For the Signet 8550
Page 1
English
Signet 8550-3 Flow Transmitter *3-8550.090-3* 3-8550.090-3 Rev. M 09/12 English
WARNING! • Remove power to unit before wiring input and output connections. • Follow instructions carefully to avoid personal injury.
Contents 1. Specifications 2. Installation 3. Electrical Connections
Flow1: Flow2:
4. Menu Functions 5. Troubleshooting 6. Ordering Information
6.25 GPM 9.75 GPM
Signet Flow Transmitter ENTER
1. Specifications Dimensions
Optional Rear Cover
96 mm (3.8 in.)
96 mm (3.8 in.)
FRONT VIEW Field Mount & Panel Mount
41 mm (1.6 in.)
92 mm (3.6 in.)
56 mm (2.2 in.)
SIDE VIEW Panel Mount
Enclosure: • Case: Panel case gasket: • Window: • Keypad: • Weight:
PBT Neoprene Polyurethane coated polycarbonate Sealed 4-key silicone rubber Approx. 325 g (12 oz.)
Display: • Alphanumeric • Update rate: • Contrast: • Accuracy: • Thermal sensitivity shift:
2 x 16 LCD 1 second User selected, 5 levels ± 0.5% of reading @ 25 ºC ± 0.005% of reading per ºC
Sensor Inputs: • Range: • Sensor power:
106 mm (4.18 in.)
96 mm (3.8 in.)
102 mm (4.0 in.)
97 mm (3.8 in.)
General Compatibility: Signet Flow Sensors (w/freq out)
Electrical • Power:
82 mm (3.23 in.)
12 to 24 VDC ±10%, regulated, 100 mA max.
0.5 to 1500 Hz 2-wire: 0.5 mA @ 5 VDC ± 1% 3- or 4-wire: 20 mA @ 5 VDC ± 1% • Optically isolated from current loop, short circuit protected Current output: • 4 to 20 mA, isolated, fully adjustable and reversible • Max loop impedance: 50 Ω max. @ 12 V 325 Ω max. @ 18 V 600 Ω max. @ 24 V • Update rate: 100 ms • Accuracy: ± 0.03 mA
SIDE VIEW
SIDE VIEW
Field Mount w/ 8050 Universal base
Field Mount w/ 8051 Integral kit
Open-collector outputs, optically isolated: • 50 mA max. sink, 30 VDC maximum pull-up voltage. • Programmable for: • High or Low setpoint with adjustable hysteresis • Pulse proportional to rate or volume (max 300 pulses/min). Environmental • Operating temperature: • Storage temperature: • Relative humidity: • Maximum altitude: • Insulation category: • Pollution degree: • Rating:
-10 to 70 °C (14 to 158 °F) -15 to 80 °C (5 to 176 °F) 0 to 95%, non-condensing 2000 m (6562 ft) II 2 NEMA 4X/IP65 front
Standards and Approvals: • CE, UL listed • Manufactured under ISO 9001 for Quality, ISO 14001 for Environmental Management and OHSAS 18001 for occupational health and safety. China RoHS (Go to www.gfsignet.com for details) Declaration of Conformity according to FCC Part 15 This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and, (2) This device must accept any interference received, including interference that may cause undesired operation.
2. Installation ProcessPro transmitters are available in two styles: panel mount and field mount. The panel mount is supplied with the necessary hardware to install the transmitter. This manual includes complete panel mounting instructions. Field mounting requires one of two separate mounting kits. The 3-8051 Integral Mounting Kit joins the sensor and instrument together into a single package. The 3-8050 Universal Mounting Kit enables the transmitter to be installed virtually anywhere. Detailed instructions for integral mounting or other field installation options are included with the 3-8051 Integral Mounting Kit or the 3-8050 Universal Mounting Kit (see Ordering Information).
