For the Square D VSD07
Page 1
Instruction Bulletin
30072-450-07 November 1998 Raleigh, NC, USA
VSD07 Adjustable Speed Drive Controller Installation and Operation Manual
Page 2
DANGER HAZARDOUS VOLTAGE • Read and understand this bulletin in its entirety before installing or operating VSD07 drive controllers. Installation, adjustment, and maintenance of these drive controllers must be performed by qualified personnel. • Disconnect all power before servicing drive controller. WAIT THREE MINUTES until DC bus capacitors discharge, then measure DC bus capacitor voltage as described in “Appendix D - Bus Voltage Measurement Procedure” on page 89 to verify that DC voltage is less than 45 V. The display is not an accurate indication of the absence of DC bus voltage. • DO NOT short across the DC bus capacitors or touch terminal strip screw connections with voltage present. • No servicable components are inside. DO NOT remove cover. • User is responsible for conforming to all applicable code requirements with respect to grounding all equipment. • Use only electrically insulated tools. If the drive controller must be replaced: • Disconnect all power. • Place a “DO NOT TURN ON” label on drive controller disconnect. • Lock disconnect in open position. Electrical shock will result in death or serious injury.
Page 3
Bulletin No. 30072-450-07 November 1998
VSD07 Adjustable Speed Drive Controller Table of Contents
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Scope of Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Revision Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 HANDLING THE DRIVE CONTROLLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Receiving and Preliminary Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Storing and Shipping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 TECHNICAL CHARACTERISTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Installation Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Sizing and Ventilation of NEMA Type 12 (IP54) Metal Enclosure . . . . . . . . . . . . 9 Calculating Enclosure Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 GENERAL WIRING PRACTICES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Branch Circuit Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Output Wiring Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Wiring for Single Phase or Three Phase Input . . . . . . . . . . . . . . . . . . . . . . . . . . 16 POWER WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Equipment Ground Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Using a Line Contactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 CONTROL WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Control Wiring vs. Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 TB-2: Circuit Common . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 TB-4: P 15 Vdc . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Surge Suppression on Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Start/Stop Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Speed Reference Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
© 1998 Square D All Rights Reserved i
Page 4
VSD07 Adjustable Speed Drive Controller Table of Contents
Bulletin No. 30072-450-07 November 1998
Speed Reference Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 0–10 Vdc and 4–20 mA Input Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Preset Speeds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Jog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Motor Operated Potentiometer (MOP) Floating Point Control +/- Speed . . . 23 Analog Output Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Drive Controller Status Digital Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 CONTROL WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Terminal Strip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Two-Wire Start/Stop Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Alternate Two-Wire Start/Stop Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Three-Wire Start/Stop Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Speed Potentiometer and Preset Speed Control . . . . . . . . . . . . . . . . . . . . . . . . 32 MOTOR THERMAL OVERLOAD PROTECTION . . . . . . . . . . . . . . . . . . . . . . . . . . 33 AVAILABLE TORQUE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 INITIAL POWER UP AND MOTOR ROTATION . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 PROGRAMMING THE DRIVE CONTROLLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Entering the Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Setting the Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Programming Direct-Entry Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Electronic Programming Module (EPM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 PARAMETER MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 DESCRIPTION OF PARAMETERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 APPENDIX A - PARAMETER VALUE TABLES . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 APPENDIX B - DISPLAY MESSAGES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 Speed Setpoint Display Stop State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 Speed Display in a Run State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 Speed Display When the Speed is 100 Hz or Greater . . . . . . . . . . . . . . . . . . . . 84 Speed Source Displays and Status Messages . . . . . . . . . . . . . . . . . . . . . . . . . . 85 APPENDIX C - TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 APPENDIX D - BUS VOLTAGE MEASUREMENT PROCEDURE . . . . . . . . . . . . . 89 ii
© 1998 Square D All Rights Reserved
Page 5
Bulletin No. 30072-450-07 November 1998
VSD07 Adjustable Speed Drive Controller Introduction
INTRODUCTION Scope of Manual The VSD07 Adjustable Speed Drive Controller from Square D is a series of drive controllers for three-phase asynchronous motors. The VSD07 series is comprised of the following: • 0.25 to 1 hp (0.20 to 0.75 kW), 120/208/240 Vac, single-phase input; 230/200/230 Vac, three-phase output • 0.25 to 3 hp (0.20 to 2.2 kW), 208/240 Vac, three-phase input • 0.5 to 3 hp (0.37 to 2.2 kW), 400/480 Vac, three-phase input • 1 to 5 hp (0.75 to 3.7 kW), 590 Vac, three-phase input This instruction bulletin covers the technical characteristics, specifications, installation, and wiring of all VSD07 series drive controllers. Revision Level This is a new document.
