Page 91

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller Appendix C - Troubleshooting

In the example on the previous page, Parameter 54 was viewed, which displayed Motor Load. The “77” in the example indicates that the load on the motor is 77% of the output current rating of the drive controller. The table below lists the fault conditions that cause the drive controller to shut down, as well as some possible causes. Please contact your local Square D sales representative for more information on troubleshooting faults. Table 13: Fault Messages Fault

Description

Possible Causes

AF

High Temperature fault

Ambient temperature too high. Fan failure (if equipped).

CF

Control fault

A blank EPM, or an EPM with corrupted Use Parameter 48 to reset to factory data has been installed. defaults or OEM defaults (if present).

EF

External fault

TB-13A and/or TB-13C is set as an Refer to Parameter 10. External Fault input and TB-13A and/or TB-13C is open with respect to TB-4.

GF

Data fault

User data and OEM defaults in the EPM 1. Obtain new EPM from OEM or are corrupted. 2. Reset to factory defaults instead of OEM defaults.

HF

High DC Bus Voltage fault

High line voltage.

Operating altitude.

Overhauling load. Deceleration rate set too fast.

Corrective Action Check motor load, fan, and ambient temperature at the drive controller. Wait for the drive controller to cool down before resetting. Derate for operating altitude.

Check input line voltage. Check Parameter (01) - Line Voltage for proper voltage selection. Add braking option, if necessary. Increase deceleration rate.

LF

Low DC Bus Voltage Low line voltage. fault

Adjust line voltage.

OF

Output fault

Bad output transistor. Boost settings are too high.

Remove all power. With drive controller disconnected, check connecting cables and motor insulation. Replace output transistor. Adjust boost settings.

Drive may be undersized. Problem with driven equipment.

Verify that drive is sized properly for motor load. Inspect motor

PF

Current Overload fault

Phase to phase or phase to ground short.

© 1998 Square D All Rights Reserved

87

Page 92

VSD07 Adjustable Speed Drive Controller Appendix C - Troubleshooting

Bulletin No. 30072-450-07 November 1998

Table 13: Fault Messages (continued) Fault

Description cF

Compatibility fault

SF

Single phasing fault One phase of three-phase input is not present.

UF

Start fault

Start command was present when drive Must wait 2 seconds after power-up to controller was powered up. apply Start command if Start Method is set to Normal.

F1

EPM fault

The EPM module is missing, damaged, Install, replace, or reseat the EPM or improperly seated. module.

F2–F9, Internal faults Fo

Possible Causes

Corrective Action

EPM programed for another drive and is Verify EPM is installed in correct drive. not compatible with this drive.

Control board has sensed a problem.

Verify input voltage at L1, L2, L3.

Consult factory.

dF

Dynamic Brake fault DB overloaded.

1. Increase decel time or 2. Remove overhauling load.

JF

Remote (Serial) fault Loss of communication with remote keypad or other serial device.

1. Reconnect serial device or 2. Reduce time between status updates on remote serial device or 3. Reduce cabling cross talk/noise.

To clear a fault, stop the controller, either on the terminal strip, or by using the Stop button on the optional remote keypad. The fault only clears if the condition that caused the fault has passed. For example, if the controller trips on a Low DC Bus Voltage Fault (LF) due to low input voltage, the fault cannot be cleared until the input voltage returns to a normal level. The following faults can be cleared by Stop or by Auto Restart: • • • • • • • • •

88

AF (temperature) dF (dynamic braking) EF (external fault) HF (high bus voltage) JF (communications fault) LF (low bus voltage) OF (output transistor fault) PF (overload fault) SF (single-phasing fault)

© 1998 Square D All Rights Reserved

Page 93

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller Appendix D - Bus Voltage Measurement Procedure

Start Fault (UF) cannot occur with Auto Restart, so only Stop will clear it. The following faults can be cleared by powering down the controller and replacing the EPM with the correct one, or by resetting the controller to factory default parameters and then asserting Stop to clear the fault: • CF (control fault) • cF (incompatibility fault) • GF (data fault) F2 to F9 and F0 (internal faults) can only be cleared by powering down the drive controller and powering it back up. In the case of F1 (EPM fault), the faulty EPM module must also be replaced or repositioned while the drive controller is powered down. If the drive controller is programmed for Auto Restart (Parameter 03), the drive controller automatically attempts to restart three times after a fault. If all three restart attempts are unsuccessful, the drive controller trips into Fault Lockout (LC), which requires a manual reset as described above. APPENDIX D - BUS VOLTAGE MEASUREMENT PROCEDURE

