Page 37

2–5 Installation and Safety Guidelines

9. Device mounting bolts and ground braid termination bolts should be #10 copper bolts or equivalent. Tapped holes instead of nut–bolt arrangements should be used whenever possible. To assure good contact on termination areas impediments such as paint, coating or corrosion should be removed in the area of contact. 10. The DL305 systems are designed to be powered by 110 VAC , 220 VAC, or 24 VDC normally available throughout an industrial environment. Isolation transformers and noise suppression devices are not normally necessary, but may be helpful in eliminating/reducing suspected power problems.

2" 50mm min.

DL305 CPU Base

Ã

Â

Ç

Â

2" 50mm min.

À

Temperature Probe Power Source

Installation and Safety Guidelines

3" 75mm min.

É 7.2" - 13.75" 183 - 350mm

Installation and Safety Guidelines

DL305 Local Expasion Base

Á

À

2" 50mm min.

Â

Å

BUS Bar

Æ

Ä Earth Ground Note: there is a minimum of 2” (50mm) clearance between the panel door and the nearest DL305 component.

Panel Ground Terminal Panel

Component Chassis

´ Star Washers

Ground Braid Copper Lugs

´ Star Washers

Panel or Single Point Ground

Page 38

2–6 Installation and Safety Guidelines

Environmental Specifications

Environmental Specifications

•

Power Supply Specifications

•

Agency Approvals

S

Enclosure Selection and Component Dimensions

Specification

Rating

Storage temperature –4° F to 158° F (–20° C to 70° C)

Power Installation and Safety Guidelines

•

The following table lists the environmental specifications that generally apply to the DL305 system (CPU, Bases I/O modules). I/O module operation may fluctuate depending on the ambient temperature and your application. Please refer to the appropriate I/O module chapters for the temperature derating curves applying to specific modules.

Installation and Safety Guidelines

Installation and Safety Guidelines

In addition to the panel layout guidelines, there are other specifications that can affect the definition and installation of a PLC system. You should always consider the following areas whenever you install any PLC system.

Ambient operating temperature

32° F to 140° F (0° C to 60° C)

Ambient humidity

5% to 95% relative humidity (non–condensing)

Vibration resistance

MIL STD 810C, Method 514.2

Shock resistance

MIL STD 810C, Method 516.2

Noise immunity

NEMA (ICS3–304) 1 uS width rectangular wave

Atmosphere

No corrosive gases

The power source must be capable of suppling voltage and current complying with the base power supply specifications.

Specifications

D3–05B

D3–05BDC

D3–08B

D3–10B

Input Voltage Range

100–240 VAC +10% / –15% 47–63Hz

20.5–30 VDC <10% ripple

100–240 VAC +10% / –15% 47–63Hz

100–240 VAC +10% / –15% 47–63Hz

Base Power

70 VA max (46W)

48 Watts

70 VA max (57W)

70 VA max (57W)

Inrush Current max.

30A

30A

30A

30A

Dielectric Strength

1500VAC for 1 minute between terminals of AC P/S, Run output, Common, 24VDC

1500VAC for 1 minute between 24VDC input terminals and Run output

1500VAC for 1 minute between terminals of AC P/S, Run output, Common, 24VDC

2000VAC for 1 minute between terminals of AC P/S, Run output, Common, 24VDC

Insulation Resistance

>10MW at 500VDC

>10MW at 500VDC

>10MW at 500VDC

>10MW at 500VDC

Power Supply Output (Voltage Ranges and Ripple)

(5VDC) 4.75–5.25V less than 0.1V p–p

(5VDC) 4.75–5.25V less than 0.1V p–p

(5VDC) 4.75–5.25V less than 0.1V p–p

(5VDC) 4.75–5.25V less than 0.1V p–p

(9VDC) 8.5–13.5V less than 0.2 V p–p

(9VDC) 8.5–13.5V less than 0.2 V p–p

(9VDC) 8.0–12.0V less than 0.2 V p–p

(9VDC) 8.0–12.0V less than 0.2 V p–p

(24VDC) 20–28V less than 1.2V p–p

(24VDC) 20–28V less than 1.2V p–p

(24VDC) 20–28V less than 1.2V p–p

(24VDC) 20–28V less than 1.2V p–p

Consumption

Page 39

2–7 Installation and Safety Guidelines

Some applications require agency approvals. Typical agency approvals which your application may require are: • UL (Underwriters’ Laboratories, Inc.) • CSA (Canadian Standards Association) • FM (Factory Mutual Research Corporation) S CUL (Canadian Underwriters’ Laboratories, Inc.)

Enclosures

Your selection of a proper enclosure is important to ensure safe and proper operation of your DL305 system. Applications of DL305 systems vary and may require additional features. The minimum considerations for enclosures include: • Conformance to electrical standards • Protection from the elements in an industrial environment • Common ground reference • Maintenance of specified ambient temperature • Access to equipment • Security or restricted access S Sufficient space for proper installation and maintenance of equipment

Before installing your PLC system you will need to know the dimensions for the components in your system. The diagrams on the following pages provide the component dimensions and should be used to define your enclosure specifications. Remember to leave room for potential expansion. Appendix D provides the weights for each component.

