VSD07 Adjustable Speed Drive Controller Installation and Operation Manual
Manual100 pagesPDF 470 KB
Installation and operation manual for the Square D VSD07 adjustable speed drive controllers for three-phase asynchronous motors.
Covers · 1 model
The models it covers
Summary
What is in it
The Square D instruction bulletin for the VSD07 series of adjustable speed drive controllers, which run three-phase asynchronous motors from 0.25 to 5 hp. It gives ratings, specifications and dimensions, enclosure sizing and ventilation, power and control wiring with diagrams (two-wire, three-wire, preset speeds, 0-10 Vdc and 4-20 mA speed references), motor overload protection, first power up, programming with the keypad and Electronic Programming Module, and a description of every parameter. Appendices cover display messages and troubleshooting.
Its parts
- Introduction
- Handling the Drive Controller
- Technical Characteristics
- Dimensions
- Installation
- General Wiring Practices
- Power Wiring Diagrams
- Control Wiring
- Control Wiring Diagrams
- Motor Thermal Overload Protection
- Available Torque
- Initial Power Up and Motor Rotation
- Programming the Drive Controller
- Parameter Menu
- Description of Parameters
From the manual
Key facts from this manual
Each line names its page in the PDF.
Instruction bulletin 30072-450-07 (November 1998) for the Square D VSD07 Adjustable Speed Drive Controller, a series of drives for three-phase asynchronous motors from 0.25 to 5 hp. It covers ratings and specifications, installation, power and control wiring, programming through the parameter menu, display messages and troubleshooting by fault code.
- Device
- Adjustable speed drive controller for three-phase asynchronous motors p. 5
- Ratings
- 0.25 to 1 hp at 120/208/240 Vac single-phase input; 0.25 to 3 hp at 208/240 Vac three-phase; 0.5 to 3 hp at 400/480 Vac three-phase; 1 to 5 hp at 590 Vac three-phase p. 5
- Fault codes
- AF high temperature, CF control, EF external, GF data, HF high DC bus voltage, LF low DC bus voltage, OF output, PF current overload, cF compatibility, SF single phasing, UF start, F1 EPM, F2 to F9 and Fo internal, dF dynamic brake, JF remote (serial) p. 91, 92
- Inputs
- 5 logic inputs (TB1, TB12, TB-13A, TB-13B, TB-13C) at 15 Vdc; speed reference 0 to 10 Vdc or 4 to 20 mA p. 9
- Outputs
- Analog 0 to 10 Vdc or 2 to 10 Vdc, proportional to frequency or motor load; open-collector outputs rated 50 mA at 30 Vdc p. 9
- Serial port
- RS-485 serial communications on the control terminal strip p. 29
- Output frequency
- 0 to 120 Hz, sine coded pulse width modulation, 3 phases p. 9
- Transient current
- 150% of nominal current for 60 s or 180% for 32 s, set by the line voltage setting p. 9
- Switching frequency
- Adjustable: 4, 6, 8 or 10 kHz, with derating at 6 kHz and above p. 9
- Motor protection
- Built-in I2t calculation, Class 10 p. 9
- Program module
- Removable Electronic Programming Module (EPM) holds user and OEM settings; the drive will not run without it p. 47
- Environment
- IP20; up to 3,300 ft (1,000 m) without derating; storage -20 to +70 °C (-4 to +158 °F) p. 6, 8
- Control wiring
- Belden 8760 (2-wire) or 8770 (3-wire) or equivalent; 16 AWG maximum at control terminals p. 23
- Efficiency
- 98%; power factor (displacement) 0.96; service factor 1.00 p. 9
What this manual walks you through
- Receiving, inspecting and storing the drive controller p. 6
- Ratings, input currents and fuse sizes for each catalog number p. 7, 8
- Separating and wiring control circuits p. 23
- Connecting a speed potentiometer p. 24
- Control terminal strip layout p. 29
- Moving the EPM to a replacement drive p. 47
- Reading speed source displays and status messages p. 89
- Viewing diagnostic parameters 50 to 60 p. 90
- Troubleshooting and clearing faults p. 91, 92
Good to know
- After disconnecting power, wait three minutes and measure the DC bus to confirm it is below 45 V; the display is not a reliable indication. p. 2
- There are no serviceable parts inside; the cover must not be removed. p. 2
- In Jog mode the Stop command does not stop the drive; the contact between TB-13B and TB-4 must be opened. p. 29
- A line contactor should switch less than once every two minutes, or filter capacitors and precharge parts may fail early. p. 23
- Never remove or install the EPM with power applied; wait three minutes after removing power. p. 47
Questions this manual answers
What does fault F1 mean on a Square D VSD07?
