Page 51

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller Parameter Menu

Table 5:

Parameter Menu (continued)

Parameter No.

Parameter Name

47 48

Clear Fault History Program Selection

50 51 52 53 54 55 56 57 58 59 60

Fault History Software Code DC Bus Voltage Motor Voltage Load 0–10 Vdc Input 4–20 mA Input TB Strip Status Keypad Status TB-30 Output TB-31 Output

Range of Adjustment [1], [2] Maintain (01), Clear (02) User Settings (01), OEM Settings (02), Reset OEM (03), Reset 60 (04), Reset 50 (05) (View-Only) (View-Only) (View-Only) (View-Only) (View-Only) (View-Only) (View-Only) (View-Only) (View-Only) (View-Only) (View-Only)

Factory Default [1], [2]

See Page

Maintain (01) User Settings (01) (N/A) (N/A) (N/A) (N/A) (N/A) (N/A) (N/A) (N/A) (N/A) (N/A) (N/A)

67 67 69 69 69 69 69 69 70 70 70 71 71

[1]

The numbers in () are the codes that correspond to the parameter value. If the range of adjustment is followed by a Table number, refer to the indicated table in Appendix A.

[2]

Factory defaults are shown for a 60 Hz base frequency. See Parameter 48 for 50 Hz base frequency.

© 1998 Square D All Rights Reserved

47

Page 52

VSD07 Adjustable Speed Drive Controller Description of Parameters

Bulletin No. 30072-450-07 November 1998

DESCRIPTION OF PARAMETERS 01 - Line Voltage Selection This calibrates the drive controller for the actual applied input voltage, and can be set to High (01) or Low (02). Refer to the table below for the proper setting depending on the applied input voltage. Model

Input Voltage Rating

VSD07••P10

Phase

Line Input Voltage

Setting

120/208/240 Vac

1 1

110–120 Vac or 220–240 Vac 200–208 Vac

High (01) Low (02)

VSD07••P20

208/240 Vac

1 or 3 1 or 3

220–240 Vac 200–208 Vac

High (01) Low (02)

VSD07••M20

208/240 Vac

3 3

220–240 Vac 200–208 Vac

High (01) Low (02)

VSD07••N40

400/480 Vac

3 3

440–480 Vac 380–415 Vac

High (01) Low (02)

VSD07••S60

590 Vac

3 3

575–600 Vac 460–480 Vac

High (01) Low (02)

02 - Carrier Frequency This sets the switching rate of the output IGBTs. Increasing the carrier frequency will result in less audible motor noise. Available settings are: 4 kHz, 6 kHz, 8 kHz, and 10 kHz. The carrier frequency setting also determines the maximum output frequency of the drive controller. Parameter Setting

Carrier Frequency

Maximum Output Frequency

01 02 03 04

4 kHz 6 kHz 8 kHz 10 kHz

66.0 Hz 96.0 Hz 120.0 Hz 120.0 Hz

NOTE: If this parameter is changed while the drive controller is running, the change will not take effect until the drive controller is stopped. Therefore, the allowable maximum frequency is not increased if the carrier frequency is increased while the drive controller is running. 48

© 1998 Square D All Rights Reserved

Page 53

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller Description of Parameters

If the select carrier frequency is greater than 6 kHz, the following derating rules apply: • For carrier frequency of 8 kHz, derate maximum ambient temperature to 109 °F (43 °C), or derate output current to 92%. • For carrier frequency of 10 kHz, derate maximum ambient temperature to 95 °F (35 °C), or derate output current to 82%.

03 - Start Method

WARNING UNINTENDED EQUIPMENT ACTION • Automatic restart can only be used for machines or installations that present no danger for personnel or equipment in the event of automatic restarting. • Equipment operation must conform with national and local safety regulations. Failure to follow these instructions can result in death, serious injury, or equipment damage. 01 NORMAL: The drive controller starts when the appropriate contact is closed on the terminal strip, or by pressing the START key on the optional remote keypad. Refer to Parameter 14. 02 START ON POWER UP: The drive controller automatically starts upon application of input power. 03 START WITH DC BRAKE: When a Start command is given, the drive controller applies DC Brake Voltage (Parameter 22) for the duration of DC Brake Time (Parameter 21) prior to starting the motor to ensure that the motor is not turning at the time of the START.

