Installation, Operating & Maintenance COMPACT 4 Piston Pneumatic Actuator
GENERAL This Installation, Operation & Maintenance manual covers the instructions required for safe use of the Compact pneumatic actuator. Read the entire IOM before using this product.
Sizes Included:
WARNINGS & SAFETY INSTRUCTIONS The user of this product must know and follow all applicable - - these types of actuators. Improper use of the product may result in injuries or property damage. Refer to the Habonim Compact catalogue for additional product safety information or contact Habonim. 1. Assure that the actuator is isolated from the air supply or electrical ancillaries before attempting to perform any maintenance. 2. Before disconnecting the actuator from a valve, always be sure the line has been depressurized and drained. Cycle the valve a few times to relieve any pressure that could be trapped in the body cavity. 3. Utmost caution must be taken when handling the actuator.
have read these instructions should disassemble or assemble the actuator. 4. Before operating an actuator which is connected to a valve in the pipeline make sure you know the valve function. 5. Do not attempt to remove the actuator pistons by use of air pressure when the covers have been removed. 6. Do not leave any grip key or shaft connection attached to the actuator, or try to manually operate the actuator while it is still connected to the air pressure. 7. Use the actuator within the pressure and temperature - product catalogue and IOM. 8. The operator must follow and observe any national or local safety laws and regulations. 9. Any product warranty will be invalidated in the case of improper operation resulting from misapplication or faulty maintenance. 10. Habonim bears no responsibility for external accessories attached to the Compact actuator.
C15, C20, C25, C30, C30M, C35,C35M,C45, C45M,C60,
ISSUE H-03/14
C60M, C75, C75M
Kfar Hanassi, Upper Galilee 12305 Israel
Tel: 972-4-6914911 Fax: 972-4-6914902 habonim@habonim.co.il www.habonim.com
Page 1
Page 2
Installation, Operating & Maintenance instructions STORAGE The Compact actuator has been packaged to provide protection during shipment, however, it can be damaged in transport. Prior to storage, inspect the actuator for shipping damage. Keep the actuators in their original packing box during storage. It is recommended to keep the actuators in a clean and dry environment until ready for use. The actuator has two air ports, which should be plugged during storage to prevent liquids or other materials from entering the actuator during storage. If the actuators are to be stored for a long period of time before installation, it is recommended to cycle them periodically to prevent setting of the seals. Store the actuators indoors to protect them from humidity and dust.
'X' -- J `"#;<%' 4. Actuators that may be located in Zone 0 or Zone 20 potentially explosive atmospheres must be installed such that they are protected from risk of impact. Actuators shall be subject to routine inspection and replaced or repaired should any damage to the surface coating be noted. "' - * from a source known to be non-hazardous and free from ingress of foreign objects or liquids. 6. User shall ensure any lubrication medium used has an "#$ maximum surface temperature of installed equipment and be resistant to carbonization.
OPERATING CONDITIONS Lubricants The actuators come lubricated from the factory and under normal operating conditions do not require re-lubrication. In the event of actuator maintenance it is recommended to use the following lubricants: For NBR O-rings use EP1. The lubricant is suitable for use from -20°C (-4°F) to +80°C (+176°F) ! "#$%' For Viton O-rings use Molykote 111 or OKS 1110 or Phalanx EP1. - !?"#;< (+302°F). For EPDM O-rings use only Silicone grease (i.e. Molykote 111 or OKS 110). The lubricants are suitable for use from -40°C (-40°F) to +140°C (+284°F). For LT O-rings use KLT-2 The lubricant is suitable for use from -60°C to +140°C Explosive Environment The Compact can be installed in any appropriate potentially J ? to the ATEX Directive 94/9/EC (Equipment intended for use in Potentially Explosive Atmospheres). Special condition for safe use. 1. When connected to an air actuator the maximum rubbing speed of any component within the valve must not exceed 1 m/s 2. The ambient temperature range for which the equipment is suitable is dependent on the material it’s constructed from the pressure at which they are to be used. Maximum withstand pressure is included within the Pressure Equipment Directive (PED) marking. Each piece of equipment has a lower ambient temperature value than is stated within the documentation provided with each individual item. 3. Layers of dust shall not be permitted to build up on the actuator. -- - temperature (LIT) or cloud ignition temperature (CIT) of the dust atmosphere in which the equipment is to be used with
Page 2
Air Supply }- =' inert gases may be used such as nitrogen, argon and natural gas. Thin hydraulic oil can also be used. Do not use water as a supply medium. Oxygen or hydrogen must NOT BE USED. * 30 microns or less. Always consult with a representative of Compact for suitability and recommended practice.
