Page 31
Bulletin No. 30072-450-07 November 1998
VSD07 Adjustable Speed Drive Controller Control Wiring Diagrams
Two-Wire Start/Stop Control Notes (refer to Figure 13 on page 26): 1. Close TB-1 to TB-4 to RUN, and open TB-1 to TB-4 to STOP. 2. If reverse direction is required, set Rotation Direction (Parameter 17) to Forward and Reverse, and set TB-13A (Parameter 10) to Start Reverse. If reverse direction is not required, wire TB-12 directly to TB-4. 3. For 0–10 Vdc or 4–20 mA speed control: a. Program Parameter 05 - Standard Speed Source for 0–10 Vdc or 4–20 mA. This method is preferable if only one speed source is required because the TB-13 terminals can be used for other functions. or b. Program one TB-13 terminal (13A, 13B, or 13C) for 0–10 Vdc or 4–20 mA. When that terminal is closed to TB-4, the drive controller responds to the selected speed reference signal. If that terminal is not closed to TB-4, the drive controller responds to the speed control source selected in Parameter 05 - Standard Speed Source. This method is used to toggle between two speed sources.
© 1998 Square D All Rights Reserved
27
Page 32
VSD07 Adjustable Speed Drive Controller Control Wiring Diagrams
Bulletin No. 30072-450-07 November 1998
Alternate Two-Wire Start/Stop Control Figure 14 is an alternate two-wire start/stop control diagram. One maintained contact is used for Run Forward and another maintained contact is used for Run Reverse.
WARNING LOSS OF CONTROL When operating in Jog mode, the local or remote Stop command does not stop the drive controller. To stop the drive controller, open the contact between TB-13B and TB-4. Failure to follow this instruction can result in death, serious injury, or equipment damage.
The TB-2 terminals are internally connected 2
30 31 TXA TXB
Common
4–20 mA Input
Reverse
0–10 Vdc or 4–20 mA Select
+
Forward
Stop P 15 Vdc 0–10 Vdc Input
1 4 5 6 11 12 2 14 13A 13B 13C 15 25
+ -
Figure 14: Alternate Two-Wire Start/Stop Control
28
© 1998 Square D All Rights Reserved
Page 33
Bulletin No. 30072-450-07 November 1998
VSD07 Adjustable Speed Drive Controller Control Wiring Diagrams
Alternate Two-Wire Start/Stop Control Notes (refer to Figure 14 on page 28): 1. Close TB-12 to TB-4 to RUN, and open TB-12 to TB-4 to STOP. 2. For this control scheme, set TB-13A to Run Reverse. Refer to Parameter 10 - TB13A Function. 3. If reverse direction is required, set Rotation Direction (Parameter 17) to Forward and Reverse. Close TB-13A to TB-2 to Run in Reverse, and open TB-13A to TB-4 to Stop. If both TB-12 and TB-13A are closed to TB-4, the drive controller stops. 4. For 0–10 Vdc or 4–20 mA speed control: a. Program Parameter 05 - Standard Speed Source for 0–10 Vdc or 4–20 mA. This method is preferable if only one speed source is required because the TB-13 terminals can be used for other functions. or b. Program one TB-13 terminal (13A, 13B, or 13C) for 0–10 Vdc or 4–20 mA. When that terminal is closed to TB-4, the drive controller responds to the selected speed reference signal. If that terminal is not closed to TB-4, the drive controller responds to the speed control source selected in Parameter 05 - Standard Speed Source. This method is used to toggle between two speed sources.
© 1998 Square D All Rights Reserved
29
Page 34
VSD07 Adjustable Speed Drive Controller Control Wiring Diagrams
Bulletin No. 30072-450-07 November 1998
Three-Wire Start/Stop Control Figure 15 is a typical three-wire start/stop control diagram. Momentary contacts (such as pushbuttons) are used for Start and Stop commands.
WARNING LOSS OF CONTROL When operating in Jog mode, the local or remote Stop command does not stop the drive controller. To stop the drive controller, open the contact between TB-13B and TB-4. Failure to follow this instruction can result in death, serious injury, or equipment damage.
The TB-2 terminals are internally connected
+
Momentary Stop Contact
2
30 31 TXA TXB
Common
4–20 mA Input
Reverse
0–10 Vdc or 4–20 mA Select
Forward
Stop P 15 Vdc 0–10 Vdc Input
1 4 5 6 11 12 2 14 13A 13B 13C 15 25
+
Momentary Start Contact
Figure 15: Three-Wire Start/Stop Control
30
© 1998 Square D All Rights Reserved
Page 35
Bulletin No. 30072-450-07 November 1998
VSD07 Adjustable Speed Drive Controller Control Wiring Diagrams
Three-Wire Start/Stop Control Notes (refer to Figure 15 on page 30): 1. Momentarily close TB-12 to TB-4 to start the drive controller, and momentarily open TB-1 to TB-4 to stop the drive controller. 2. If reverse direction is required, set Rotation Direction (Parameter 17) to Forward and Reverse, and set TB-13A (Parameter 10) to Start Reverse. If the Fwd/Rev switch is changed while the drive controller is running, the drive controller does not change direction until the Start button is pushed. If reverse direction is not required, the Start pushbutton must be wired directly to TB-12 and TB-4. 3. For 0–10 Vdc or 4–20 mA speed control, use one of the following methods: a. Program Parameter 05 - Standard Speed Source for 0–10 Vdc or 4–20 mA. This method is preferable if only one speed source is required because the TB-13 terminals can be used for other functions. or b. Program one TB-13 terminal (13A, 13B, or 13C) for 0–10 Vdc or 4–20 mA. When that terminal is closed to TB-4, the drive controller responds to the selected speed reference signal. If that terminal is not closed to TB-4, the drive controller responds to the speed control source selected in Parameter 05 - Standard Speed Source. This method is used to toggle between two speed sources.