Installation and Safety Guidelines

Component Dimensions

Installation and Safety Guidelines

Agency Approvals

Page 40

2–8 Installation and Safety Guidelines

11.41” 290mm

5 slot base

.94” 24mm

10.63” 270mm

Handheld Programer on side view of Base

3.54” 90mm

4.84” 123mm

4.41” 112mm 15.55” 395mm

8 slot base

5.35” 136mm

Installation and Safety Guidelines

14.76” 375mm

3.54” 90mm

4.84” 123mm

18.30” 465mm

10 slot base

17.51” 445mm

3.54” 90mm

Installation and Safety Guidelines

Installation and Safety Guidelines

4.84” 123mm

Handheld programmer cable

I/O Expander cable

4.92’ 1.5m

1.6’ 0.5m 1.15” 29.9 mm

1.37” 34.8mm

Handheld programmer

CPU

4.33” 110mm

3.86” 96mm

4.67” 118.6mm

4.65” 118mm

.94” 24mm

Page 41

2–9 Installation and Safety Guidelines

Component Dimensions Part 2 1.37” 34.8mm

4.65”/118nn – 8 I/O Pts 4.86”/123mm – 16 I/O Pts

I/O modules

3.86” 98mm

4.67” 118.6mm

Installation and Safety Guidelines

.55” 14mm

I/O module w/24 pin connector 1.37” 34.8mm

24 pin connector

3.86” 98mm

2.00” 51mm

4.84” 123mm

1.85” 47mm 0.51” 13mm

0.4” 10.3mm

Data communication units (Prom Writer Unit has the same dimensions) 4.33” 110mm

4.65” 118mm

1.5” 38mm

Installation and Safety Guidelines

2.06” 52.4mm

Page 42

2–10 Installation and Safety Guidelines

Base Mounting Dimensions Below are the mounting dimensions which should be used when mounting DL305 bases. Make sure you have followed the installation guidelines for proper spacing. 5 slot base

11.41” 290mm

.94” 24mm

10.63” 270mm

Handheld Programer on side view of Base 3.54” 90mm

Installation and Safety Guidelines

Installation and Safety Guidelines

Installation and Safety Guidelines

4.84” 123mm

8 slot base

4.41” 112mm 5.35” 136mm

15.55” 395mm 14.76” 375mm

3.54” 90mm

4.84” 123mm

18.30” 465mm

10 slot base

17.51” 445mm

3.54” 90mm

4.84” 123mm

Installing Components in the Base When inserting components into the base, align the PC board(s) of the module with the grooves on the top and bottom of the base. Push the module straight into the base until it is firmly seated in the backplane connector.

Align module to slots in base and slide in

Page 43

2–11 Installation and Safety Guidelines

Base Wiring

The following diagram shows the terminal connections located on the power supply of the DL305 bases. WARNING: Damage will occur to the base power supply if 220 VAC is connected to the 115 VAC terminal connections. Once the power wiring is connected, install the protective cover. When the cover is removed there is a risk of electrical shock if you accidentally touch the connection terminals. 24 VDC Terminal Strip

110/220 VAC Terminal Strip

Installation and Safety Guidelines

Line Neutral

This is an example of how to connect power when using local CPU and Expansion bases. 110VAC Line

220VAC

24VDC + –

Neutral

110VAC

220VAC

24VDC + –

Local CPU

Local CPU

Local CPU

110VAC

220VAC

24VDC + –

Expansion Base 1

Expansion Base 1

Expansion Base 1

110VAC

220VAC

24VDC + –

Expansion Base 2

Expansion Base 2

Expansion Base 2

Installation and Safety Guidelines

Expansion Base Wiring

Page 44

2–12 Installation and Safety Guidelines

I/O Wiring This information provides a general idea on how to wire the different types of modules in the DL305 system. For specific information on wiring a particular module refer to the specification sheet in the appropriate I/O chapter or manual.

Installation and Safety Guidelines

Installation and Safety Guidelines

Installation and Safety Guidelines

I/O Wiring Guidelines

You should consider these guidelines when wiring your system. 1. There is a limit to the size of wire the modules can accept. The table below lists the maximum AWG for each module type. Smaller AWG is acceptable to use for each of the modules. Module type

Maximum AWG

8 point

12

16 point

16

2. Always use a continuous length of wire, do not combine wires to attain a needed length. 3. Use the shortest possible cable length. 4. Use wire trays for routing where possible 5. Avoid running wires near high energy wiring. 6. Avoid running input wiring in close proximity to output wiring where possible. 7. To minimize voltage drops when wires must run a long distance , consider using multiple wires for the return line. 8. Avoid running DC wiring in close proximity to AC wiring where possible. 9. Avoid creating sharp bends in the wires.

Page 45

2–13 Installation and Safety Guidelines

Wiring the Different There are three main types of module faces for the DL305 I/O. These module faces are: lift covers over terminal blocks, flip covers over terminal blocks and D–shell Module Types compatible sockets. If the module you are using has a cover you can remove the cover either by lifting from the bottom or by flipping the door open. Some of the modules have removable terminal blocks. These modules can be recognized by the squeeze tabs on the top and bottom of the terminal block. To remove the terminal block, press the squeeze tabs and pull the terminal block away from the module. WARNING: For some modules, field device power may still be present on the terminal block even though the PLC system is turned off. To minimize the risk of electrical shock, check all field device power before you remove the connector.

D–shell Connector

Removable Cover

Removable Terminal Block

Installation and Safety Guidelines

Squeeze Tab

Installation and Safety Guidelines

Squeeze Tab

Page 46