- * according to recommended instrumentation piping practice. Prior to connection make sure all lines have no loops and are free of water, oil or other contaminants that may be trapped in -' - * -' Where sealants have been used for threaded connections, care must be taken to avoid excess material being forced into the actuator ports. Supply Pressure The supply pressure for the Compact actuators are as follows: Double-acting: 2-8 barg (30-120 psig). Spring-return: 3-8 barg (40-120 psig). Spring-return actuators can also operate with air pressure of 2 * - shown in the Compact catalogue. When sizing an actuator to the available air supply, make sure you have adequate power in the actuator to allow the valve to complete its operation and leave enough power for safety margin. Temperature The standard temperature limits for the Compact actuators are -20°C (-4°F) to +80°C (+176°F). For temperatures below - - - required such as grease, O-rings, pinion bearings and pads. The Compact maximum working temperature is 130°C (266°F) when used with Viton O-rings and HT grease. The Compact minimum working temperature is -60°C (-76°F) when being used with LT O-rings and LT grease.
Page 3
Installation, Operating & Maintenance instructions Double Acting (DA) Pressure entering Port A to open: Center chamber pressurized. Pistons move outward and the pinion rotates counter clockwise (CCW).
When used in sub-zero temperatures it is essential to use an air dryer on the air supply line to prevent moisture. Always consult with a representative of Compact for suitability and recommended practice. Humidity – Corrosion In corrosive environments or in high humidity environments it is recommended to use a Breather Block to avoid contaminated air from the environment entering the actuator. (See Bulletin B370 Namur Breather Block). Reducers Habonim recommends using reducers to properly control the opening / closing speed of Compact actuators, especially if - PRINCIPLE OF OPERATION The Compact actuator is a pneumatic quarter-turn rack & pinion actuator. Air pressure applied to the piston surface area generates thrust which transforms linear motion to rotary motion of the pinion. The Compact has four pistons centrally located around one pinion. This means that the actuator can generate twice the torque of dual piston actuators, is lightweight, occupies minimum space and has minimal air consumption.
Pressure entering Port B to close: Outside chambers pressurized. Pistons move inward and the pinion rotates clockwise (CW).
AIR CONNECTIONS The actuator air connections are marked A and B. Port B connects via a series of holes to all the four pistons. The air passes into the Namur cover (or insert) and through holes which are connected to the two neighboring pistons.
- ensures a quick response.
- <?" port A is to the right and port B to the left.
Spring Return (SR) Pressure entering Port A to open: Center chamber pressurized. Pistons move outward and the pinion rotates counter clockwise (CCW). Springs are compressed.
B A
In sizes C60/C60M and are vertical where port A is above port B
Pressure entering port A into the center chamber pushes the pistons outward and rotates the pinion CW
A B
Pressure exiting Port A to close: Air released from center chamber. Springs drive pistons inward. Pinion rotates clockwise (CW)
B A
Pressure entering port B into the outer chambers pushes the pistons inward and rotates the pinion CW
B A
Page 3
Page 4
Installation, Operating & Maintenance instructions
NAMUR Solenoid Mounting Connection of the air supply is accomplished by mounting a solenoid directly onto the Namur cover which has a mounting pad conforming to the Namur standards. (Only Solenoids made to the NAMUR standard can be mounted in this way.) * tubing from remote solenoid valves.
INDICATOR & PUCK All actuators are assembled with a highly visible indicator or puck. | direction arrows to identify valve position. The arrows can be arranged to provide any pattern according to the valve ports.
TWO WAY
T - PORT
L - PORT
Use a screw driver or sharp instrument at the arrow head to push it out and reposition as necessary.
ISO 5211 or DIN 3337 "/?? DIN 3337) international standards and incorporates a star shaped valve can be attached by a bracket or mounted directly onto the actuator using one of the various ISO hole patterns. TRAVEL ADJUSTMENT The actuator comes factory adjusted to produce a 90° rotation. The rotation is restricted by the stop (13) and four adjustment - ' The screws are threaded into the actuator body and are diametrically opposed to create simultaneous and equal forces on opposite sides of the stop to eliminate off-center forces.
The puck has three contact screws to allow signaling of any position. The puck is screwed to the pinion Namur thread. (The indicator snaps to the pinion with its Namur interface projecting above it and enabling any ancillary to connect to the pinion). The indicator assembles on the pinion with its Namur interface projecting above the pinion enabling the connection of ancillary devices to the pinion. IDENTIFICATION Compact actuators are supplied with a nameplate located on the side of the body. The information includes actuator size, model, type, spring set, threads, indicator, additional options, date of manufacture, protection rating, pressure limits and company logo.
