The text of a manual · part 2 of 10

VSD07 Adjustable Speed Drive Controller Installation and Operation Manual, pages 11 to 20

Pages 11 to 20 of 100

The original document is the PDF (470 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Square D VSD07

Page 11

Bulletin No. 30072-450-07 November 1998

Table 3: HP 0.25

0.5

1

1.5

2

3

5

VSD07 Adjustable Speed Drive Controller Dimensions

Drive Controller Dimensions

V (Input)

Model

120/208/240

VSD07U07P10

208/240

VSD07U07P20

120/208/240

VSD07U09P10

208/240

VSD07U09P20

400/480

VSD07U09N40

120/208/240

VSD07U18P10

208/240

VSD07U18P20

208/240

VSD07U18M20

400/480

VSD07U18N40

590

VSD07U18S60

208/240

VSD07U25M20

400/408

VSD07U25N40

208/240

VSD07U29M20

400/408

VSD07U29N40

590

VSD07U29S60

208/240

VSD07U41M20

400/480

VSD07U41N40

590

VSD07U41S60

590

VSD07U72S60

© 1998 Square D All Rights Reserved

H

W

D

P

R in (mm) 5.75 (146)

2.88 (73)

3.76 (96)

0.80 (20)

4.37 (111)

5.75 (146)

2.88 (73)

3.76 (96)

0.80 (20)

4.37 (111)

5.75 (146)

3.76 (96)

5.24 (133)

1.90 (48)

4.37 (111)

5.75 (146)

2.88 (73)

4.56 (116)

1.60 (41)

4.37 (111)

5.75 (146)

2.88 (73)

5.56 (141)

2.60 (66)

4.37 (111)

5.75 (146)

2.88 (73)

5.56 (141)

2.60 (66)

3.06 (78)

5.75 (146)

2.88 (73)

5.56 (141)

2.60 (66)

3.06 (78)

5.75 (146)

3.76 (96)

6.74 (171)

3.40 (86)

3.25 (83)

7

Page 12

VSD07 Adjustable Speed Drive Controller Installation

Bulletin No. 30072-450-07 November 1998

INSTALLATION Installation Precautions • The VSD07 drive controller is an open device and must be installed in a suitable enclosure. The environment around the drive controller must not exceed pollution degree 2 requirements as defined in NEMA ICS-1 Annex A, IEC 664, or UL 840. • Figure 2 shows the minimum clearances required around the drive controller for unobstructed airflow; above and below: ≥ 2 in (50 mm), sides: ≥ 1 in (25 mm). These clearances should not be used as a minimum enclosure size. • Mount the drive controller vertically. • Avoid placing the drive controller near any heat sources. • Verify that the voltage and frequency characteristics of the input line match the drive controller nameplate rating. • Drive controllers with dual input voltage ratings must be programmed for the proper supply voltage (see Parameter 01 - Line Voltage Selection in “Description of Parameters” on page 48). • Install a disconnecting means between the input line and drive controller. Follow national and local codes. • Fused overcurrent protection is required on the input line. Use Class CC fuses per Table 1 on page 3. • Turn off all power before installing the drive controller. Place a “DO NOT TURN ON” label on the drive controller disconnect. Before proceeding with installation, lock the disconnect in the open position. • Verify that the motor rating matches the output rating of the drive controller. • For 600 V systems, if no line reactor is installed or if power factor correction is used, contact the Drives Product Support Group at (919) 217-6535.

8

© 1998 Square D All Rights Reserved

Page 13

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller Installation

≥2 (50)

≥1 (25)

≥1 (25)

Dim:

in mm

≥2 (50)

Figure 2:

Clearances and Ventilation

Sizing and Ventilation of NEMA Type 12 (IP54) Metal Enclosure Calculating Enclosure Size To calculate the maximum allowable thermal resistance of the enclosure, Rth (°C/W): T i = Max. internal ambient temp. (°C) around drive controller Ti – To Rth = ----------------P

T o = Max. external ambient temp. (°C) around enclosure P = Total power dissipated in enclosure (W) (see Table 1 on pages 3–4)

NOTE: Deration is required for carrier frequency ≥ 6 kHz. See page 49.

