Page 41

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller Initial Power Up and Motor Rotation

WARNING DRIVE CONTROLLER DAMAGE • Drive controller will be damaged if input line voltage is applied to output terminals (T1, T2, T3). Check power connections before energizing the drive controller. • Do not continuously cycle input power to the drive controller more than once every two minutes. Damage to the drive controller will occur. Failure to follow these instructions can result in death, serious injury, or equipment damage.

NOTE: Before applying power, ensure that the EPM module is present and properly seated. See Figure 17 for the location of the EPM module.

EPM Module

Figure 17: EPM Module © 1998 Square D All Rights Reserved

37

Page 42

VSD07 Adjustable Speed Drive Controller Initial Power Up and Motor Rotation

Bulletin No. 30072-450-07 November 1998

To power up the drive controller: 1. Disconnect the driven load from the motor. Verify that the drive controller input terminals (L1, L2, and L3) are wired to the proper input voltage per the nameplate rating of the drive controller. 2. Energize the incoming power line. The LED display flashes a two digit number (“03” in the example below) that identifies the parameter set contained in the drive controller. The display then indicates “--”. The drive controller is now disabled as shown below: Apply input power. Display flashes parameter set value (00-99). Display then indicates “--”.

Review all parameters to ensure that they are applicable to a given drive controller application. However, the following four key parameters must be checked and adjusted, if necessary, prior to motor operation: • • • •

38

Line Voltage Motor Overload Control Type Rotation

© 1998 Square D All Rights Reserved

Page 43

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller Programming the Drive

PROGRAMMING THE DRIVE CONTROLLER The drive controller is programmed by one of three methods: 1. Using the three buttons and 2-digit LED display on the front of the drive controller. 2. Programming the Electronic Programming Module (EPM) using the optional Portable Programming Fixture. 3. Using serial communications through a serial link. This section describes programming the drive controller using the buttons and display, which are shown below:

Buttons

Display

Mode

Entering the Password To access the parameters, enter the Program mode by pressing the Mode button. This activates the Password prompt. The display reads “00” and the right-hand decimal point blinks, as shown below:

Press Mode. Display indicates “00”. Right decimal point blinks.

© 1998 Square D All Rights Reserved

39

Page 44

VSD07 Adjustable Speed Drive Controller Programming the Drive

Bulletin No. 30072-450-07 November 1998

Next enter the four-digit password. Since the display is only two digits, this requires two steps. Press ▲ to scroll to the first 2 digits of password value. Default password is 1225. Press Mode to enter first two digits.

Once the Mode button is pressed, the display changes to “00” and the right-hand decimal point blinks more rapidly. This indicates that the last two digits of the password must now be entered. Right decimal point blinks faster. Press ▲ to scroll to last 2 digits of password value. Press Mode to enter first two digits.

When the Mode button is pressed, the right-hand decimal point stays on instead of blinking, and “01” is displayed. This indicates that the Program mode is accessed at the beginning of the parameter menu (01 is the first parameter). If the display flashes “Er”, the password was incorrect. Repeat the process to enter the password. The password is stored in Parameter 44. You must change this parameter to change the password. See “44 - Password” on page 67. When you have changed the password, be sure to record and keep track of the password.

40

© 1998 Square D All Rights Reserved

Page 45

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller Programming the Drive

Setting the Parameters Once the Program mode is accessed, use the ▲ and ▼ buttons to scroll to the desired parameter number. Right decimal point stays on instead of blinking. Use ▲ and ▼ to scroll to the desired parameter number (i.e., 19 - Acceleration Time).

Press Mode to display the parameter setting, a 2-digit code (see Table 6 on page 72). Right decimal point blinks.

Use the ▲ and ▼ buttons to scroll to a new value.

Use ▲ and ▼ to scroll to the new parameter value from the table. Press Mode to store new value.

Press the Mode button to store the new setting and exit the Program mode. To re-enter the Program mode, press the Mode button again within two minutes, otherwise you must re-enter the password.

© 1998 Square D All Rights Reserved

41

Page 46

VSD07 Adjustable Speed Drive Controller Programming the Drive

Bulletin No. 30072-450-07 November 1998

Programming Direct-Entry Parameters Most of the parameters are programmed by entering the codes defined in Appendix A. The Minimum Frequency, Preset Speeds, and the Password (Parameters 23, 31–37, 44), however, are programmed by directly entering the value. The procedure is similar to entering the Password. The parameter value is four digits, but the display is two digits, so the value must be entered in two parts. For example, to enter a preset speed of 32.5 Hz, first enter “03”, then “25”. In the display below, the Mode button has already been pressed to display the first two digits of the present setting, and the right-hand decimal point is blinking: Use ▲ and ▼ to scroll to the first 2 digits of the new parameter value. Press Mode to store the first two digits.