DANGER HAZARDOUS VOLTAGE • This equipment contains energy storage devices. Read and understand the Bus Voltage Measurement Procedure before performing procedure. Measurement of DC bus capacitor voltage must be performed by qualified personnel. • The display is not an accurate indication of the absence of DC bus voltage. • DO NOT short across capacitors or touch unshielded components or terminal strip screw connections with voltage present. • Many parts in this drive controller, including printed wiring boards, operate at line voltage. DO NOT TOUCH. Use only electrically insulated tools. Electrical shock will result in death or serious injury. © 1998 Square D All Rights Reserved

89

Page 94

VSD07 Adjustable Speed Drive Controller Appendix D - Bus Voltage Measurement Procedure

Bulletin No. 30072-450-07 November 1998

To measure the bus capacitor voltage: 1. Disconnect and verify that all power is removed from drive controller. 2. Wait 3 minutes to allow the DC bus to discharge. 3. Set the voltmeter to the 1000 Vdc scale. Measure the voltage between the terminals B- and B+ (see Figure 18) to verify that the DC voltage is less than 45 V. Do not short across capacitor terminals with voltage present! 4. If the bus capacitors are not fully discharged, contact your local Square D representative. Do not operate the drive controller.

T1

T2

T3

B-

B+

- + 3-Phase AC Motor

DC Bus Voltage

Figure 18: DC Bus Voltage Measurement Terminals

90

© 1998 Square D All Rights Reserved

Page 95

Bulletin No. 30072-450-07 November 1998

A acceleration boost 46, 65, 79 time 46, 58, 59, 72 address 67 AF (high temperature) 87 altitude ratings 4 analog 0–10 Vdc inputs 51, 69 0–10 Vdc outputs 23, 53, 71 4–20 mA inputs 51, 70 circuit common 19 output specifications 5 speed potentiometer 20 auto restart 49, 50, 88

B base frequency 46, 64, 77 boost 46, 64, 65, 79 br (DC braking) 85 brake DC 49, 50, 58, 60, 61, 72–77 dynamic 45, 88 branch circuit 13 bus voltage 89

C cable 14 carrier frequency 45, 48 cF (compatibility fault) 88 CF (control fault) 87 CL (current limit) 85 clear fault history 67 clearance 9 coast 50 conduits 12 contactors 19, 20

© 1998 Square D All Rights Reserved

VSD07 Adjustable Speed Drive Controller Index control fault 87 pad 85 source 46 start/stop 26–31, 57 terminal strip 25 voltage 5 wiring 19–33 CP (control pad) 85 current limit 46, 62, 77, 85 overload 87 specifications 5 speed source 85

D data fault 87 DC brake 49, 50, 58 status 85 time 46, 60, 72 voltage 46, 61, 76 DC bus fault 87 measuring voltage 89 terminals 90 voltage 47, 69 deceleration 51 override 85 time 46, 58, 60, 72 defaults 45 DF (dynamic brake fault) 88 digital outputs 5, 24 dimensions 6, 7 display drive status 85 error 85 messages 82 speed 83 speed source 85 drive status 24, 85 dynamic brake 45, 88

E EF (external fault) 87 efficiency 5 EI (external current source) 85 enclosure calculating 8–11 ratings 4 EPM error 85 faults 87, 88 location 37 programming 39, 43 Er (invalid data) 85 errors 85 EU (external volt. source) 85

F F1 (EPM fault) 88 F2–F9 88 faults 87 fault history 47, 67, 69 lockout 85 programming outputs 52 fixed boost 64, 79 frequency 46 base 46, 64, 77 carrier 45, 48 maximum 46, 62, 76 minimum 46, 61 scaling 46, 66, 80 specifications 5 fuse ratings 3