© 1998 Square D All Rights Reserved
1
Page 6
VSD07 Adjustable Speed Drive Controller Handling the Drive Controller
Bulletin No. 30072-450-07 November 1998
HANDLING THE DRIVE CONTROLLER Receiving and Preliminary Inspection Before installing the VSD07 drive controller, read this manual and follow all precautions: • Before removing the drive controller from its packing material, verify that it is not damaged from shipping. Any damage to the packing carton usually indicates improper handling. If any damage is found, notify the carrier and your Square D representative. • After removing the drive controller from its packaging, visually inspect the exterior for shipping damage. If any shipping damage is found, notify the carrier and your sales representative. • Verify that the drive controller nameplate and label conform to the packing slip and corresponding purchase order.
CAUTION EQUIPMENT DAMAGE HAZARD Do not operate or install any drive controller that appears damaged. Failure to follow this instruction can result in injury or equipment damage.
Storing and Shipping If the drive controller is not immediately installed, store it in a clean, dry area where the ambient temperature is between -20 and +70 °C (-4 to +158 °F). If the drive controller is shipped to another location, use the original shipping material and carton to protect the drive controller.
2
© 1998 Square D All Rights Reserved
Page 7
Bulletin No. 30072-450-07 November 1998
VSD07 Adjustable Speed Drive Controller Technical Characteristics
TECHNICAL CHARACTERISTICS Table 1:
Ratings
Drive Controller
Motor Power
Catalog No.
hp kW
Total 3-Phase Short RecomDissiRated Output Circuit mended pated Current (A) [1, 2] Rating Fuse Power 120–240 VAC Controllers w/ 1-Phase Input Input Line Current (A)
No. of Phases
Input (VAC) 120
208 240
Output (VAC) 230
200
W
230 kAIC Class CC rms sym.
VSD07U07P10 0.25 0.20
1
6.0
3.5
3.0
1.4
1.6
1.4
20
1
10 A, 600 V
VSD07U09P10 0.5 0.37
1
9.2
5.3
4.6
2.2
2.5
2.2
27
1
15 A, 600 V
VSD07U18P10
1
15.8
9.1
7.9
4.0
4.6
4.0
45
1
25 A, 600 V
1
0.75
208–240 VAC Controllers w/ 1-Phase or 3-Phase Input Catalog No.
hp kW
VSD07U07P20 0.25 0.20 VSD07U09P20 0.5 0.37
Input (VAC)
No. of Phases
208
240
1
3.6
3.2
3
1.9
1.7
1
5.4
4.7
3
3.1
2.7
1
9.7
8.4
3
5.5
4.8
VSD07U18P20
1
0.75
VSD07U18M20
1
0.75
3
5.5
VSD07U25M20 1.5
1.1
3
VSD07U29M20
2
1.5
VSD07U41M20
3
2.2
Output (VAC) 200
230
1.6
1.4
2.5
W
2.2 kAIC Class CC rms sym.
19
1
19
1
10 A, 600 V 10 A, 600 V
26
1
10 A, 600 V
26
1
10 A, 600 V
47
1
15 A, 600 V
4.6
4.0
47
1
15 A, 600 V
4.8
4.6
4.0
39
1
10 A, 600 V
7.1
6.3
6.2
5.4
62
1
12 A, 600V
3
9.1
7.9
7.8
6.8
78
1
15 A, 600V
3
12.4
10.8
11.0
9.6
117
1
20 A, 600V
400–480 VAC Controllers w/ 3-Phase Input Catalog No.
hp kW
No. of Phases
Input (VAC) 400
480
Output (VAC) 400
460
W kAIC Class CC rms sym.