© 1998 Square D All Rights Reserved

49

Page 54

VSD07 Adjustable Speed Drive Controller Description of Parameters

Bulletin No. 30072-450-07 November 1998

04 AUTO RESTART: When a Start command is given, or after a fault, or upon application of power, the drive controller applies DC Brake Voltage (Parameter 22) for the duration of DC Brake Time (Parameter 21) prior to starting (or restarting) the motor. The drive controller attempts three restarts after a fault. During the interval between restart attempts, the display reads “SP” to indicate Start Pending. If all three restart attempts fail, the drive controller trips into Fault Lockout (displayed “LC”) and requires a manual reset. The delay time for Start Pending (SP) is 15 seconds or until the fault is removed, whichever is longer. There is no delay time at power up when Auto Restart is enabled, other than the normal power up delay of approximately 2 seconds. Refer to “Appendix C - Troubleshooting” on page 86.

NOTE: Options 02 and 04 require a two-wire start/stop circuit with a maintained Run contact. The Run contact must remain closed for the auto-start and auto-restart functions to operate. 04 - Stop Method

WARNING LOSS OF CONTROL When operating in Jog mode, the local or remote stop command does not stop the drive controller. To stop the drive controller, open the contact between TB-13B and TB-4. Failure to follow these instructions can result in death, serious injury, or equipment damage. 01 COAST TO STOP: When a stop command is given, the drive controller shuts off the output to the motor, allowing it to coast freely to a stop. 02 COAST WITH DC BRAKE: When a stop command is given, the drive controller activates DC braking (after a delay of up to 2 seconds, depending on frequency) to help decelerate the load. Refer to Parameters: 21 - DC Brake Time, and 22 - DC Brake Voltage.

50

© 1998 Square D All Rights Reserved

Page 55

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller Description of Parameters

03 RAMP TO STOP: When a stop command is given, the drive controller decelerates the motor to a stop at the rate determined by Parameter 20 - Deceleration Time.

WARNING NO HOLDING TORQUE • DC injection braking does not provide holding torque at zero speed. • DC injection braking does not function during loss of power or drive controller fault. • When required, use separate brake for holding torque. Failure to follow these instructions can result in death, serious injury, or equipment damage. 04 RAMP WITH DC BRAKE: When a stop command is given, the drive controller decelerates the motor down to 0.2 Hz (at the rate set by Parameter 20 - Deceleration Time) and then activates the DC braking. This is used to bring the load to a final stop, as the motor may still be turning slightly after the drive controller stops. Refer to Parameters: 21 - DC Brake Time, and 22 - DC Brake Voltage. 05 - Standard Speed Source This selects the speed reference source when the drive controller is in standard speed mode. 01 KEYPAD: Use the ▲ and ▼ buttons to increase or decrease the desired operating speed. 02 PRESET SPEED 1: The drive controller operates at the frequency set into Parameter 31. 03 0–10 Vdc: The drive controller responds to a 0–10 Vdc signal wired to TB-2 and TB-5. 04 4–20 mA: The drive controller responds to a 4–20 mA signal wired to TB-2 and TB-25.