The EPM module is missing, damaged or improperly seated; install, replace or reseat it. p. 92
What does LC on the VSD07 display mean?
Fault lockout: the drive failed three restart attempts and needs a manual reset. p. 89
How do I replace a VSD07 without reprogramming it?
Move the Electronic Programming Module from the old drive to the new one; the new drive is then ready to run with the same settings. p. 47
How do I clear a fault on the VSD07?
Stop the drive from the terminal strip or with the Stop button on the optional remote keypad; the fault clears only once its cause has passed. p. 92
What horsepower range does the VSD07 series cover?
From 0.25 hp up to 5 hp, depending on the input voltage version. p. 5
Contents
Chapters and sections
Each line opens the PDF at its page.
- DANGER2
- Calculating Enclosure Size 93
- Ventilation 113
- 0–10 Vdc and 4–20 mA Input Signals 224
- Preset Speeds 224
- Jog 224
- Introduction5
- Scope of Manual5
- Revision Level5
- Handling the Drive Controller6
- Receiving and Preliminary Inspection6
- Storing and Shipping6
- Technical Characteristics7
- Dimensions10
- Installation12
- Installation Precautions12
- Calculating Enclosure Size13
- Ventilation15
- General Wiring Practices16
- Branch Circuit Connections17
- Output Wiring Precautions18
- Grounding19
- Wiring for Single-Phase or Three-Phase Input20
- POWER WIRING DIAGRAMS21
- Equipment Ground Terminal22
- Using a Line Contactor23
- Control Wiring23
- Control Wiring vs. Power Wiring23
- TB-2: Circuit Common23
- TB-4: P 15 Vdc23
- Surge Suppression24
- Start/Stop Control24
- Speed Reference Signals24
- Three-Wire Start/Stop Control34
- 20 - Deceleration Time64
- 21 - DC Brake Time64
- 22 - DC Brake Voltage65
- 23 - Minimum Frequency65
- 24 - Maximum Frequency66
- 25 - Current Limit66
31 more lines, from page 67 on
- 26 - Motor Overload67
- 27 - Base Frequency68
- 28 - Fixed Boost68
- 29 - Acceleration Boost69
- 30 - Slip Compensation69
- 31 to 37 - Preset Speed 1 to 769
- 40 - Frequency Scaling70
- 41 - Load Scaling (Motor Load)70
- 43 - Serial Address71
- 44 - Password71
- 47 - Clear Fault History71
- 48 - Program Selection71
- 50 - Fault History73
- 51 - Software Version73
- 52 - DC Bus Voltage73
- 53 - Motor Voltage73
- 54 - Motor Load73
- 55 - 0 to 10 Vdc Analog Input73
- 56 - 4 to 20 mA Analog Input74
- 57 - Terminal Strip Status74
- 58 - Keypad And Protection Status74
- 59 - TB-30 Analog Output75
- 60 - TB-31 Analog Output75
- Appendix A - Parameter Value Tables76
- Appendix B - Display Messages86
- Speed Setpoint Display Stop State86
- Speed Display in a Run State87
- Speed Display When the Speed is 100 Hz or Greater88
- Speed Source Displays and Status Messages89
- Appendix C - Troubleshooting90
- Appendix D - Bus Voltage Measurement Procedure93