Page 2
2.1 Panel Installation panel gasket
1. The panel mount transmitter is designed for installation using a 1/4 DIN Punch. For manual panel cutout, an adhesive template is provided as an installation guide. Recommended clearance on all sides between instruments is 1 inch. 2. Place gasket on instrument, and install in panel. 3. Slide mounting bracket over back of instrument until quick-clips snap into latches on side of instrument. 4. To remove, secure instrument temporarily with tape from front or grip from rear of instrument. DO NOT RELEASE. Press quick-clips outward and remove.
terminals latch mounting bracket sr Gnd SenIELD)
7 (SH System -
2 Loop
System p+
Pwr
4
Output
-
3 sr IN SenD) sr V+ SenACK)
6 (RE 5 (BL
Pwr
1 Loo
Output
+
Panel Mount Installation Detail quick-clips
3. Electrical Connections Caution: Failure to fully open terminal jaws before removing wire may permanently damage instrument. 2
Wiring Procedure 1. Remove 0.5 - 0.625 in. (13-16 mm) of insulation from wire end. 2. Press the orange terminal lever downward with a small screwdriver to open terminal jaws. 3. Insert exposed (non-insulated) wire end in terminal hole until it bottoms out. 4. Release orange terminal lever to secure wire in place. Gently pull on each wire to ensure a good connection.
1
Wiring Removal Procedure 1. Press the orange terminal lever downward with a small screwdriver to open terminal jaws. 2. When fully open, remove wire from terminal.
Terminals 3-6: System Power and Loop Power 12-24 VDC ±10% system power and current loop outputs. Max. loop impedance: 50 Ω max. @ 12 V 325 Ω max. @ 18 V 600 Ω max. @ 24 V
Terminals 11-16: Flow sensor inputs
6
Loop 2-
5
Loop 2+
4
System Pwr Loop 1 -
9
3
System Pwr + Loop 1 +
8
2
AUX Power -
1
AUX Power +
Terminals 1 and 2: AUXILIARY power Used only if the flow sensor requires more than 1.5 mA current. For Signet sensors this is limited to the following products: • 2000 • 2507 • 2551 • 2552 • Open-collector Input signals
10
7
16
Snsr 2 Gnd (WHITE)
15
Snsr 2 IN (RED)
Output 2+
14
Snsr 2 V+ (BLACK)
Output 1-
13
Snsr 1 Gnd (WHITE)
12
Snsr 1 IN (RED)
11
Snsr 1 V+ (BLACK)
Output 2-
Output 1+
Internal open-collector output circuit 15Ÿ S
Isolation
D
Outputs 1 2 _ +
Terminals 7-10: Open-collector Outputs Two transistor outputs, programmable (see CALIBRATE menu) as: • High or Low setpoint with adjustable hysteresis. • Pulse based on Volume. • Frequency based on flow rate. May be disabled (Off) if not used. 2
Signet 8550-3 Flow Transmitter
Page 3
3.1 System Power/Loop Connections Stand-alone application, no current loop used Transmitter Terminals Loop 2 –
6
NC
Loop 2 +
5
NC
System Power/Loop 1 –
4
System Power/Loop 1 +
3
AUX Power –
2
AUX Power +
1
Connection to a PLC/Recorder, separate supply
– +
Power Supply 12-24 VDC
Connection to a PLC with built-in power supply
PLC or Recorder Transmitter Terminals Loop 2 –
6
Loop 2 +
5
System Power/Loop 1 –
4
System Power/Loop 1 +
3
AUX Power –
2
AUX Power +
+ –
1
Transmitter Terminals
Channel 2 4-20 mA
– +
Channel 1 4-20 mA
– +
Power Supply 12-24 VDC
Loop 2 –
6
Loop 2 +
5
System Power/Loop 1 –
4
System Power/Loop 1 +
3
AUX Power –
2
AUX Power +
1
PLC Terminals
+ –
Channel 2 4-20 mA
+ –
Channel 1 4-20 mA
– +
Power Supply 12-24 VDC
Internal PLC Connection
Example: Two transmitters connected to PLC/Recorder with separate power supply PLC or Recorder
+ – + – + – Transmitter 1 Terminals
+ –
Channel 1 4-20 mA in Channel 2 4-20 mA in Channel 3 4-20 mA in Channel 4 4-20 mA in
Transmitter 2 Terminals
Loop 2 –
6
6
Loop 2 –
Loop 2 +
5
5
Loop 2 +
System Power/Loop 1 –
4
4
System Power/Loop 1 –
System Power/Loop 1 +
3
3
System Power/Loop 1 +
AUX Power –
2
2
AUX Power –
AUX Power +
1
1
AUX Power +
– +
Power Supply 12-24 VDC
Auxiliary Power Note: Auxiliary power is necessary for flow sensors that require more than 1.5 mA of current. This includes the following Signet flow sensors: 2000, 2507, 2551, 2552 and all Open Collector signal inputs.