Once the Mode button is pressed to store the first two digits of the new parameter value, the right-hand decimal point will blink more rapidly. This indicates that the last two digits of the new parameter value must now be entered. Use ▲ and ▼ to scroll to the last 2 digits of the new parameter value. Press Mode to store the last two digits.

42

© 1998 Square D All Rights Reserved

Page 47

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller Programming the Drive

Electronic Programming Module (EPM) Every VSD07 drive controller has an Electronic Programming Module (EPM). The EPM stores the user's parameter settings and special OEM default settings (if programmed). The EPM can be installed in another drive controller for quick set-up. For example, if a drive controller is replaced with a new one, the EPM can be taken out of the first drive controller and installed in the new drive controller. Downtime is minimized because the new drive controller doesn't require programming - it is ready to run when the EPM is installed. • Do not remove or install the EPM while power is applied to drive controller. After removing the power from drive controller, wait three minutes before removing the EPM. The VSD07 drive controller contains two or three sets of parameter values, depending on whether the drive controller is programmed with optional OEM default settings. 1. The factory default settings are permanently stored on the main control board and cannot be changed. 2. The user settings are stored in the EPM. When the drive controller is shipped from the factory, the user settings are the same as the factory default settings. The user settings can be changed to configure the drive controller for a particular application. 3. The optional OEM default settings are also stored in the EPM. OEM default settings are typically used in cases where many drive controllers are used for the same application, which requires that all of the drive controllers have the same parameter settings. The OEM default settings cannot be changed without the optional Portable Programming Fixture. The drive controller is programmed to operate according to the user settings or the OEM default settings. Refer to Parameter 48 on page 67.

NOTE: The drive controller will not operate without the EPM. The drive controller displays “F1” if the EPM is missing or damaged.

© 1998 Square D All Rights Reserved

43

Page 48

VSD07 Adjustable Speed Drive Controller Programming the Drive

Bulletin No. 30072-450-07 November 1998

A Portable Programming Fixture is an optional accessory. It can quickly and easily program many VSD07 Series drive controllers for the same configuration. Once a “master” EPM is programmed, the fixture is used to copy those settings to other EPMs. If the OEM settings in the EPM become corrupted, the drive controller operates normally, until an attempt is made to perform a Reset OEM using Parameter 48 - Program Selection. The drive controller will flash “GF” to indicate that the OEM settings are no longer valid. This requires that the EPM be re-programmed using the Portable Programming Fixture. If the OEM settings and the user settings are both corrupted, the drive controller displays “GF” immediately and the drive controller requires a RESET 60 or RESET 50 using Parameter 48 - Program Selection. Once the Reset is performed, the parameters are programmed individually to match the OEM default settings. This allows the drive controller to operate as if it were in OEM mode, even though it is actually operating in User mode. Refer to Parameter 48 on page 67.

NOTE: The drive controller also displays “GF” if a Reset OEM or Operate With OEM Settings is attempted when the drive controller is not equipped with the OEM default option.

44

© 1998 Square D All Rights Reserved

Page 49

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller Parameter Menu

PARAMETER MENU Table 5:

Parameter Menu

Parameter No.

Parameter Name

01 02 03

Line Voltage Carrier Frequency Start Method

04

Stop Method

05 06 13

Standard Speed Source TB-14 Output TB-15 Output

08

TB-30 Output

09

TB-31 Output

10

TB-13A Function Select

Range of Adjustment [1], [2]

Factory Default [1], [2]

