Page 61
Bulletin No. 30072-450-07 November 1998
VSD07 Adjustable Speed Drive Controller Description of Parameters
13 - TB-15 Open Collector Output This selects the status indication for the open-collector output at TB-15, and has the same selections as Parameter 6 - TB-14 Open Collector Output. 14 - Control This selects the source of start/stop and direction commands. 01 TERMINAL STRIP ONLY: The drive controller only responds to start/stop and direction commands from the terminal strip. The keypad is totally disabled. 02 REMOTE KEYPAD ONLY: The drive controller only responds to start/stop and direction commands from the optional remote keypad. 03 TERMINAL STRIP OR REMOTE KEYPAD: Terminal TB-13A or TB-13C can be used to toggle between terminal strip control and remote keypad control. See Parameters 10 and 12.
NOTE: The stop button on the optional remote keypad is always active in (02) and (03) above. 15 - Serial Link
WARNING LOSS OF CONTROL Setting parameter number 15, Serial Link, to 03 disables communication loss detection. Provide alternate control paths when disabling communication loss detection. Failure to follow these instructions can result in death, serious injury, or equipment damage. 01 DISABLED: Disables the serial link. 02 ENABLED WITH TIMER: Activates the serial link with a “watchdog” timer that will shut down the drive controller after 10 seconds of no serial activity, which could indicate a failed serial link. © 1998 Square D All Rights Reserved
57
Page 62
VSD07 Adjustable Speed Drive Controller Description of Parameters
Bulletin No. 30072-450-07 November 1998
03 ENABLED WITHOUT TIMER: Activates the serial link without a “watchdog” timer. Do not operate the drive controller from the serial link without the watchdog timer, as control of the drive controller could be lost if there is a failure in the serial link. 16 - Keypad Speed Editing This selects the increments of the speed setpoint when the speed source is the ▲ and ▼ buttons on the front of the drive. 01 TENTHS OF Hz: The speed setpoint changes by tenths of Hz. If the button is pressed and held, the speed setpoint changes by tenths of Hz until the next whole Hz is reached, and then the setpoint changes by 1 Hz increments. 02 WHOLE Hz: The speed setpoint only changes by one Hz increments. 17 - Rotation Direction 01 FORWARD ONLY: The drive controller only allows rotation in the forward direction. However, Jog Reverse (see Parameter 11) still operates even if Forward Only is selected. 02 FORWARD AND REVERSE: The drive controller allows rotation in both directions. 18 - Range Selector This selects the range of possible settings for Parameters 19 (Acceleration Time), 20 (Deceleration Time), and 21 (DC Brake Time). Refer to the table below:
58
Parameter Setting
Range (s)
Increments (s)
01
0.1–9.9
0.1
02
0.3–29.7
0.3
03
1.0–99.0
1.0
04
3.0–297.0
3.0
05
10.0–990.0
10.0
06
30.0–2970.0
30.0
© 1998 Square D All Rights Reserved
Page 63
Bulletin No. 30072-450-07 November 1998
VSD07 Adjustable Speed Drive Controller Description of Parameters
Once a range is selected, specific settings for Parameters 19, 20, and 21 can be selected from Table 6 on page 72. Only one range can be selected, which applies to all three parameters.
NOTE: If a new range is selected such that the values of Parameters 19, 20, and/or 21 are higher than the highest setting of the new range, the drive controller continues to operate with those values until the parameters are changed. When the parameter is viewed, “100” will be blinking to indicate that the present value is above the new range. If a new range is selected such that the values of Parameters 19, 20, and/or 21 are still within the new range, the drive controller continues to operate with those values until the parameters are changed. When the parameter is viewed, the setting number from the new range that corresponds to the closest higher value to the present value will be blinking to indicate that the present value does not have an exact match in the new range. 19 - Acceleration Time This sets the acceleration rate for all speed reference sources (keypad, speed potentiometer, 4–20 mA, 0–10 Vdc, jog, and the preset speeds). This setting is the time to accelerate from 0 Hz to the Base Frequency (Parameter 27). To set this parameter, select a value from Table 6 on page 72 that is within the time range defined by the Range Selector setting (Parameter 18). Setting 00 cannot be selected.
© 1998 Square D All Rights Reserved
59
Page 64
VSD07 Adjustable Speed Drive Controller Description of Parameters
Bulletin No. 30072-450-07 November 1998
20 - Deceleration Time This sets the deceleration rate for all speed reference sources (keypad, speed potentiometer, 4–20 mA, 0–10 Vdc, jog, and preset speeds). This setting is the time to decelerate from base frequency to 0 Hz. If the drive controller is set to coast to stop (Parameter 04), this parameter has no effect when a stop command is given. To set this parameter, select a value from Table 6 in Appendix A that is within the time range defined by the range selector setting (Parameter 18). Setting 00 cannot be selected. 21 - DC Brake Time
WARNING NO HOLDING TORQUE • DC injection braking does not provide holding torque at zero speed. • DC injection braking does not function during loss of power or drive controller fault. • When required, use separate brake for holding torque. Failure to follow these instructions can result in death, serious injury, or equipment damage. This determines the length of time that the DC braking voltage is applied to the motor. The DC Brake Time should be set to the lowest value that provides satisfactory operation in order to minimize motor heating. To set this parameter, select a value from Table 6 in Appendix A that is within the time range defined by the Range Selector setting (Parameter 18).