© 1998 Square D All Rights Reserved

51

Page 56

VSD07 Adjustable Speed Drive Controller Description of Parameters

Bulletin No. 30072-450-07 November 1998

06 - TB-14 Open Collector Output This selects the status indication for the open-collector output at TB-14. The terms “open” and “close” refer to the state of the internal transistor that activates the circuit. When the transistor is “closed”, TB-14 is at the same potential as TB-4, allowing current to flow. 01 NONE: Disables the open-collector output. 02 RUN: Closes upon a start command. Opens if the drive controller is in a stop state, the drive controller faults, or input power is removed. DC braking is considered a stop state. 03 FAULT: Closes if there is no fault condition. Opens if the drive controller faults, or input power is removed. 04 INVERSE FAULT: Closes if the drive controller faults. Opens if there is no fault condition. 05 FAULT LOCKOUT: Closes when input power is applied. Opens if three restart attempts are unsuccessful, or if input power is removed. 06 AT SET SPEED: Closes if the drive controller is within ±0.5 Hz of the speed setpoint. 07 ABOVE PRESET SPEED 3: Closes if the output frequency exceeds the Preset Speed 3 setting. Opens if the output frequency is equal to or less than Preset Speed 3 (Parameter 33). 08 CURRENT LIMIT: Closes if the output current exceeds the current limit setting. Opens if the output current is equal to or less than current limit (see Parameter 25). 09 AUTOMATIC MODE: Closes if an automatic (terminal strip) speed reference is active. Opens if a standard (Parameter 5) speed reference is active. 10 REVERSE: Closes when reverse rotation is active. Opens when forward rotation is active. (see Parameter 17 - Rotation Direction).

52

© 1998 Square D All Rights Reserved

Page 57

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller Description of Parameters

08 - TB-30 Analog Output Terminal TB-30 is used as an analog output proportional to either output frequency or motor load. Frequency Scaling (Parameter 40) or Load Scaling (Parameter 41) is used to scale the output signal. 01 NONE 02 0–10 Vdc FREQ 03 2–10 Vdc FREQ 04 0–10 Vdc LOAD 05 2–10 Vdc LOAD

NOTE: The 2–10 Vdc signal is converted to a 4–20 mA signal by connecting a resistor in series with the signal such that the total load resistance is 500 Ω. However, this output cannot be used with devices that derive power from a 4–20 mA signal. 09 - TB-31 Analog Output Terminal TB-31 is used as an analog output proportional to motor load, or as the control signal to activate the optional external dynamic braking module. Load Scaling (Parameter 41) is used to scale the output signal when TB-31 is used as an analog output proportional to motor load. 01 NONE 02 0–10 Vdc LOAD 03 2–10 Vdc LOAD 04 DYNAMIC BRAKING: TB-31 becomes the “trigger” that activates the optional external dynamic braking module. Refer to the manual included with the dynamic braking option.

NOTE: The 2–10 Vdc signal is converted to a 4–20 mA signal by connecting a resistor in series with the signal such that the total load resistance is 500 Ω. However, this output cannot be used with devices that derive power from a 4–20 mA signal.

© 1998 Square D All Rights Reserved

53

Page 58

VSD07 Adjustable Speed Drive Controller Description of Parameters

Bulletin No. 30072-450-07 November 1998

10 - TB-13A Function Select This is used to select the function of terminal TB-13A. Closing TB-13A to TB-4 activates the selected function. The following can be selected: 01 NONE: Disables the TB-13A function. 02 0–10 Vdc: Selects 0–10 Vdc as the auto speed reference input. The 0–10 Vdc signal is wired to TB-5 and TB-2. 03 4–20 mA: Selects 4–20 mA as the auto speed reference input. The 4–20 mA signal is wired to TB-25 and TB-2. 04 PRESET SPEED 1: Selects Preset Speed 1 as the auto speed reference. The drive controller operates at the frequency programmed into Parameter 31. 05 RUN REVERSE: Close TB-13A to TB-4 to run in the reverse direction, and open to stop. This setting forces TB-12 to act as run Fwd, requiring a maintained contact to run in the forward direction. TB-1 must be closed to TB-4 for this function to operate. 06 START REVERSE: Momentarily close TB-13A to TB-4 to start the drive controller in the reverse direction. Momentarily open TB-1 to TB-4 to stop. This setting forces TB-12 to act as Start Fwd, requiring a momentary contact to start in the forward direction. 07 EXTERNAL FAULT: Sets TB-13A as a normally closed external fault input. If TB-13A is open with respect to TB-4, the controller will fault. 08 REMOTE KEYPAD: Selects the optional remote keypad as the control source. Refer to Parameter 14 - Control. 09 DB FAULT: Sets TB-13A as a dynamic braking fault input when using the optional dynamic braking module. When this input is activated by the dynamic braking module, the controller will either ramp or coast to a stop, depending on the selected STOP METHOD (Parameter 04). Refer to the manual included with the dynamic braking option.