See Page

High (01), Low (02) High (01) 4 kHz (01), 6 kHz (02), 8 kHz (03), 10 kHz (04) 6 kHz (02) Normal (01), Start On Power Up (02), Normal (01) Start with DC Brake (03), Auto Restart (04) Coast (01), Coast With DC Brake (02), Ramp (03), Coast (01) Ramp With DC Brake (04) Keypad (01), Preset Speed 1 (02), 0–10 Vdc (03), Keypad (01) 4–20 mA (04) None (01), Run (02), Fault (03), Inverse Fault (04), None (01) Fault Lockout (05), At Set Speed (06), None (01) Above Preset 3 (07), Current Limit (08), Auto Speed (09), Reverse (10) None (01), 0–10 Vdc Freq (02), 2–10 Vdc Freq (03), None (01) 0–10 Vdc Load (04), 2–10 Vdc Load (05) None (01), 0–10 Vdc Load (02), None (01) 2–10 Vdc Load (03), Dynamic Braking (04) None (01), 0–10 Vdc (02), 4–20 mA (03), None (01) Preset Speed 1 (04), Run Reverse (05), Start Reverse (06), External Fault (07), Remote Keypad (08), DB Fault (09)

48 48 49 50 51 52 to 57

53 53 54

WARNING LOSS OF CONTROL When operating in Jog mode, the local or remote Stop command does not stop the drive controller. To stop the drive controller, open the contact between TB-13B and TB-4. Failure to follow this instruction can result in death, serious injury, or equipment damage. 11

TB-13B Function Select

None (01), 0–10 Vdc (02), 4–20 mA (03), Preset Speed 2 (04), Decrease Freq (05), Jog Forward (06), Jog Reverse (07)

None (01)

55

[1]

The numbers in () are the codes that correspond to the parameter value. If the range of adjustment is followed by a Table number, refer to the indicated table in Appendix A.

[2]

Factory defaults are shown for a 60 Hz base frequency. See Parameter 48 for 50 Hz base frequency.

© 1998 Square D All Rights Reserved

45

Page 50

VSD07 Adjustable Speed Drive Controller Parameter Menu

Bulletin No. 30072-450-07 November 1998

Table 5:

Parameter Menu (continued)

Parameter No.

Parameter Name

12

TB-13C Function Select

13 14

TB-15 Output Control

15

Serial Link

16 17 18 19 20 21 22 23 24

25 26 27 28 29 30 31–37 40 41 43 44

Range of Adjustment [1], [2]

Factory Default [1], [2]

None (01), 0–10 Vdc (02), 4–20 mA (03), Preset Speed 3 (04), Increase Freq (05), External Fault (06), Remote Keypad (07), DB Fault (08) (See Parameter 6 - TB-14 Output) Terminal Strip Only (01), Remote Keypad Only (02), Terminal Strip or Remote Keypad (03) Disable (01), Enable With Timer (02), Enable Without Timer (03) Tenths Of Hz (01), Whole Hz (02) Forward Only (01), Forward and Reverse (02) Refer to “Description of Parameters” section.

See Page

None (01)

56

None (01) Terminal Strip Only (01)

57 57

Enable With Timer (02) Keypad Speed Tenths (01) Rotation Forward Only (01) Range Selector 1.0–99.0 (03) Acceleration Time 20.0 Sec (20) 0.1–2970 Sec (Table 6). Range depends on the Deceleration Time 20.0 Sec (20) setting of Parameter 18 - Range Selector. DC Brake Time 0.0 Sec (00) DC Brake Voltage 0.0–30.0% (Table 7) 0.0% (00) Minimum Frequency 0.0–Maximum Freq 0.0 Hz Maximum Frequency Minimum Freq - 120 Hz (Table 7). Maximum setting 60.0 Hz (39) depends on the setting of Carrier Frequency. Minimum setting 21.0 Hz if the Minimum Freq. is set below 21.0 Hz. Current Limit 30–180% (Table 8). If Line Voltage is set to Low, 180% (75) maximum setting 150%. Motor Overload 30–100% (Table 8) 100% (70) Base Frequency 30.0–129.0 Hz (Table 8) 60.0 Hz (30) Fixed Boost 0.0–30.0% (Table 9) 1.0% (02) Accel Boost 0.0–19.8% (Table 9) 0.0% (00) Slip Compensation 0.0–5.0% (Table 9) 0.0% (00) Preset Speeds 0.0–120.0 Hz 0.0 Hz Frequency Scaling 0.0–198.0 Hz (Table 10) 60.0 Hz (30) Load Scaling 0–198% (Table 10) 198% (99) Serial Address 1–99 1 Password 0000–9999 1225

57 58 58 58 59 60 60 61 61 62

62 63 64 64 65 65 65 66 66 67 67

[1]

The numbers in () are the codes that correspond to the parameter value. If the range of adjustment is followed by a Table number, refer to the indicated table in Appendix A.

[2]

Factory defaults are shown for a 60 Hz base frequency. See Parameter 48 for 50 Hz base frequency.

46