91

Page 96

VSD07 Adjustable Speed Drive Controller Index

G

L

GE (error message) 85 GF (data fault) 85, 87 grounding 15, 16, 18

LC (fault lockout) 85 LF (low DC bus voltage) 87 line contactor 19 line voltage 37, 48 load motor 69 scaling 46, 66, 80 lockout 85

H HF (high DC bus voltage) 87 holding torque 60 horsepower ratings 3 humidity rating 4

I inputs 0–10 Vdc analog 51, 69 4–20 mA analog 51, 70 faults 87 specifications 5 speed reference 20, 54–56 inspection 2 installation 8 internal fault 88

J JF (serial fault) 88 JG (jog) 85 jog 22

M max. frequency 46, 62, 76 messages 85 min. frequency 46, 61 motor load 66, 69 overheating 34 overload 46, 63, 77 overspeed 35 protection 5 ratings 3 rotation 58 thermal overload 33 voltage 47, 69 motor operated potentiometer

23 mounting 6–11

K

N keypad 57 changing speed 51, 58 speed 46 status 70

NEMA Type 12 (IP54) 8, 11

92

O OEM settings 68 OF (output fault) 87 OP (motor operated potentiometer) 85 open collector 24, 52, 57

Bulletin No. 30072-450-07 November 1998 outputs 0–10 Vdc analog 23 analog 53, 71 drive status 24 fault 87 open collector 24, 52, 57 specifications 5 wiring 14 overheating 33, 34 overload current 87 motor 46, 63, 77 thermal 33, 34 overspeed 35

P P1–P7 display 85 parameters 41, 45 resetting 68 selecting range 58 settings 72–81 password 39, 46, 67 PF (current overload) 87 phases fault 88 specifications 5 pollution rating 4 potentiometer as speed source 85 power 12 Vdc supply 24 15 Vdc supply 19 factor 5 input wiring 17 output wiring 18 ratings 3 power up 36, 37, 38, 49

© 1998 Square D All Rights Reserved

Page 97

Bulletin No. 30072-450-07 November 1998 preset speeds 22, 46, 65 control wiring 32 display 85 programming 39–71

R ramp 51 range selecting 58 ratings electrical 3, 5 environmental 4 relays external 24 specifications 5 surge suppression 20 restarting 37, 49, 50, 88 rotation 46, 58 run 52

S scaling 46 frequency 66, 80 load 46, 66, 80 serial address 46, 67 fault 88 link 46, 57 service factor 5 setpoint 23, 58, 82 settings OEM 68 resetting 68 selecting 67 user 67 SF (single phasing fault) 88 shipping 2 slip compensation 46, 65, 79 software version 47, 69 © 1998 Square D All Rights Reserved

VSD07 Adjustable Speed Drive Controller Index

SP (start pending) 85 specifications 4 speed changing 51 display 83 overspeed 35 potentiometer 32 preset 32, 46, 65 reference 5, 20, 54–56 setpoint 23, 58, 82 source 21, 45, 51, 85 start/stop 52, 57 faults 87, 88 precautions 36 selecting type 45, 49–51 wiring 26–31 startup 36–38, 49 storing 2 surge suppression 20 switching frequency 5

T TB-4 19 temperature 4, 87 terminal strip 25, 57, 70 terminals 0–10 Vdc analog 53 0–10 Vdc inputs 21, 69 0–10 Vdc outputs 23 12 Vdc supply 24 15 Vdc supply 19 4–20 mA inputs 21, 70 common 19 DC bus 90 ground 18 jog 22 open collector 24, 52, 57 speed reference 21, 54–56 thermal overload 33 torque 35 for control wiring 19 for power terminals 18 holding torque 60 transient current 5 troubleshooting 86

U UF (start fault) 88 user settings 67

V ventilation 9, 11 vibration 4 voltage 12 Vdc supply 24 15 Vdc supply 19 DC brake 46, 61, 76 DC bus 47, 69, 89 fault 87 line 37 motor 47, 69 precautions 36 ratings 3 selecting 48 specifications 5 speed source 85

W wiring 2-wire 26, 28 3-wire 30 branch circuits 13 control 19–33 general practices 12 grounding 15 inputs 17 outputs 14, 18 93