3.2 Sensor Input Connections Wiring Tips: • Do not route sensor cable in conduit containing AC power wiring. Electrical noise may interfere with sensor signal. • Routing sensor cable in grounded metal conduit will help prevent electrical noise and mechanical damage. • Seal cable entry points to prevent moisture damage. • Only one wire should be inserted into a terminal. Splice double wires outside the terminal. Terminals Aux Power Required
No Aux Power
2000 2507 2551 2552 Open-collector input signals
515/3-8510-XX 525 2100 2536/3-8512-XX 2540/2541
Signet 8550-3 Flow Transmitter Instructions
16
Snsr 2 Gnd (SHIELD)
2 IN 15 Snsr (RED) 2 V+ 14 Snsr (BLACK)
13
Snsr 1 Gnd (SHIELD)
Maximum cable length is 60 m (200 ft.) for 515/8510-XX, 525 and any sinusoidal flow signal. Flow
B
Flow1: Flow2:
6.25 GPM 9.75 GPM
A
ENTER
A ” 200 ft. (60 m) B ” 200 ft. (60 m)
Maximum cable length is 305 m (1000 ft). for 2536/8512-XX, 2540/2541 and any open-collector flow signal. 8550 3 Flow
B
Flow1: Flow2:
6.25 GPM 9.75 GPM
A
ENTER
1 IN 12 Snsr (RED) 1 V+ 11 Snsr (BLACK)
A ” 1000 ft. (300 m) B ” 1000 ft. (300 m) 3
Page 4
3.3 Open Collector Output The Open collector output can be used as a switch that responds when the flow rate moves above or below a setpoint, or it can be used to generate a pulse that is relative to the flow volume or to the flow rate. • Low Output energizes when the flow rate is less than the setpoint. The output will de-energize when the flow rate moves above the setpoint plus the hysteresis value.
Process
Hysteresis
Low Setpoint Time
Relay energized Relay de-energized
• High Output energizes when the flow rate is greater than the setpoint. The output will de-energize when the flow rate drops below the setpoint plus the hysteresis value. • Frequency Output is a pulse stream that is based on the input flow sensor signal. Set for 1 (input frequency = output frequency). Set for even numbers (2, 4, 6, 8, . . . . 254 maximum) to scale output frequency.
Process
High Setpoint
Hysteresis
• Pulse Output is a pulse based on the volume of fluid that passes the sensor. Set any value from 0.0001 to 99999.
Time
The output may be disabled (Off) if not used.
4. Menu Functions VIEW menu • During normal operation, ProcessPro displays the VIEW menu. • When editing the CALIBRATE or OPTIONS menus, ProcessPro will return to the VIEW menu if no activity occurs for 10 minutes. • To select a VIEW display, press the ▲ or ▼ arrow keys. The selections will scroll in a continuous loop. • Changing the VIEW display does not interrupt system operations. • No key code is necessary to change display selection. • Output settings cannot be edited from the VIEW menu.
Flow1: Flow2:
6.25 GPM 9.75 GPM
Signet Flow Transmitter ENTER
View Menu Display
Flow1: 123.4 GPM Flow2: 567.8 GPM Delta Flow: 10.5 GPM
Description Monitor the flow rate of Channel 1 and Channel 2 simultaneously. This is the permanent view display. Monitor the delta flow rate (Channel 1 rate - channel 2 rate = Delta Flow) This is a permanent display.
All of the displays below are temporary. After 10 minutes the display returns to the permanent display.
Tot1: 1234567.8 Tot2: 123456.78
Monitor channel 1 and channel 2 Resettable Totalizers. Press the ► key to reset the totalizer. If Reset is locked, you must enter Key Code. Lock or Unlock function is in OPTIONS menu
Perm1: 1234567.8 Gallons
Monitor channel 1 Permanent Totalizer value.
