VSD07 Adjustable Speed Drive Controller Installation and Operation Manual, pages 1 to 10

Pages 1 to 10 of 100

The original document is the PDF (470 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Square D VSD07

Page 1

Instruction Bulletin

30072-450-07 November 1998 Raleigh, NC, USA

VSD07 Adjustable Speed Drive Controller Installation and Operation Manual

Page 2

DANGER HAZARDOUS VOLTAGE • Read and understand this bulletin in its entirety before installing or operating VSD07 drive controllers. Installation, adjustment, and maintenance of these drive controllers must be performed by qualified personnel. • Disconnect all power before servicing drive controller. WAIT THREE MINUTES until DC bus capacitors discharge, then measure DC bus capacitor voltage as described in “Appendix D - Bus Voltage Measurement Procedure” on page 89 to verify that DC voltage is less than 45 V. The display is not an accurate indication of the absence of DC bus voltage. • DO NOT short across the DC bus capacitors or touch terminal strip screw connections with voltage present. • No servicable components are inside. DO NOT remove cover. • User is responsible for conforming to all applicable code requirements with respect to grounding all equipment. • Use only electrically insulated tools. If the drive controller must be replaced: • Disconnect all power. • Place a “DO NOT TURN ON” label on drive controller disconnect. • Lock disconnect in open position. Electrical shock will result in death or serious injury.

Page 3

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller Table of Contents

INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Scope of Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Revision Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 HANDLING THE DRIVE CONTROLLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Receiving and Preliminary Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Storing and Shipping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 TECHNICAL CHARACTERISTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Installation Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Sizing and Ventilation of NEMA Type 12 (IP54) Metal Enclosure . . . . . . . . . . . . 9 Calculating Enclosure Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 GENERAL WIRING PRACTICES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Branch Circuit Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Output Wiring Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Wiring for Single Phase or Three Phase Input . . . . . . . . . . . . . . . . . . . . . . . . . . 16 POWER WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Equipment Ground Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Using a Line Contactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 CONTROL WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Control Wiring vs. Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 TB-2: Circuit Common . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 TB-4: P 15 Vdc . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Surge Suppression on Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Start/Stop Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Speed Reference Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

© 1998 Square D All Rights Reserved i

Page 4

VSD07 Adjustable Speed Drive Controller Table of Contents

Bulletin No. 30072-450-07 November 1998

Speed Reference Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 0–10 Vdc and 4–20 mA Input Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Preset Speeds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Jog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Motor Operated Potentiometer (MOP) Floating Point Control +/- Speed . . . 23 Analog Output Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Drive Controller Status Digital Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 CONTROL WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Terminal Strip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Two-Wire Start/Stop Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Alternate Two-Wire Start/Stop Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Three-Wire Start/Stop Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Speed Potentiometer and Preset Speed Control . . . . . . . . . . . . . . . . . . . . . . . . 32 MOTOR THERMAL OVERLOAD PROTECTION . . . . . . . . . . . . . . . . . . . . . . . . . . 33 AVAILABLE TORQUE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 INITIAL POWER UP AND MOTOR ROTATION . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 PROGRAMMING THE DRIVE CONTROLLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Entering the Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Setting the Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Programming Direct-Entry Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Electronic Programming Module (EPM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 PARAMETER MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 DESCRIPTION OF PARAMETERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 APPENDIX A - PARAMETER VALUE TABLES . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 APPENDIX B - DISPLAY MESSAGES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 Speed Setpoint Display Stop State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 Speed Display in a Run State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 Speed Display When the Speed is 100 Hz or Greater . . . . . . . . . . . . . . . . . . . . 84 Speed Source Displays and Status Messages . . . . . . . . . . . . . . . . . . . . . . . . . . 85 APPENDIX C - TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 APPENDIX D - BUS VOLTAGE MEASUREMENT PROCEDURE . . . . . . . . . . . . . 89 ii

© 1998 Square D All Rights Reserved

Page 5

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller Introduction

INTRODUCTION Scope of Manual The VSD07 Adjustable Speed Drive Controller from Square D is a series of drive controllers for three-phase asynchronous motors. The VSD07 series is comprised of the following: • 0.25 to 1 hp (0.20 to 0.75 kW), 120/208/240 Vac, single-phase input; 230/200/230 Vac, three-phase output • 0.25 to 3 hp (0.20 to 2.2 kW), 208/240 Vac, three-phase input • 0.5 to 3 hp (0.37 to 2.2 kW), 400/480 Vac, three-phase input • 1 to 5 hp (0.75 to 3.7 kW), 590 Vac, three-phase input This instruction bulletin covers the technical characteristics, specifications, installation, and wiring of all VSD07 series drive controllers. Revision Level This is a new document.

