Page 21

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller Power Wiring Diagrams

POWER WIRING DIAGRAMS

VSD07••P10 Models L1

Figure 4:

L2

120 VAC Single-Phase Input Power Wiring Diagram

L1

Figure 5:

L2

N*

VSD07••P10, VSD07••P20 Models *On VSD07••P20 models, this terminal is labeled L3. NOTE: Do not connect 240 V to “N”.

208/240 VAC Single-Phase Input Power Wiring Diagram

L1

Figure 6:

N

L2

L3

VSD07••M20, VSD07••P20, VSD07••N40, and VSD07••S60 Models

Three-Phase Input Power Wiring Diagram

© 1998 Square D All Rights Reserved

17

Page 22

VSD07 Adjustable Speed Drive Controller Power Wiring Diagrams

Bulletin No. 30072-450-07 November 1998

WARNING DRIVE CONTROLLER DAMAGE Drive controller will be damaged if input line voltage is applied to output terminals (T1, T2, T3). Check power connections before energizing drive controller. Failure to follow this instruction can result in death, serious injury, or equipment damage.

T1

T2

T3

B-

B+

- + 3-Phase AC Motor

DC Bus Voltage

Figure 7:

Output Power Wiring Diagram (all models)

Table 4:

Wire Size and Torque for Power Terminals

VSD07

Maximum Wire Size [1, 2]

Torque

All Models

12 AWG

4.0–4.5 lb-in (0.45–0.5 N•m)

[1] 75 °C copper. [2] Minimum strand size: 26 AWG.

Equipment Ground Terminal The equipment ground connection is made by a #8-32 screw terminal mounted to the heat sink.

18

© 1998 Square D All Rights Reserved

Page 23

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller Control Wiring

Using a Line Contactor When controlling the power with an isolation line contactor, limit operations of the contactor to less than once every two minutes. Failure to follow this recommendation may cause premature failure of the filtering capacitors and precharge circuit components. Use logic inputs to start and stop the drive controller. CONTROL WIRING Control Wiring vs. Power Wiring Run external control wiring in a separate conduit away from all other input and output power wiring. Failure to do this can result in electrical noise on the control wiring, causing erratic drive controller behavior. Use twisted wires or shielded cable grounded at the drive controller chassis ONLY. Recommended control wire is Belden 8760 (2-wire) or 8770 (3-wire), or equivalent. Strip off 0.20 to 0.25 in (5.1 to 6.4 mm) of insulation for control wiring. Maximum wire size for all control terminals is 16 AWG. Tightening torque is 0.2 lb-in (0.23 kg cm). TB-2: Circuit Common The TB-2 terminals are used as circuit common for analog input and analog output functions. There are two TB-2 terminals, which are internally connected on the main control board. If necessary, TB-2 may be connected to chassis ground.

NOTE: Connect TB-2 to chassis ground when using serial communications. TB-4: P 15 Vdc This terminal is used to provide voltage to the external logic input signals (TB-1, TB-12, TB-13A, TB-13B, and TB-13C). Do not use this terminal to power any other external circuits or loads. © 1998 Square D All Rights Reserved

19

Page 24

VSD07 Adjustable Speed Drive Controller Control Wiring

Bulletin No. 30072-450-07 November 1998

Surge Suppression Current and voltage surges and spikes in the coils of contactors, relays, and solenoids, near or connected to the drive controller cause erratic drive controller operation. Use a snubber circuit on relay and contactor coils associated with the inverter. • For AC loads, snubbers consist of a resistor and a capacitor in series across the coil. • For DC loads, place a free-wheeling or flyback diode across the coil. Surge suppression devices are available. See the Square D Digest. Start/Stop Control There are various control schemes that allow for 2-wire and 3-wire Start/Stop circuits. See “Control Wiring Diagrams” on page 25. Speed Reference Signals The drive controller allows for three analog speed reference inputs: 1. Speed Potentiometer: Connect the wiper lead of a 2.5–10 kΩ potentiometer to terminal TB-5, and connect the high and low end leads to terminals TB-6 and TB-2, respectively. The TB-2 terminals are internally connected 1 4 5 6 11 12 2 14 13A 13B 13C 15 25 2