Perm2: 123456.78 Gallons
Monitor channel 2 Permanent Totalizer value.
Loop 1 Output: 12.00 mA Loop 2 Output: 12.00 mA
Monitor the 4 to 20 mA output for Loop 1 and 2.
Last CAL: 02-10-09 4
Monitor date for scheduled maintenance or date of last calibration. (See description in Calibrate Menu.) Signet 8550-3 Flow Transmitter
Page 5
ProcessPro Editing Procedure: Step 1. Press and hold ENTER key: • 2 seconds to select the CALIBRATE menu. • 5 seconds to select the OPTIONS menu.
Step 2. The Key Code is ▲-▲-▲-▼ keys in sequence. • After entering the Key Code, the display will show the first item in the selected menu.
Step 3. Scroll menu with ▲ or ▼ arrow keys. Step 4. Press ► key to select menu item to be edited. • The first display element will begin flashing.
Step 5. Press ▲ or ▼ keys to edit the flashing element. • ► key advances the flashing element.
Step 6. Press ENTER key to save the new setting and return to Step 3.
Notes on Step 1: • The View Menu is normally displayed. • The CALIBRATE and OPTIONS menus require a KEY CODE. Press & hold for access:
Notes on Step 2: If no key is pressed for 5 minutes while display is showing "Enter Key Code", the display will return to the VIEW menu. CALIBRATE: ---Enter Key Code
ENTER
CALIBRATE: *--Enter Key Code VIEW
2s
5s
CALIBRATE: **-Enter Key Code CALIBRATE: ***Enter Key Code
CALIBRATE
OPTIONS
Notes on Steps 3 and 4: • Refer to pages 6 and 7 for complete listing of menu items and their use. • From the Step 3 display, pressing the ▲ and ▼ keys simultaneously will return the display to the VIEW menu. • If no key is pressed for 10 minutes, display will also return to the VIEW menu.
First item in CALIBRATE menu
Flow1 Units: GPM >
Flow1 Units: GPM >
Step 3
Step 3: Finished Editing? Press the ▲ and ▼ keys simultaneously after saving the last setting to return to normal operation.
Step 4
Output1 Setpnt: 20.0 GPM >
Notes on Steps 5 and 6: Output1 Setpnt: 20.00 GPM • All output functions remain active during editing. • Only the flashing element can be edited. Output1 Setpnt: Step 5 10.00 GPM • ► key advances the flashing element in a continuous loop. • Edited value is effective immediately after pressing ENTER key. • If no key is pressed for 10 minutes unit will restore the last saved value and return to step 3. Output1 Setpnt: • Step 6 (pressing ENTER key) always returns you to Step 3. 10.00 GPM • Repeat steps 3-6 until all editing is completed.
Step 5: Made an Error? Press the ▲ and ▼ keys simultaneously while any element is flashing. This will recall the last saved value of the item being edited and return you to Step 3.
Signet 8550-3 Flow Transmitter Instructions
Output1 Setpnt: 1 .00 GPM
9
Step 6
ENTER
Output1 Setpnt:
Saving
Output1 Setpnt: 19.00 GPM > 5
Page 6
Calibrate Menu
Display (Factory settings shown)
Flow1 Units: GPM
Description
>
The first three characters set the Flow Rate units of measure and have no effect on calculations. They may be any character, upper or lower case. The last character sets the Flow rate Timebase. Select S (seconds), M (minutes), H (hours) or D (days)
Flow1 K-Factor: 60.000
This setting converts the input frequency from the flow sensor into a flow rate. The K-Factor is unique to the sensor model and to the pipe size and schedule. Refer to data in the sensor manual for the correct value. Limits: 0.0001 to 99999. (The K-factor cannot be set to 0.)
Total1 Units: Gallons
This setting identifies the Totalizer units. It has no effect on any calculation. It serves as a label only. Each character can be any alpha or numeric selection, upper or lower case.
Total1 K-Factor 60.000
>
This setting converts the input frequency from the flow sensor into a volumetric total. It also is used as the basis for the Open Collector pulse mode. The setting is usually the same as the Flow K-Factor, or different by x10 or x100. Limits: 0.0001 to 99999. (Cannot be set to 0.)