© 1998 Square D All Rights Reserved

1

Page 6

VSD07 Adjustable Speed Drive Controller Handling the Drive Controller

Bulletin No. 30072-450-07 November 1998

HANDLING THE DRIVE CONTROLLER Receiving and Preliminary Inspection Before installing the VSD07 drive controller, read this manual and follow all precautions: • Before removing the drive controller from its packing material, verify that it is not damaged from shipping. Any damage to the packing carton usually indicates improper handling. If any damage is found, notify the carrier and your Square D representative. • After removing the drive controller from its packaging, visually inspect the exterior for shipping damage. If any shipping damage is found, notify the carrier and your sales representative. • Verify that the drive controller nameplate and label conform to the packing slip and corresponding purchase order.

CAUTION EQUIPMENT DAMAGE HAZARD Do not operate or install any drive controller that appears damaged. Failure to follow this instruction can result in injury or equipment damage.

Storing and Shipping If the drive controller is not immediately installed, store it in a clean, dry area where the ambient temperature is between -20 and +70 °C (-4 to +158 °F). If the drive controller is shipped to another location, use the original shipping material and carton to protect the drive controller.

2

© 1998 Square D All Rights Reserved

Page 7

Bulletin No. 30072-450-07 November 1998

VSD07 Adjustable Speed Drive Controller Technical Characteristics

TECHNICAL CHARACTERISTICS Table 1:

Ratings

Drive Controller

Motor Power

Catalog No.

hp kW

Total 3-Phase Short RecomDissiRated Output Circuit mended pated Current (A) [1, 2] Rating Fuse Power 120–240 VAC Controllers w/ 1-Phase Input Input Line Current (A)

No. of Phases

Input (VAC) 120

208 240

Output (VAC) 230

200

W

230 kAIC Class CC rms sym.

VSD07U07P10 0.25 0.20

1

6.0

3.5

3.0

1.4

1.6

1.4

20

1

10 A, 600 V

VSD07U09P10 0.5 0.37

1

9.2

5.3

4.6

2.2

2.5

2.2

27

1

15 A, 600 V

VSD07U18P10

1

15.8

9.1

7.9

4.0

4.6

4.0

45

1

25 A, 600 V

1

0.75

208–240 VAC Controllers w/ 1-Phase or 3-Phase Input Catalog No.

hp kW

VSD07U07P20 0.25 0.20 VSD07U09P20 0.5 0.37

Input (VAC)

No. of Phases

208

240

1

3.6

3.2

3

1.9

1.7

1

5.4

4.7

3

3.1

2.7

1

9.7

8.4

3

5.5

4.8

VSD07U18P20

1

0.75

VSD07U18M20

1

0.75

3

5.5

VSD07U25M20 1.5

1.1

3

VSD07U29M20

2

1.5

VSD07U41M20

3

2.2

Output (VAC) 200

230

1.6

1.4

2.5

W

2.2 kAIC Class CC rms sym.

19

1

19

1

10 A, 600 V 10 A, 600 V

26

1

10 A, 600 V

26

1

10 A, 600 V

47

1

15 A, 600 V

4.6

4.0

47

1

15 A, 600 V

4.8

4.6

4.0

39

1

10 A, 600 V

7.1

6.3

6.2

5.4

62

1

12 A, 600V

3

9.1

7.9

7.8

6.8

78

1

15 A, 600V

3

12.4

10.8

11.0

9.6

117

1

20 A, 600V

400–480 VAC Controllers w/ 3-Phase Input Catalog No.

hp kW

No. of Phases

Input (VAC) 400

480

Output (VAC) 400

460

W kAIC Class CC rms sym.

VSD07U09N40 0.5 0.37

3

1.6

1.4

1.3

1.1

26

1

10 A, 600 V

VSD07U18N40

3

2.8

2.4

2.3

2.0

41

1

10 A, 600 V

1

0.75

VSD07U25N40 1.5

1.1

3

3.6

3.2

3.1

2.7

51

1

10 A, 600 V

VSD07U29N40

2

1.5

3

4.6

4.0

3.9

3.4

67

1

10 A, 600 V

VSD07U41N40

3

2.2

3

6.2

5.4

5.5

4.8

101

1

10 A, 600 V

[1] The maximum transient output current setting is either 180% or 150% of the rated output current, depending on whether Line Voltage Selection (Parameter 01) is set to High or Low. [2] Input voltage corresponds to output voltage as follows: 120 V → 230 V 400 V → 400 V © 1998 Square D All Rights Reserved

