
I/O module w/24 pin connector 1.37” 34.8mm
24 pin connector
3.86” 98mm
2.00” 51mm
4.84” 123mm
1.85” 47mm 0.51” 13mm
0.4” 10.3mm
Data communication units (Prom Writer Unit has the same dimensions) 4.33” 110mm
4.65” 118mm
1.5” 38mm
Installation and Safety Guidelines
2.06” 52.4mm
Page 42
2–10 Installation and Safety Guidelines
Base Mounting Dimensions Below are the mounting dimensions which should be used when mounting DL305 bases. Make sure you have followed the installation guidelines for proper spacing. 5 slot base
11.41” 290mm
.94” 24mm
10.63” 270mm
Handheld Programer on side view of Base 3.54” 90mm
Installation and Safety Guidelines
Installation and Safety Guidelines
Installation and Safety Guidelines
4.84” 123mm
8 slot base
4.41” 112mm 5.35” 136mm
15.55” 395mm 14.76” 375mm
3.54” 90mm
4.84” 123mm
18.30” 465mm
10 slot base
17.51” 445mm
3.54” 90mm
4.84” 123mm
Installing Components in the Base When inserting components into the base, align the PC board(s) of the module with the grooves on the top and bottom of the base. Push the module straight into the base until it is firmly seated in the backplane connector.
Align module to slots in base and slide in
Page 43
2–11 Installation and Safety Guidelines
Base Wiring
The following diagram shows the terminal connections located on the power supply of the DL305 bases. WARNING: Damage will occur to the base power supply if 220 VAC is connected to the 115 VAC terminal connections. Once the power wiring is connected, install the protective cover. When the cover is removed there is a risk of electrical shock if you accidentally touch the connection terminals. 24 VDC Terminal Strip
110/220 VAC Terminal Strip
Installation and Safety Guidelines
Line Neutral
This is an example of how to connect power when using local CPU and Expansion bases. 110VAC Line
220VAC
24VDC + –
Neutral
110VAC
220VAC
24VDC + –
Local CPU
Local CPU
Local CPU
110VAC
220VAC
24VDC + –
Expansion Base 1
Expansion Base 1
Expansion Base 1
110VAC
220VAC
24VDC + –
Expansion Base 2
Expansion Base 2
Expansion Base 2
Installation and Safety Guidelines
Expansion Base Wiring
Page 44
2–12 Installation and Safety Guidelines
I/O Wiring This information provides a general idea on how to wire the different types of modules in the DL305 system. For specific information on wiring a particular module refer to the specification sheet in the appropriate I/O chapter or manual.
Installation and Safety Guidelines
Installation and Safety Guidelines
Installation and Safety Guidelines
I/O Wiring Guidelines
You should consider these guidelines when wiring your system. 1. There is a limit to the size of wire the modules can accept. The table below lists the maximum AWG for each module type. Smaller AWG is acceptable to use for each of the modules. Module type
Maximum AWG
8 point
12
16 point
16
2. Always use a continuous length of wire, do not combine wires to attain a needed length. 3. Use the shortest possible cable length. 4. Use wire trays for routing where possible 5. Avoid running wires near high energy wiring. 6. Avoid running input wiring in close proximity to output wiring where possible. 7. To minimize voltage drops when wires must run a long distance , consider using multiple wires for the return line. 8. Avoid running DC wiring in close proximity to AC wiring where possible. 9. Avoid creating sharp bends in the wires.
Page 45
2–13 Installation and Safety Guidelines
Wiring the Different There are three main types of module faces for the DL305 I/O. These module faces are: lift covers over terminal blocks, flip covers over terminal blocks and D–shell Module Types compatible sockets. If the module you are using has a cover you can remove the cover either by lifting from the bottom or by flipping the door open. Some of the modules have removable terminal blocks. These modules can be recognized by the squeeze tabs on the top and bottom of the terminal block. To remove the terminal block, press the squeeze tabs and pull the terminal block away from the module. WARNING: For some modules, field device power may still be present on the terminal block even though the PLC system is turned off. To minimize the risk of electrical shock, check all field device power before you remove the connector.
D–shell Connector
Removable Cover
Removable Terminal Block
Installation and Safety Guidelines
Squeeze Tab
Installation and Safety Guidelines
Squeeze Tab