Loop1 Source: Flow1
>
Select the input source to be associated with Loop output #1: Flow sensor #1, Flow sensor #2, or Delta Flow.
Loop1 Range: GPM 000.00 → 100.00
>
Select the minimum and maximum values for the Current loop output #1. The 8550 will allow any values from 0.0000 to 99999
Output1 Source: Flow1
>
Select the desired mode of operation for the Open Collector output. Options available are Flow sensor #1, Flow sensor #2, or Delta Flow.
Output1 Mode: Low
>
Select the desired mode of operation for the Open Collector output #1. Options available are High, Low, volumetric Pulse, or Frequency. The signal may be disabled (Off) if not used.
Output1 Setpnt: 10.0 GPM
>
In Low or High Mode, the Open Collector output #1 will be activated when the Flow rate reaches this value. Be sure to modify this setting if you change the Flow Units.
Output1 Hys: 5.0 GPM
>
The Open Collector output will be deactivated at Setpoint ± Hysteresis, depending on High or Low Setpoint selection. (See details on page 4.)
Output1 Volume: 100.00 Gallons
>
In Pulse mode, the Open collector output #1 will generate one pulse when this volume of flow passes the sensor. The measurement is based on the Total K-Factor. The 8550 will allow any value from 0.0001 to 99999.
Output PlsWdth: 0.1 Seconds
>
In Pulse mode, this setting defines the duration of the Open Collector output pulse. The 8550 allows any value from 0.1 seconds to 999.9 seconds.
Output1 Freq.: Divide by 1 >
In Frequency mode, the Open Collector output will simulate the sensor frequency, divided by this setting. Set for 1 (input frequency = output frequency). Set for even numbers (2, 4, 6, 8 . . . 254 max) to scale output frequency.
Last CAL: 2-10-09
Use this “note pad” to record important dates, such as annual recertification or scheduled maintenance.
All functions labeled "1" will repeat for channel 2.
6
Signet 8550-3 Flow Transmitter
Page 7
Options Menu
Display (Factory settings shown)
Description
Contrast: 3
>
Adjust the LCD contrast for best viewing. A setting of 1 is lowest contrast, 5 is highest. Select lower contrast if the display is in warmer ambient surroundings.
Flow1 Decimal *****.
>
Set the decimal to the best resolution for your application. The display will automatically scale up to this resolution. Select *****., ****.*, ***.**, **.*** or *.****
Total1 Decimal ******.**
>
Set the totalizer decimal to the best resolution for your application. Select ********., *******.*, or ******.**
Averaging 1: Off
>
OFF provides the quickest output response to changes in flow. Longer averaging period produces more stable display and output response. Select OFF, 8 s, 20 s, 50 s or 120 s.
Sensitivity 1: 0
>
Sensitivity works in conjunction with Averaging to balance response time with signal stability. Selections are 0 to 9. Select 0 (zero) for the minimum sensitivity, or 9 for the maximum sensitivity. The function is described below.
Total Reset Lock Off
>
Lock Off : No key code required to reset the resettable totalizer. Lock On : The Key Code must be entered to reset the resettable totalizer.
Loop1 Adjust 4.00 mA
>
Loop1 Adjust 20.00 mA
>
Adjust the minimum and maximum current output. Use this setting to match the system output to any external device. The display value represents the precise current output. Adjustment limits: • 3.80 mA < 4.00 mA > 5.00 mA • 19.00 mA < 20.00 mA > 21.00 mA
Output1 Active Low
>
Active HIGH: This setting is used to turn a device (pump, valve) ON at the setpoint. Active LOW: This setting is used to turn a device OFF at the setpoint.
>
Press ▲ or ▼ keys to manually order any output current value from 3.6 mA to 21.00 mA to test current loop output.
Test Loop1: Test Output 1: >
Press ▲ or ▼ keys to manually toggle the state of open collector output.
All functions labeled "1" will repeat for channel 2.
No AVERAGING, no SENSITIVITY With AVERAGING set to 0 (zero) and with SENSITIVITY set to zero, the 8550 responds to every unstable shift in the flow. The dashed red line represents the actual output of the flow sensor in unstable flow conditions.