208 V → 200 V 480 V → 460 V

240 V → 230 V 590 V → 575 V 3

Page 8

VSD07 Adjustable Speed Drive Controller Technical Characteristics

Table 1:

Bulletin No. 30072-450-07 November 1998

Ratings (continued)

Drive Controller

Motor Power

Input Line Current (A)

Total Short RecomDissiCircuit mended pated Rating Fuse Power

3-Phase Rated Output Current (A)[1]

590 VAC Controllers w/ 3-Phase Input Input (VAC)

Output (VAC)

590

575

3

1.9

1.6

43

1

10 A, 600 V

3

3.5

3.0

63

1

10 A, 600 V

2.2

3

4.7

4.2

96

1

10 A, 600 V

3.7

3

7.4

6.6

154

1

10 A, 600 V

Catalog No.

hp

No. of kW Phases

VSD07U18S60

1

0.75

VSD07U29S60

2

1.5

VSD07U41S60

3

VSD07U72S60

5

W kAIC Class CC rms sym.

[1] The maximum transient output current setting is either 180% or 150% of the rated output current, depending on whether Line Voltage Selection (Parameter 01) is set to High or Low.

Table 2:

Specifications

Environment Degree of protection

IP20

Resistance to vibration/shock. Applies to all but 3 hp and 5 hp 590 V drive controllers, and 1 hp, 120–240 Vac, single-phase drive controllers (VSD07U18P10).

Vibration:

1.5 mm peak-to-peak from 7 to 13 Hz 1.0 mm peak-to-peak from 13 to 22.3 Hz 2 g from 22.3 to 150 Hz IEC 88-2-6

Shock:

15 g, 11 ms, half sine, IEC 68-2-27

Pollution degree

Pollution degree 2 according to NEMA ICS-1, IEC 664, and UL 840

Maximum relative humidity

95% maximum, non-condensing and without dripping (provide heating system if there is condensation) -4 to +158 °F (-20 to +70 °C) 32 to +122 °F (0 to +50 °C) with carrier frequency < 6 kHz. See page 50.

Maximum ambient temperature

Storage: Operation:

Altitude

Up to 3,300 ft (1,000 m) without derating

4

© 1998 Square D All Rights Reserved

Page 9

Bulletin No. 30072-450-07 November 1998

Table 2:

VSD07 Adjustable Speed Drive Controller Technical Characteristics

Specifications (continued)

Electrical Characteristics

Input voltage

VSD07U••P10: VSD07U••P20: VSD07U••M20: VSD07U••N40: VSD07U••S60: Tolerance (all models):

Input frequency

48 to 62 Hz

Input phases

VSD07U••P10: VSD07U••P20: VSD07U••M20, N40 & S60:

Output voltage

See Table 1 on page 3.

120/208/240 Vac, 1-phase 208/240 Vac, 1- or 3-phase 208/240 Vac, 3-phase 400/480 Vac, 3-phase 590 Vac, 3-phase +10% / -15%

1 1 or 3 3

Output frequency

0 to 120 Hz, sine coded pulse width modulation (PWM)

Output phases

3

Switching frequency

Adjustable from 4 kHz, 6 kHz, 8 kHz, 10 kHz. Refer to “02 - Carrier Frequency” on pages 48 to 49 for deration if carrier frequency is ≥ 6 kHz.

Service factor

1.00

Efficiency

98%

Power factor (displacement)

0.96

Max. transient current

150% of nominal drive controller current for 60 s 180% of nominal drive controller current for 32 s Determined by line voltage setting.

Speed reference follower

0–10 Vdc, 4–20 mA

Control voltage

5 logic inputs (TB1, TB12, TB-13A, TB-13B & TB-13C), 15 Vdc

Power supply for auxiliary relays

50 mA at 12 Vdc

Analog outputs

0–10 Vdc or 2–10 Vdc Proportional to frequency or motor load. See page 23.

Digital outputs

Open-collector outputs: 50 mA at 30 Vdc

Motor protection

Protection integrated in the drive controller by I2t calculation, Class 10. See page 33.

© 1998 Square D All Rights Reserved

5

Page 10

VSD07 Adjustable Speed Drive Controller Dimensions

Bulletin No. 30072-450-07 November 1998

DIMENSIONS

0.38 10

H

R

W Dim:

in mm

0.38 10

0.18 4.6

D

P

Dia. Slot 0.19

4.8

Mounting Tab Detail

Figure 1:

6

VSD07 Adjustable Speed Drive Controller Dimensions

© 1998 Square D All Rights Reserved