NOTE: In order for the Run Reverse and Start Reverse functions to operate, set Parameter 17 - Rotation Direction to forward and reverse.

54

© 1998 Square D All Rights Reserved

Page 59

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller Description of Parameters

11 - TB-13B Function Select

WARNING LOSS OF CONTROL • When operating in Jog mode, the local or remote stop command does not stop the drive controller. To stop the drive controller, open the contact between TB-13B and TB-4. • Jog reverse operates the drive controller in reverse rotation even if rotation direction (Parameter 17) is set to forward only. Failure to follow these instructions can result in death, serious injury, or equipment damage. This selects the function of terminal TB-13B. Closing TB-13B to TB-4 activates the selected function. The following functions can be selected: 01 NONE: Disables the TB-13B function. 02 0–10 Vdc: Selects 0–10 Vdc as the auto speed reference input. The 0–10 Vdc signal is wired to TB-5 and TB-2. 03 4–20 mA: Selects 4–20 mA as the auto speed reference input. The 4–20 mA signal is wired to TB-25 and TB-2. 04 PRESET SPEED 2: Selects Preset Speed 2 as the auto speed reference. The drive controller operates at the frequency programmed into Parameter 32. 05 DECREASE FREQUENCY: Decreases the speed setpoint when using the MOP function. Refer to “Speed Reference Selection” on page 21. 06 JOG FORWARD: Jog in the forward direction. In this mode, the drive controller will jog at the speed programmed into Parameter 32 - Preset Speed 2. 07 JOG REVERSE: Jog in the reverse direction. In this mode, the drive controller will jog at the speed programmed into Parameter 32 - Preset Speed 2.

© 1998 Square D All Rights Reserved

55

Page 60

VSD07 Adjustable Speed Drive Controller Description of Parameters

Bulletin No. 30072-450-07 November 1998

08 DB FAULT: Sets TB-13A as a dynamic braking fault input when using the optional dynamic braking module. When this input is activated by the dynamic braking module, the drive controller will either ramp or coast to a stop, depending on the selected STOP METHOD (Parameter 04). Refer to the manual included with the dynamic braking option.

NOTE: If the drive controller is commanded to jog while running, the drive controller enters the Jog mode and runs at Preset Speed 2. When the jog command is removed, the drive controller will stops. NOTE: External fault, if configured, overrides the Jog function. 12 - TB-13C Function Select This selects the function of terminal TB-13C. Closing TB-13C to TB-4 activates the TB-13C input function. The following functions can be selected: 01 NONE: Disables the TB-13C function. 02 0–10 Vdc: Selects 0–10 Vdc as the auto speed reference input. The 0–10 Vdc signal is wired to TB-5 and TB-2. 03 4–20 mA: Selects 4–20 mA as the auto speed reference input. The 4–20 mA signal is wired to TB-25 and TB-2. 04 PRESET SPEED 3: Selects Preset Speed 3 as the auto speed reference. The drive controller operates at the frequency programmed into Parameter 33. 05 INCREASE FREQUENCY: Increases the speed setpoint when using the MOP function. Refer to “Speed Reference Selection” on page 21. 06 EXTERNAL FAULT: Sets TB-13C as a normally closed external fault input. If TB-13C is open with respect to TB-4, the drive controller will fault. 07 REMOTE KEYPAD: Selects the optional remote keypad as the control source. Refer to Parameter 14 - Control.

56

© 1998 Square D All Rights Reserved