© 1998 Square D All Rights Reserved
31
Page 36
VSD07 Adjustable Speed Drive Controller Control Wiring Diagrams
Bulletin No. 30072-450-07 November 1998
Speed Potentiometer and Preset Speed Control Figure 16 shows how to wire a speed potentiometer and/or Preset Speed control for either a two-wire or three-wire start/stop circuit.
WARNING LOSS OF CONTROL When operating in Jog mode, the local or remote Stop command does not stop the drive controller. To stop the drive controller, open the contact between TB-13B and TB-4. Failure to follow this instruction can result in death, serious injury, or equipment damage.
The TB-2 terminals are internally connected
2
30 31 TXA TXB
Preset Speed Select
Preset Speed Select
Preset Speed Select
Start
Common
0–10 Vdc Input 10 Vdc Supply
Stop P 15 Vdc
1 4 5 6 11 12 2 14 13A 13B 13C 15 25
2.5 Ω–10 kΩ
Figure 16: Speed Potentiometer and Preset Speed Control
32
© 1998 Square D All Rights Reserved
Page 37
Bulletin No. 30072-450-07 November 1998
VSD07 Adjustable Speed Drive Controller Motor Thermal Overload Protection
Speed Potentiometer and Preset Speed Control Notes (refer to Figure 16 on page 32): 1. Program the Preset Speeds (Parameters 31–37) to the desired values. 2. Program TB-13A, TB-13B, and TB-13C (refer to Parameters 10, 11, and 12). To select a preset speed, close the appropriate TB-13 terminal(s) to TB-4. See preset speed table on page 66. 3. If reverse rotation is also required, TB-13A cannot be used as a Preset Speed Select. Program the TB-13A to select Run Reverse or Start Reverse. Use TB-13B and TB-13C to select preset speeds. 4. For speed potentiometer control, program Parameter 05 - Standard Speed Source for 0–10 Vdc. If none of the preset speeds are selected (all of the TB-13 terminals are open), the drive controller responds to the speed potentiometer. MOTOR THERMAL OVERLOAD PROTECTION The VSD07 drive controller provides indirect motor thermal protection by continuously calculating the I2t of the motor based on the setting of the parameter. This calculation establishes thermal protection of the motor and drive controller for normal conditions of ambient temperature. Typical trip values are: • Motor current = 180% of nominal drive controller current for 32 s. • Motor current = 150% of nominal drive controller current for 60 s. If the motor current ≤ 110% of the nominal drive controller current, the drive controller will not trip. Equivalent to Class 10 overloads.
© 1998 Square D All Rights Reserved
33
Page 38
VSD07 Adjustable Speed Drive Controller Motor Thermal Overload Protection
Bulletin No. 30072-450-07 November 1998
The thermal state of the drive controller is automatically reset when power is removed.
CAUTION LOSS OF MOTOR OVERLOAD PROTECTION When external overload relays are connected to the drive controller output, the overload relay must be capable of operation over the expected range of drive controller output frequencies (including direct current). When DC injection braking is used: • The overload relay must be capable of operation with direct current flowing in the motor. • Do not use overload relays equipped with current transformers for sensing the motor current. MOTOR OVERHEATING This drive controller does not provide direct thermal protection for the motor. A thermal sensor in the motor may be required for protection at all speeds and loading conditions. Consult motor manufacturer for thermal capability of motor when operated over desired speed range. If drive trips on overload fault, allow sufficient time for the motor to cool prior to restarting. Failure to follow these instructions can result in injury or equipment damage.
34
© 1998 Square D All Rights Reserved
Page 39
Bulletin No. 30072-450-07 November 1998
VSD07 Adjustable Speed Drive Controller Available Torque
AVAILABLE TORQUE Continuous duty: • For self-ventilated motors, motor cooling depends on the speed. • Continuous duty results in motor derating for speeds less than 50% of the nameplate motor speed. Operation in overspeed: • In overspeed operation, the voltage no longer increases with the frequency, resulting in reduced induction in the motor and loss of torque. Consult the motor manufacturer to ensure that the motor operates in overspeed. • For a special motor, the base frequency (Parameter 27) can be adjusted between 30 and 129 Hz and the maximum frequency (Parameter 24) can be adjusted between minimum frequency and 120 Hz.
CAUTION MACHINERY OVERSPEED Some motors and/or loads are not suited for operation above nameplate motor speed and frequency. Consult motor manufacturer before operating motor above rated speed. Failure to follow this instruction can result in injury or equipment damage.
© 1998 Square D All Rights Reserved
35
Page 40
VSD07 Adjustable Speed Drive Controller Initial Power Up and Motor Rotation
Bulletin No. 30072-450-07 November 1998
INITIAL POWER UP AND MOTOR ROTATION
DANGER HAZARDOUS VOLTAGE • Before attempting to operate the drive controller, motor, and driven equipment, ensure that all procedures pertaining to installation and wiring have been properly followed. See “General Wiring Practices” on page 12. • Disconnect all power before servicing the drive controller. WAIT THREE MINUTES until DC bus capacitors discharge, then measure DC bus capacitor voltage as described on page 89 to verify that DC voltage is less than 45 V. The display is not an accurate indication of the absence of DC bus voltage. • DO NOT short across the DC bus capacitors or touch terminal strip screw connections with voltage present. • No serviceable components are inside. DO NOT remove cover. • User is responsible for conforming to all applicable code requirements with respect to grounding all equipment. • Use only electrically insulated tools. If the drive controller must be replaced: • Disconnect all power. • Place a “DO NOT TURN ON” label on drive controller disconnect. • Lock disconnect in open position. Electrical shock will result in death or serious injury.
36