60
© 1998 Square D All Rights Reserved
Page 65
Bulletin No. 30072-450-07 November 1998
VSD07 Adjustable Speed Drive Controller Description of Parameters
22 - DC Brake Voltage This sets the magnitude of the DC braking voltage, in percentage of the nominal DC Bus voltage (DC Bus = input AC voltage X 1.414). The point at which the DC braking is activated depends on the selected Stop Method (Parameter 04). If Coast With DC Brake is selected, and a stop command is issued, braking is activated after a time delay of up to 2 seconds, depending on the output frequency at the time of the stop command. In this case, DC braking helps decelerate the load. If Ramp With DC Brake is selected, braking is activated when the output frequency reaches 0.2 Hz. In this case, the drive controller decelerates the load to 0.2 Hz and then DC braking is used to stop and hold the motor. To set this parameter, select a value from Table 7 in Appendix A. To minimize motor heating, DC Brake Voltage should be set to the lowest value that provides satisfactory operation. 23 - Minimum Frequency This sets the minimum output frequency of the drive controller for all speed reference sources except the Preset Speeds (Parameters 31–37). When using a 0–10 Vdc or 4–20 mA analog speed reference signal, this parameter also sets the drive controller speed that corresponds to the minimum analog input (0 Vdc or 4 mA). Unlike most other parameters, the minimum frequency is entered directly, rather than selecting a value from a table. Refer to “Programming DirectEntry Parameters” on page 42.
NOTE: If this parameter is changed while the drive controller is running, the new value will not take effect until the drive controller is stopped.
© 1998 Square D All Rights Reserved
61
Page 66
VSD07 Adjustable Speed Drive Controller Description of Parameters
Bulletin No. 30072-450-07 November 1998
24 - Maximum Frequency This sets the maximum output frequency of the drive controller for all speed reference sources except the Preset Speeds (Parameters 31–37). It is used with Minimum Frequency (Parameter 23) to define the operating range of the drive controller. The highest Maximum Frequency setting is determined by the Carrier Frequency setting (Parameter 02). The minimum allowable setting is either 21.0 Hz (if Minimum Frequency is set below 21.0 Hz), or is equal to the Minimum Frequency setting (if Minimum Frequency is set above 21.0 Hz). When using a 0–10 Vdc or 4–20 mA analog speed reference signal, this parameter also sets the drive controller speed that corresponds to the maximum analog input (10 Vdc or 20 mA). To set this parameter, select a value from Table 7 in Appendix A.
NOTE: If this parameter is changed while the drive controller is running, the new value will not take effect until the drive controller is stopped. 25 - Current Limit This sets the maximum allowable output current of the drive controller before current limiting takes effect. The maximum setting is either 180% or 150%, depending on whether Line Voltage Selection (Parameter 01) is set to High or Low. The drive controller enters current limit when the load demands more current than the Current Limit setting. To reduce the output current, the drive controller will reduce the output frequency if the motor current exceeds the current limit setting. When the overcurrent condition passes, the drive controller accelerates the motor back up to the speed setpoint. To set this parameter, select a value from Table 8 in Appendix A.
62
© 1998 Square D All Rights Reserved
Page 67
Bulletin No. 30072-450-07 November 1998
VSD07 Adjustable Speed Drive Controller Description of Parameters
26 - Motor Overload
CAUTION LOSS OF MOTOR OVERLOAD PROTECTION When using external overload relays connected to the drive controller output, the overload relay must be capable of operation over the expected range of drive controller output frequencies (including direct current). When DC injection braking is used: • The overload relay must be capable of operation with direct current flowing in the motor. • Do not use overload relays equipped with current transformers for sensing the motor current. MOTOR OVERHEATING This drive controller does not provide direct thermal protection for the motor. Use of a thermal sensor in the motor may be required for protection at all speeds and loading conditions. Consult motor manufacturer for thermal capability of motor when operated over desired speed range. If drive controller trips on overload fault, allow sufficient time for the motor to cool prior to restarting. Failure to follow these instructions can result in injury or equipment damage. The motor overload circuit protects the motor from excessive overcurrent. This circuit allows the drive controller to deliver up to 150% current for one minute, and higher current levels for shorter periods of time. If the overload circuit “times out”, the drive controller will trip into an Overload fault. Motor Overload should be set to the ratio (in percent) of the motor current rating to the drive controller current rating in order to properly protect the motor. See the example on the next page.