VSD07U09N40 0.5 0.37
3
1.6
1.4
1.3
1.1
26
1
10 A, 600 V
VSD07U18N40
3
2.8
2.4
2.3
2.0
41
1
10 A, 600 V
1
0.75
VSD07U25N40 1.5
1.1
3
3.6
3.2
3.1
2.7
51
1
10 A, 600 V
VSD07U29N40
2
1.5
3
4.6
4.0
3.9
3.4
67
1
10 A, 600 V
VSD07U41N40
3
2.2
3
6.2
5.4
5.5
4.8
101
1
10 A, 600 V
[1] The maximum transient output current setting is either 180% or 150% of the rated output current, depending on whether Line Voltage Selection (Parameter 01) is set to High or Low. [2] Input voltage corresponds to output voltage as follows: 120 V → 230 V 400 V → 400 V © 1998 Square D All Rights Reserved
208 V → 200 V 480 V → 460 V
240 V → 230 V 590 V → 575 V 3
Page 8
VSD07 Adjustable Speed Drive Controller Technical Characteristics
Table 1:
Bulletin No. 30072-450-07 November 1998
Ratings (continued)
Drive Controller
Motor Power
Input Line Current (A)
Total Short RecomDissiCircuit mended pated Rating Fuse Power
3-Phase Rated Output Current (A)[1]
590 VAC Controllers w/ 3-Phase Input Input (VAC)
Output (VAC)
590
575
3
1.9
1.6
43
1
10 A, 600 V
3
3.5
3.0
63
1
10 A, 600 V
2.2
3
4.7
4.2
96
1
10 A, 600 V
3.7
3
7.4
6.6
154
1
10 A, 600 V
Catalog No.
hp
No. of kW Phases
VSD07U18S60
1
0.75
VSD07U29S60
2
1.5
VSD07U41S60
3
VSD07U72S60
5
W kAIC Class CC rms sym.
[1] The maximum transient output current setting is either 180% or 150% of the rated output current, depending on whether Line Voltage Selection (Parameter 01) is set to High or Low.
Table 2:
Specifications
Environment Degree of protection
IP20
Resistance to vibration/shock. Applies to all but 3 hp and 5 hp 590 V drive controllers, and 1 hp, 120–240 Vac, single-phase drive controllers (VSD07U18P10).
Vibration:
1.5 mm peak-to-peak from 7 to 13 Hz 1.0 mm peak-to-peak from 13 to 22.3 Hz 2 g from 22.3 to 150 Hz IEC 88-2-6
Shock:
15 g, 11 ms, half sine, IEC 68-2-27
Pollution degree
Pollution degree 2 according to NEMA ICS-1, IEC 664, and UL 840
Maximum relative humidity
95% maximum, non-condensing and without dripping (provide heating system if there is condensation) -4 to +158 °F (-20 to +70 °C) 32 to +122 °F (0 to +50 °C) with carrier frequency < 6 kHz. See page 50.
Maximum ambient temperature
Storage: Operation:
Altitude
Up to 3,300 ft (1,000 m) without derating
4
© 1998 Square D All Rights Reserved
Page 9
Bulletin No. 30072-450-07 November 1998
Table 2:
VSD07 Adjustable Speed Drive Controller Technical Characteristics
Specifications (continued)
Electrical Characteristics
Input voltage
VSD07U••P10: VSD07U••P20: VSD07U••M20: VSD07U••N40: VSD07U••S60: Tolerance (all models):
Input frequency
48 to 62 Hz
Input phases
VSD07U••P10: VSD07U••P20: VSD07U••M20, N40 & S60:
Output voltage
See Table 1 on page 3.
120/208/240 Vac, 1-phase 208/240 Vac, 1- or 3-phase 208/240 Vac, 3-phase 400/480 Vac, 3-phase 590 Vac, 3-phase +10% / -15%
1 1 or 3 3
Output frequency
0 to 120 Hz, sine coded pulse width modulation (PWM)
Output phases
3
Switching frequency
Adjustable from 4 kHz, 6 kHz, 8 kHz, 10 kHz. Refer to “02 - Carrier Frequency” on pages 48 to 49 for deration if carrier frequency is ≥ 6 kHz.
Service factor
1.00
Efficiency
98%
Power factor (displacement)
0.96
Max. transient current
150% of nominal drive controller current for 60 s 180% of nominal drive controller current for 32 s Determined by line voltage setting.
Speed reference follower
0–10 Vdc, 4–20 mA
Control voltage
5 logic inputs (TB1, TB12, TB-13A, TB-13B & TB-13C), 15 Vdc
Power supply for auxiliary relays
50 mA at 12 Vdc
Analog outputs
0–10 Vdc or 2–10 Vdc Proportional to frequency or motor load. See page 23.
Digital outputs
Open-collector outputs: 50 mA at 30 Vdc
Motor protection
Protection integrated in the drive controller by I2t calculation, Class 10. See page 33.
© 1998 Square D All Rights Reserved
5
Page 10
VSD07 Adjustable Speed Drive Controller Dimensions
Bulletin No. 30072-450-07 November 1998
DIMENSIONS
0.38 10
H
R
W Dim:
in mm
0.38 10
0.18 4.6
D
P
Dia. Slot 0.19
4.8
Mounting Tab Detail
Figure 1:
6
VSD07 Adjustable Speed Drive Controller Dimensions
© 1998 Square D All Rights Reserved