AVERAGING only With AVERAGING set to 50 seconds and SENSITIVITY still set to zero the flow rate is stabilized, but a sharp change in flow rate is not represented for 50 seconds or longer (dotted green line).
AVERAGING and SENSITIVITY With AVERAGING at 50 seconds and SENSITIVITY set to 4 OR 5, the flow rate is stabilized, while the sudden shift in flow is reflected very quickly (solid blue line).
Signet 8550-3 Flow Transmitter Instructions
2s
10 s
20 s
30 s
40 s
50 s
60 s
70 s
NOTE: The SENSITIVITY function is ineffective if the AVERAGING function is set to zero (seconds).
7
Page 8
5. Troubleshooting Display Condition
Possible Causes
Suggested Solutions
Flow rate exceeds display capability
• Increase Flow units time base • Move flow decimal one place to the right
• Open Collector pulse rate exceeds maximum of 300 pulses per minute. • Pulse width set too wide.
• Increase Pulse volume setting • Decrease pulse width setting. • Reduce system flow rate
Value must be more than 0
K-Factors cannot be set to 0.
Enter K-Factor from 0.0001 to 99999
Open Collector is always activated
• Hysteresis value too large • Defective transmitter
• Change the hysteresis value • Replace transmitter
-
-
-
-
-
Pulse Overrun
6. Ordering Information Mfr. Part No.
Code
Description
3-8550-1 3-8550-1P 3-8550-2 3-8550-2P 3-8550-3 3-8550-3P
159 000 047 159 000 048 159 000 049 159 000 050 159 000 051 159 000 052
Flow transmitter, Field mount Flow transmitter, Panel mount Flow transmitter, Field mount with relays Flow transmitter, Panel mount with relays Flow transmitter, Field mount with dual input/output Flow transmitter, Panel mount with dual input/output
Accessories Mfr. Part No.
Code
Description
3-0000.596 3-5000.598 3-5000.399 3-8050 3-8050.390-1 3-8050.390-3 3-8050.390-4 3-8050.391 3-8050.395 3-8050.396 3-8051 3-8051-1 3-8051-2 3-9000.392 3-9000.392-1 3-9000.392-2 7300-7524 7300-1524 7300-3024 7300-5024 7300-1024
159 000 641 198 840 225 198 840 224 159 000 184 159 001 702 159 310 116 159 310 117 159 001 703 159 000 186 159 000 617 159 000 187 159 001 755 159 001 756 159 000 368 159 000 839 159 000 841 159 000 687 159 000 688 159 000 689 159 000 690 159 000 691
Heavy duty wall mount bracket Surface Mount Bracket 5 x 5 inch adapter plate for Signet retrofit Universal mounting kit Retaining Nut Replacement Kit, NPT, Valox® Retaining Nut Replacement Kit, NPT, PP Retaining Nut Replacement Kit, NPT, PVDF Retaining Nut Replacement Kit, NPT, Stainless Steel Splashproof rear cover RC Filter kit (for relay use) Flow Sensor Integral Mounting Kit, NPT, Valox Flow Sensor Integral Mounting Kit, NPT, PP Flow Sensor Integral Mounting Kit, NPT, PVDF Liquid tight connector kit for rear cover (includes 3 connectors) Liquid tight connector kit, NPT (1 piece) Liquid tight connector kit, PG13.5 (1 piece) 24 VDC Power Supply 7.5 W, 300mA 24 VDC Power Supply 15 W, 600mA 24 VDC Power Supply 30 W, 1.3 A 24 VDC Power Supply 50 W, 2.1 A 24 VDC Power Supply 100 W, 4.2 A
Georg Fischer Signet LLC, 3401 Aero Jet Avenue, El Monte, CA 91731-2882 U.S.A. • Tel. (626) 571-2770 • Fax (626) 573-2057 For Worldwide Sales and Service, visit our website: www.gfsignet.com • Or call (in the U.S.): (800) 854-4090 For the most up-to-date information, please refer to our website at www.gfsignet.com 3-8550.090-3 Rev. M 09/12 English
© Georg Fischer Signet LLC 2012