30 31 TXA TXB

2.5–10 kΩ Potentiometer

Figure 8:

20

Speed Potentiometer Connection

© 1998 Square D All Rights Reserved

Page 25

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller Control Wiring

2. 0–10 Vdc: Wire the positive to terminal TB-5 and the negative to terminal TB-2. TB-5 input impedance is 120 kΩ. The TB-2 terminals are internally connected 1 4 5 6 11 12 2 14 13A 13B 13C 15 25 2

(+)

30 31 TXA TXB

(-) 0–10 Vdc

Figure 9:

0–10 VDC Connection

3. 4–20 mA: Wire the positive to terminal TB-25 and the negative to terminal TB-2. TB-25 input impedance is 100 Ω. The TB-2 terminals are internally connected 1 4 5 6 11 12 2 14 13A 13B 13C 15 25 2

(-)

30 31 TXA TXB

(+) 4–20 mA

Figure 10: 4–20 mA Connection Speed Reference Selection If you use the analog speed reference input to control the drive controller speed, terminal TB-13A, 13B, or 13C (Parameter 10, 11, or 12) are programmed to select the source for the desired analog input signal. When the TB-13 terminal is connected to TB-4, the drive controller follows the selected analog speed reference input. If an analog speed reference input is not selected on the terminal strip using TB-13A, 13B, or 13C, speed control defaults to standard mode, which is determined by the setting of Parameter 05 - Standard Speed Source. In this mode, the sources of speed control are the ▲ (increase) and ▼ (decrease) buttons on the front of the drive controller (factory default). Speed control can be reassigned to Preset Speed 1 (Parameter 31), a 0–10 Vdc signal, or a 4–20 mA signal. © 1998 Square D All Rights Reserved

21

Page 26

VSD07 Adjustable Speed Drive Controller Control Wiring

Bulletin No. 30072-450-07 November 1998

0–10 Vdc and 4–20 mA Input Signals TB-13A, TB-13B, and TB-13C can be programmed to select a 0–10 Vdc or 4–20 mA analog speed reference input. Preset Speeds TB-13A can be programmed to select Preset Speed 1, TB-13B to select Preset Speed 2, and TB-13C to select Preset Speed 3. There are seven preset speeds, which are activated by different combinations of contact closures between TB-13A, 13B, 13C, and TB-4. See Parameters 31–37 on page 65. Jog TB-13B can be set to Jog Forward or Jog Reverse. The Jog speed is set by Preset Speed 2. Close TB-13B to TB-4 to Jog, and open the contact to Stop.

WARNING LOSS OF CONTROL When operating in Jog mode, the local or remote Stop command does not stop the drive controller. To stop the drive controller, open the contact between TB-13B and TB-4. Failure to follow this instruction can result in death, serious injury, or equipment damage.

NOTE: If the drive controller is commanded to jog while running, the drive controller enters Jog mode and runs at PRESET SPEED 2. When the Jog command is removed, the drive controller stops.

22

© 1998 Square D All Rights Reserved

Page 27

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller Control Wiring

Motor Operated Potentiometer (MOP) / (Floating Point Control) +/- Speed TB-13B and TB-13C are used for this function, which controls the drive controller speed using contacts wired to the terminal strip. Program TB-13B for Decrease Freq., and program TB-13C for Increase Freq. Closing TB-13B to TB-4 activates the Decrease Freq. function, and causes the speed setpoint to decrease until the contact is opened. Closing TB-13C to TB-4 activates the Increase Freq. function, and causes the speed setpoint to increase until the contact is opened. The Increase Freq. function only operates while the drive controller is running.