© 1998 Square D All Rights Reserved

9

Page 14

VSD07 Adjustable Speed Drive Controller Installation

Bulletin No. 30072-450-07 November 1998

Useful heat exchange surface area, S (in2), of a wall-mounted enclosure consists of the sides, top, and front. To calculate minimum surface area required for the enclosure:

K S = -------Rth

Rth = Thermal resistance of the enclosure (calculated previously) K = Thermal resistance per square inch of the enclosure K = 186 with enclosure fan K = 233 without enclosure fan

When sizing the enclosure: • Use only metallic enclosures which have good thermal conduction. • This calculation does not consider any external heat sources. Do not install enclosures where external heat sources (such as direct sunlight) can add to enclosure heat load. • If additional devices are inside the enclosure, include the heat load of the devices in the calculation. • The useful area for convection cooling of the enclosure varies depending upon the method of mounting. You must allow for free air movement over all surfaces considered for convection cooling. Example calculation of the enclosure size for a VSD07U18M20 drive controller mounted in a Type 12 enclosure: • • • •

Maximum external temperature: To = 25 °C Power dissipated inside enclosure: P = 43 W Maximum internal temperature: Ti = 50 °C for carrier frequency ≥ 6 kHz Thermal resistance per square inch of enclosure: K = 186

Maximum allowable thermal resistance, Rth: 50 °C – 25 °C Rth = ----------------------------------- = 0.58 °C/W 43 W

10

© 1998 Square D All Rights Reserved

Page 15

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller Installation

Minimum useful heat exchange surface area, S: 186 2 S = ----------- = 320 in 0.58

Useful heat exchange surface area (S) of the proposed wall-mounted enclosure: • Height: 9 in • Width: 6 in • Depth: 10 in front area top area side area

S = (9 x 6) + (9 x 10) + 2(9 x 10) = 324 in2 The enclosure must provide the required surface area and must also meet your application needs. If it does not, you must do one of the following: • Use a larger enclosure. • Add a passive heat exchanger to the enclosure. • Add an air conditioning unit to the enclosure. Ventilation When mounting the drive controller inside a Type 12 or IP54 enclosure: • Observe minimum clearance distances shown in Figure 2 on page 9. • Follow the “Installation Precautions” on page 8. • If necessary, install a stirring fan to circulate the air inside the enclosure and to distribute the heat uniformly. If there is a possibility of condensation, keep the control supply switched on during periods when the motor is not running or install thermostatically controlled strip heaters.

© 1998 Square D All Rights Reserved

11

Page 16

VSD07 Adjustable Speed Drive Controller General Wiring Practices

Bulletin No. 30072-450-07 November 1998

GENERAL WIRING PRACTICES Power wiring to the motor must have the maximum possible separation from all other power wiring, whether from the same drive controller or other drive controllers; do not run power and control wiring in the same conduit. This separation reduces the possibility of coupling electrical transients from power circuits into control circuits, or from motor power wiring into other power circuits.

CAUTION EQUIPMENT DAMAGE HAZARD Follow wiring practices described in this document in addition to those already required by the applicable electrical codes. Failure to follow this instruction can result in injury or equipment damage. When wiring VSD07 drive controllers: • Use metallic conduit for all drive controller wiring. Do not run control and power wiring in the same conduit. • Separate metallic conduits carrying power wiring or low-level control wiring by at least 3 in (7.62 cm). • Separate non-metallic conduits or cable trays used to carry power wiring from metallic conduit carrying low-level control wiring by at least 12 in (30.5 cm). • Whenever power and control wiring cross, the metallic conduits and non-metallic conduits or trays must cross at right angles. • Wire and ground in accordance with the National Electrical Code (NEC) or Canadian Electrical Code (CEC), and all applicable local codes. • Do not install contactors between the drive controller and the motor as this may result in drive controller damage. • Use only UL Listed and CSA Certified wire.