Page 98

VSD07 Adjustable Speed Drive Controller Index

DESCRIPTION OF PARAMETERS 01 - Line Voltage Selection . . . . . . . . . . . . 48 02 - Carrier Frequency . . . . . . . . . . . . . . . 48 03 - Start Method . . . . . . . . . . . . . . . . . . . 49 04 - Stop Method . . . . . . . . . . . . . . . . . . . 50 05 - Standard Speed Source . . . . . . . . . . 51 06 - TB-14 Open Collector Output . . . . . . 52 08 - TB-30 Analog Output . . . . . . . . . . . . . 53 09 - TB-31 Analog Output . . . . . . . . . . . . . 53 10 - TB-13A Function Select . . . . . . . . . . . 54 11 - TB-13B Function Select . . . . . . . . . . . 55 12 - TB-13C Function Select . . . . . . . . . . 56 13 - TB-15 Open Collector Output . . . . . . 57 14 - Control . . . . . . . . . . . . . . . . . . . . . . . . 57 15 - Serial Link . . . . . . . . . . . . . . . . . . . . . 57 16 - Keypad Speed Editing . . . . . . . . . . . . 58 17 - Rotation Direction . . . . . . . . . . . . . . . 58 18 - Range Selector . . . . . . . . . . . . . . . . . 58 19 - Acceleration Time . . . . . . . . . . . . . . . 59 20 - Deceleration Time . . . . . . . . . . . . . . . 60 21 - DC Brake Time . . . . . . . . . . . . . . . . . 60 22 - DC Brake Voltage . . . . . . . . . . . . . . . 61 23 - Minimum Frequency . . . . . . . . . . . . . 61 24 - Maximum Frequency . . . . . . . . . . . . . 62 25 - Current Limit . . . . . . . . . . . . . . . . . . . 62 26 - Motor Overload . . . . . . . . . . . . . . . . . 63 27 - Base Frequency . . . . . . . . . . . . . . . . 64 28 - Fixed Boost . . . . . . . . . . . . . . . . . . . . 64 29 - Acceleration Boost . . . . . . . . . . . . . . . 65 30 - Slip Compensation . . . . . . . . . . . . . . 65 31-37 - Preset Speed #1 to #7 . . . . . . . . . 65 43 - Serial Address . . . . . . . . . . . . . . . . . . 67 44 - Password . . . . . . . . . . . . . . . . . . . . . . 67 47 - Clear Fault History . . . . . . . . . . . . . . . 67

94

Bulletin No. 30072-450-07 November 1998

48 - Program Selection . . . . . . . . . . . . . . . 67 50 - Fault History . . . . . . . . . . . . . . . . . . . . 69 51 - Software Version . . . . . . . . . . . . . . . . 69 52 - DC Bus Voltage . . . . . . . . . . . . . . . . . 69 53 - Motor Voltage . . . . . . . . . . . . . . . . . . . 69 54 - Motor Load . . . . . . . . . . . . . . . . . . . . . 69 55 - 0 to 10 Vdc Analog Input . . . . . . . . . . 69 56 - 4 to 20 mA Analog Input . . . . . . . . . . 70 57 - Terminal Strip Status . . . . . . . . . . . . . 70 58 - Keypad And Protection Status . . . . . . 70 59 - TB-30 Analog Output . . . . . . . . . . . . . 71 60 - TB-31 Analog Output . . . . . . . . . . . . . 71

APPENDIX A PARAMETER VALUE TABLES . . . . . . . . . 72 APPENDIX B DISPLAY MESSAGES . . . . . . . . . . . . . . . 82 APPENDIX C TROUBLESHOOTING . . . . . . . . . . . . . . . . 86 APPENDIX D BUS VOLTAGE MEASUREMENT PROCEDURE . . . . . . . . . . . . . . . . . . . . . . 89

© 1998 Square D All Rights Reserved

Page 99

This page is a scan with no text; see it in the PDF.

Page 100

Square D and

Square D Company 8001 Highway 64 East Knightdale, NC 27545 USA (919) 266-3671 www.squared.com are registered trademarks of Square D Company.

Electrical equipment should be serviced only by qualified electrical maintenance personnel. No responsibility is assumed by Square D for any consequences arising out of the use of this material. Bulletin No. 30072-450-07 November 1998 © 1998 Square D All Rights Reserved.