NOTE: If TB-13A, TB-13B, and TB-13C are all programmed to select speed references, and two or three of the terminals are closed to TB-4, the higher terminal has priority and will override the others. For example, if TB-13A is programmed to select 0–10 Vdc, and TB-13C is programmed to select Preset Speed 3, closing both terminals to TB-4 causes the drive controller to respond to Preset Speed 3, because TB-13C overrides TB-13A. Analog Output Signals Terminal TB-30 provides a 0–10 Vdc or a 2–10 Vdc signal proportional to output frequency or motor load. TB-31 provides the same signals proportional to load only. The 2–10 Vdc signal is converted to a 4–20 mA signal using a resistor in series with the signal such that the total load resistance is 500 Ω. Refer to Parameters 08 and 09 on page 53.

NOTE: These analog output signals cannot be used with “loop-powered” devices that derive power from the 4–20 mA signal.

© 1998 Square D All Rights Reserved

23

Page 28

VSD07 Adjustable Speed Drive Controller Control Wiring

Bulletin No. 30072-450-07 November 1998

Drive Controller Status Digital Outputs There are two open-collector outputs at terminals TB-14 and TB-15. The open-collector circuits are current-sinking types, rated at 30 Vdc and 50 mA maximum. The open-collector outputs are programmed to indicate any of the following: Run, Fault, Inverse Fault, Fault Lockout, At Set Speed, Above Preset Speed 3, Current Limit, Auto Speed Mode, and Reverse. See Parameter 06 on page 52 and Parameter 13 on page 57. Figure 11 illustrates how the 12 Vdc power supply at TB-11 is used with the open-collector output to operate an external relay:

Open Collector

VSD07 Terminal Strip

Diode Snubber (Recommended) + 12 V

TB-11

Relay Coil

TB-14

Figure 11: Connecting an External Relay

24

© 1998 Square D All Rights Reserved

Page 29

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller Control Wiring Diagrams

CONTROL WIRING DIAGRAMS Terminal Strip

WARNING LOSS OF CONTROL When operating in Jog mode, the local or remote Stop command does not stop the drive controller. To stop the drive controller, open the contact between TB-13B and TB-4. Failure to follow this instruction can result in death, serious injury, or equipment damage.

The TB-2 terminals are internally connected

RS-485 Serial Communications

0–10 or 2–10 Vdc Output: Load

Circuit Common

30 31 TXA TXB

0–10 or 2–10 Vdc Output: Frequency

Open-Collector Output

4–20 mA Speed Reference Input

TB-13B Function Select

TB-13C Function Select

Open-Collector Output

TB-13A Function Select

Start Circuit Common

Stop P 15 Vdc 1–10 Vdc Speed Reference Input 10 Vdc Supply for Speed Potentiometer 12 Vdc Supply (50 mA max.)

1 4 5 6 11 12 2 14 13A 13B 13C 15 25 2

Figure 12: Control Terminal Strip

NOTE: The function of terminals TB-13A, TB-13B, TB-13C, TB-14, TB-15, TB-30, and TB-31 are dependent on the programming of certain parameters. Refer to “Description of Parameters” on page 48. Factory Default: 13A, 13B, and 13C set to “none” (01). For additional information on operating the drive controller from the terminal strip, see “Control Wiring” on page 19. Refer to Figures 13, 14, 15, and 16 for the most common wiring configurations. © 1998 Square D All Rights Reserved

25

Page 30

VSD07 Adjustable Speed Drive Controller Control Wiring Diagrams

Bulletin No. 30072-450-07 November 1998

Two-Wire Start/Stop Control Figure 13 shows how to wire one maintained contact for Run and Stop commands.

WARNING LOSS OF CONTROL When operating in Jog mode, the local or remote Stop command does not stop the drive controller. To stop the drive controller, open the contact between TB-13B and TB-4. Failure to follow this instruction can result in death, serious injury, or equipment damage.

The TB-2 terminals are internally connected 30 31 TXA TXB

Common

4–20 mA Input

Reverse

0–10 Vdc or 4–20 mA Select

+

Forward

Stop P 15 Vdc 0–10 Vdc Input

1 4 5 6 11 12 2 14 13A 13B 13C 15 25 2

+ -

Maintained Run/Stop Contact

Figure 13: Two-Wire Start/Stop Control

26

© 1998 Square D All Rights Reserved