Actuator description Compact “C” series
MODEL
Work Instruction
19
19 13
13
Week of manufacture
90° The standard stop screws the travel limits. Other Intermediate positions can be achieved with a longer set of stop screws which will enable travel from 0° to 20° and from 90° to 70° rotation.
95° 85°
SERIES
XXXXX XX XX MAX PRESSURE: 120 PSI, 8 BAR
Year of manufacture
70°
20° +5° -5°
0°
Page 4
COMP
CT
INDUSTRIAL VALVES & ACTUATORS LTD KFAR HANASSI, 1230500, IL
Page 5
Installation, Operating & Maintenance instructions
1
DISASSEMBLY
2
Disassembly of Double Acting Covers
General Before any disassembly, make sure you read all the warnings
Do not attempt to disassemble the actuator while it is still connected to the valve or to any ancillary device. Verify that the actuator is not pressurized. Check that the air ports are vented and that spring return actuators are in the fail close position. Work in a clean area, free of dust, debris, grease, corrosives and moisture. For security and comfort perform repairs on a table equipped with a vice and an available air supply. Clamp an adaptor to the vice and place the actuator drive on it. Use only Metric hex head wrenches and ensure the edges are not blunt.
2.1 Before disassembly mark the covers (9) with the body. This is recommended so as to reassemble each cover to its original position when re-assembling the actuator. 2.2 Remove the cover screws (11). If initially the screws are _ 2.3 Remove the covers making sure not to damage the O-ring seals (7, 7A, 10). When removing the Namur cover (8A) ensure that the O-ring connecting to the inner chamber is secure in its groove. To convert to a SR actuator, go to Section 7 for instructions.
DA Cover Removal
11
9
3
Disassembly of Spring Return Covers Caution: Springs in the actuator are under tension. The compact actuator has 2 types of spring assemblies. - Š - <?"_ </#_ </"_ <`#_ <`"_ <="_ <Œ#_ <‚"' The loaded cartridge spring assembly– used in the M models: <`#„_ <`"„_ <="„_ <Œ#„_ <‚"„' Before disassembling a SR actuator you must identify the model type of the actuator according to the following: 1. Identify by the attached tag. /' - * * "tensioned springs" warning on the Covers. 3. Cartridge spring actuators have a longer cup cover according to the following table:
Standard spring assembly
Cover height H1 (mm)
Cartridge spring assembly
Cover height H2 (mm)
<?"
18.8
N/A
N/A
C20
//'"
N/A
N/A
</"
/Œ'"
N/A
N/A
C30
30.1
C30M
="'?
<`"
36.2
<`"„
"#'#
<="
43.2
<="„
60.2
C60
"'`
C60M
73.3
<‚"
71.0
<‚"„
86.0
Standard Spring Assembly H1
Page 5
Cartridge Spring Assembly H2
Page 6
Installation, Operating & Maintenance instructions After identifying the actuator type, use the following disassembly instruction: ’ - <JJ„ Š instructions in Section 3.1-3.8 ’ - <JJ Š disassembly instructions in Section 4
Disassembly of Spring Return Covers for Cartridge Spring Assembly C30M, C35M, C45M, C60M, C75M Caution: Springs in the actuator are under tension. 3.1 Before disassembly, mark each of the non-Namur covers (29) with the body. This is recommended to identify each cover and to reassemble it in its original position when re-assembling the actuator. 3.2 Open a gap of 10 mm maximum between the cover and the actuator body. Release the cover screws in sequence by turning each opposing screw two rotations at a time. After opening the gap there should be no tension on the cover, make sure the cover can be moved freely. Warning: If after opening a 10mm gap the cover is still under tension, close the cover by retightening the screws and contact Habonim. DO NOT release the cover completely. 3.3 Only after ensuring that the cover is loose, release the cover screw and remove the cover while supporting the spring cartridge to prevent it from falling out of cover. 3.4 Make sure that the Cover O-ring (7,7A) is secure in its groove. When removing the Namur cover (29A) makes s ure the air supply O-ring (10) is also secure in its groove. 3.5 Carefully examine the spring cartridge and make sure it’s not damaged, special attention must be given to the bent pipe at the center which holds the complete unit together. In case cracks or any other severe damage is observed, close the cover by retightening the screws and contact Habonim. 3.6 Warning: Under NO circumstances should the spring cartridge be cut or disassembled in order to change the spring set. The only way to change the spring set is by changing to a different spring cartridge. 3.7 Place the spring cartridge in the cover for assembly with the seals. 3.8 Follow the same procedure for all four cylinders.
or to convert it to a DA actuator, go to Section 7.16 for instructions.
10mm gap
Spring Cartridge bent pipe
Page 6