© 1998 Square D All Rights Reserved
63
Page 68
VSD07 Adjustable Speed Drive Controller Description of Parameters
Bulletin No. 30072-450-07 November 1998
To set this parameter, select a value from Table 8 in Appendix A. Example: A 3 hp, 480 Vac drive controller with a 4.8 A rating is operating a 2 hp motor with a current rating of 3.4 A. Dividing the motor current rating by the drive controller current rating yields 71% (3.4 ÷ 4.8 = 0.71 = 71%). From Table 8 in Appendix A, setting 41 corresponds to 71%. 27 - Base Frequency The Base Frequency determines the V/Hz ratio by setting the output frequency at which the drive controller outputs full voltage to the motor. In most cases, set the Base Frequency to match the motor's rated frequency. To set this parameter, select a value from Table 8 in Appendix A.
NOTE: If this parameter is changed while the drive controller is running, the new value will not take effect until the drive controller is stopped. Example: A 460 Vac, 60 Hz motor requires a V/Hz ratio of 7.67 (460 V ÷ 60 Hz = 7.67 V/Hz) in order to produce full torque. Setting the Base Frequency to 60 Hz causes the drive controller to output full voltage (460 Vac) at 60 Hz, which yields the required 7.67 V/Hz. Output voltage is proportional to output frequency, so the 7.67 V/Hz ratio is maintained from 0–60 Hz, allowing the motor to produce full torque from 2 Hz (below 2 Hz there is less torque due to slip) up to 60 Hz. 28 - Fixed Boost Fixed Boost is used in applications which require high starting torque. Fixed Boost increases starting torque by increasing the output voltage at lower frequencies (below 30 Hz for 60 Hz base frequency), which increases the V/Hz ratio. To set this parameter, select a value from Table 9 in Appendix A.
64
© 1998 Square D All Rights Reserved
Page 69
Bulletin No. 30072-450-07 November 1998
VSD07 Adjustable Speed Drive Controller Description of Parameters
29 - Acceleration Boost Acceleration Boost helps accelerate high-inertia loads. During acceleration, the output voltage is increased to increase motor torque. Once the motor reaches the new speed setpoint, the boost is turned off and the output voltage returns to the normal value. To set this parameter, select a value from Table 9 in Appendix A. 30 - Slip Compensation Slip Compensation is used to counteract changes in motor speed (slip) caused by changes in load. In a standard AC induction motor, the shaft speed decreases as load increases, and increases as load decreases. By increasing or decreasing the output frequency in response to an increasing or decreasing load, the slip is counteracted and speed is maintained. Most standard NEMA B motors have a 3% slip rating. To set this parameter, select a value from Table 9 in Appendix A. 31 to 37 - Preset Speed 1 to 7 Preset speeds are only active when the drive controller is in Auto mode, and are activated by closing the contacts between TB-4 and TB-13A, 13B, and 13C. The TB-13 terminals must be programmed as preset speed selects using Parameters 10–12. Unlike most other parameters, the preset speed values are entered directly, rather than selecting a value from a table. Refer to “Programming Direct-Entry Parameters” on page 42 for instructions on programming direct-entry parameters.
NOTE: Preset speeds can operate outside of the range defined by the minimum and maximum frequency parameters (Parameters 23 and 24). The range of operation for the preset speeds is from 0 Hz to the absolute maximum frequency determined by the Carrier Frequency (see Parameter 02). Therefore, when using preset speeds, the drive controller can operate below the Minimum Frequency setting, and above the Maximum Frequency setting, but not above the absolute maximum frequency determined by the carrier frequency. © 1998 Square D All Rights Reserved
65
Page 70
VSD07 Adjustable Speed Drive Controller Description of Parameters
Bulletin No. 30072-450-07 November 1998
Preset Speed
TB-13A
TB-13B
TB-13C
1
Closed
Open
Open
2
Open
Closed
Open
3
Open
Open
Closed
4
Closed
Closed
Open
5
Closed
Open
Closed
6
Open
Closed
Closed
7
Closed
Closed
Closed
NOTE: When a TB-13 terminal is programmed for a function other than a preset speed select, it is considered Open for the table above. 40 - Frequency Scaling This scales the analog output signal at TB-30 when it is configured for a frequency output. This setting is the output frequency that is indicated when the output signal measures 10 Vdc. To set this parameter, select a value from Table 10 in Appendix A. Example: A 0–5 Vdc signal is required to indicate 0–60 Hz. Setting this parameter to 120 Hz yields 10 Vdc at 120 Hz, and 5 Vdc at 60 Hz. If the drive controller only operates up to 60 Hz, the output signal at TB-30 is limited to the desired 0–5 Vdc. 41 - Load Scaling (Motor Load) This scales the analog output signal at TB-30 and/or TB-31 when they are configured for a motor load output. This setting is the load (in %) that is indicated when the output signal measures 10 Vdc. To set this parameter, select a value from Table 10 in Appendix A. Example: A 0–10 Vdc signal is required to indicate 0–150% motor load. Setting this parameter to 150% yields 10 Vdc at 150% load.
66