12

© 1998 Square D All Rights Reserved

Page 17

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller General Wiring Practices

• Minimum wire voltage ratings: 300 V for 120, 208, and 240 Vac systems, and 600 V for 400, 480, and 590 Vac systems. • Use copper wire with a minimum of 75 ˚C insulation rating. • Strip off 0.20 to 0.25 in (5.1 to 6.4 mm) of insulation for input power, output power, and DC Bus wiring. Branch Circuit Connections All branch circuit components and equipment (such as transformers, feeder cables, disconnect devices, and protective devices) must be rated for the maximum input current of the VSD07 drive controller, not the motor full load current. The drive controller input current is stamped on the nameplate.

WARNING OVERCURRENT PROTECTIVE DEVICES MUST BE PROPERLY COORDINATED • To achieve published fault withstand current ratings, install the specified fuses. • Do not connect drive controller to power feeder whose short circuit capacity exceeds drive controller withstand fault rating. See Table 1 on page 3. Failure to follow these instructions can result in death, serious injury, or equipment damage.

© 1998 Square D All Rights Reserved

13

Page 18

VSD07 Adjustable Speed Drive Controller General Wiring Practices

Bulletin No. 30072-450-07 November 1998

Output Wiring Precautions

WARNING DRIVE CONTROLLER DAMAGE Drive controller will be damaged if input line voltage is applied to output terminals (T1, T2, T3). Check power connections before energizing drive controller. Failure to follow this instruction can result in death, serious injury, or equipment damage. The drive controller is sensitive to the amount of capacitance (either phase-to-phase or phase-to-ground) present on the output power conductors. If excessive capacitance is present, the drive controller may trip on overcurrent. Follow the guidelines below when selecting output power cable: • Cable type: the cable selected must have a low capacitance phase-tophase and to ground. Do not use mineral-impregnated cable because it has a very high capacitance. Immersion of cables in water increases capacitance. • Cable length: the longer the cable, the greater the capacitance. Maximum recommended cable length: 100 ft (30.5 mm). A minimum inductance is required to protect the drive controller output from short circuits. Provide at least 24 in (61 cm) of cable at drive controller output (T1, T2, T3). • Proximity to other output cables: because of the high frequency switching and increased capacitance, the drive controller may fault under some conditions. • Do not use lightning arrestors or power factor correction capacitors on the output of the drive controller. • All three power output wires, from terminals T1, T2, and T3 to the motor, must be kept tightly bundled and run in a separate metallic conduit away from all other power and control wiring.

14

© 1998 Square D All Rights Reserved

Page 19

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller General Wiring Practices

CAUTION DRIVE CONTROLLER SWITCH FAILURE For proper electronic short circuit protection of the drive controller, certain values of inductance may be required in the output power wiring. Inductance can be supplied by the power wiring or auxiliary inductors. Failure to follow this instruction can result in equipment damage. Grounding Ground the drive controller according to these instructions and to applicable electrical codes. To ground the drive controller: • Connect a copper wire from the equipment ground terminal to the power system ground conductor. Wire size is determined by the drive controller size and by electrical codes. • Verify that resistance to ground is 1 Ω or less. Improper grounding causes intermittent and unreliable operation.

DANGER HAZARDOUS VOLTAGE • Properly ground the drive controller panel before applying power. • Do not use metallic conduits as a ground conductor. Failure to follow these instructions will result in death, serious injury, or equipment damage. Ground multiple drive controllers as shown in Figure 3. Do not loop or series the ground cables.

© 1998 Square D All Rights Reserved

15

Page 20

VSD07 Adjustable Speed Drive Controller General Wiring Practices

Bulletin No. 30072-450-07 November 1998

YES

NO

Drive Controller

Drive Controller

Drive Controller

Drive Controller

Drive Controller

Drive Controller

Drive Controller

Drive Controller

Drive Controller

Figure 3:

Grounding Multiple Drive Controllers

Wiring for Single-Phase or Three-Phase Input For 120 Vac, wire the input to terminals L1 and N. For 208/240 Vac, wire the input to terminals L1 and L2. See Figures 4 and 5 on page 17. If the drive controller is rated for single- and three-phase input, wire to terminals L1 and L2 for single-phase input, or wire to terminals L1, L2, and L3 for three-phase input. If the drive controller is rated for three-phase input, wire the input to terminals L1, L2, and L3. Refer to Figure 6.

16