For the Toyopuc OUT-15 and Toyopuc OUT-18
Page 170
Comparison
Conversion
Parity calculation
Classification
Command word
Odd
83 MKP1
Even
81 MKP2
Odd
84 PCH1
Even
82 PCH2
BCD → Conversion to binary data
2 digits → 8bits
Binary → Conversion to BCD data
8bits → 2 digits
152 BIN 3 WBIN 153 DBIN 154 BCD 4 WBCD 155 DBCD
Parity bit create Parity check
4 digits → 16bits 8 digits → 32bits 16bits → 4 digits 32bits → 8 digits
Symbol
Function
Execution time
S
Most significant bit is set/reset so that the bit number of "1" becomes odd (MKP1) [Even (MKP2)], using the lower 7bits in the content of S as "source data". The result is stored in D.
3.96
MKP1 MKP2
PCH1 PCH2
D
CARRY FLAG is turned ON unless the bit number of "1" is odd (PCH1) [even (PCH2)] upon parity check of S content.
S
BIN WBIN DBIN
S
D
BCD data stored in S is converted to binary data and, thereafter, stored in D.
BCD WBCD DBCD
S
D
Binary data stored in S is converted to BCD data and, thereafter, stored in D.
(µs)
3.96 5.52 5.52 3.56 7.12 15.88 3.64 10~13 27~38
JIS →Conversion to binary data
156 JBIN
JBIN
S
D
K
Character and numeral data shown with K from the address of S are deemed as JIS code and then stored in the area having D as its head address, after converted to binary number.
Binary data → Conversion to JIS
157 BJIS
BJIS
S
D
K
The digit number shown with K from the address of S is deemed as hexadecimal number and the stored in the area having D as its head address, after converted to JIS code.
4 →16 DECODER
50 DECO
D
The content of S is stored in D, after its lower 4bit was decoded to hexadecimal data.
1.24
D
ON bit position, of 16 bits in the S content, is converted to binary data (two or more ON bits; Priority is given to the lower bit.) and the converted data is stored in lower 4 bits of D.
5.80
K
Binary 4bit data is converted to 7-segment data, but limited to the digit number shown with K from the address of S, and the converted data is stored in the area which of head address is D.
8.88+2.26n
DECO
S
16 →4 DECODER
51 ENCO
ENCO
7-SEGMENT DECODER
52 SEG
SEG
Hour, minute, second → Convert to sec
158 WTIM1
Sec → Convert to hour, minute, sec
159 WTIM2
WTIM2
S
Code conversion Setting
85 CDSET
CDSET
S1
WTIM1
S
S
D
S
D with S on its head is converted to binary data of 0.1 sec unit and the
S2
The content of S is deemed as binary data of 0.1 sec unit and converted to BCD type data of hour, minute and second. The converted data is stored in 4 bytes with D on its head.
47.83
D
The content of S1 is transferred to register shown with (D address +S2 content). The content of S1 is handled as BCD.
6.04
CDO1
S1
S2
D
Code conversion Output 2
87 CDO2
CDO2
S1
S2
D
BCD data stored in the register shown with (S2 address +S1 content) is transferred to D+1 and furthermore transferred to D after converted to binary data.
Bit reset
Bit extract
On bit counter
1 bit right shift n-bit right shift
Shift
1 bit left shift n bit left shift 1 bit right/left shift n bit right/left shift
11.20
D
86 CDO1
8bits 16bits 32bits 8bits 16bits 32bits 8bits 16bits 32bits 8bits 16bits 32bits 8bits 16bits 32bits 8bits 16bits 32bits 8bits 16bits 32bits 8bits 16bits 32bits 8bits 16bits 32bits 8bits 16bits 32bits 8bits 16bits 32bits
2.84+3.00n converted data is stored in D.
Code conversion Output 1
Comparison
3.08+3.92n
The BCD type data of hour, minute and second which is stored in 4 bytes
The content of register shown with (S2 address +S content ) is transferred to D. The content of S1 is handled as BCD.
Bit set Bit operation
No.
17 CP 12 WCP 211 DCP 136 BSET 137 WBSET 138 DBSET 139 BRST 140 WBRST 141 DBRST 54 BPU 142 WBUP 143 DBUP 208 SUM 209 WSUM 210 DSUM 217 SFR 36 WSFR 218 DSFR 224 BSFR 225 WBSFR 226 DBSFR 219 SFL 37 WSFL 220 DSFL 227 BSFL 228 WBSFL 229 DBSFL 221 SRL 222 WSRL 223 DSRL 230 BSRL 231 WBSRL 232 DBSRL
CP WCP DCP
S1
S2
BSET WBSET DBSET
S
D
BRST WBRST DBRST
S
D
BUP WBUP DBUP
S1
S2
SUM WSUM DSUM
S
D
D SFR WSFR DSFR
S
T
BSFR WBSFR DBSFR
S
D SFL WSFL T DSFL BSFL WBSFL DBSFL
K
S
S
K
D
SRL L/R WSRL T DSRL
S
L/R BSRL T WBSRL DBSRL
S
7-51
6.04
8.20
2.84 2.84 4.36 2.00 D bit is set as designated in S content. 2.00 2.80 2.00 D bit is reset as designated in S content. 2.00 2.80 3.16 Bit content of S2 which is designated in S1 4.16 content is transferred to CARRY FLAG. 3.96 3~9 The sum of bits under ON, of bits in S content, is 3~16 counted and the result is stored in D. 3~30 2.76 S content is shifted by 1 bit to the right. The content entered in D is shifted to most significant bit and the content of least 2.64 significant bit is shifted to CARRY FLAG. 3.52 3.36+0.56n S content is shifted by designated bit number 3.36+0.56n (K) to the right. 3.80+0.96n 2.76 S content is shifted by 1 bit to the left. the content entered in D is shifted to most significant bit and the content of least 2.64 significant bit is shifted to CARRY FLAG 3.28 3.36+0.56n S content is shifted by designated bit number 3.36+0.56n (K) to the left. 3.88+0.96n 3.76 S content is shifted by 1 bit to the left (L/R=ON) 3.76 [right (L/R=OFF). 4.28 4.52+0.48n S content is shifted 1 bit by designated bit number (K) to the left (L/R=ON) 4.52+0.48n [right )L/R=OFF)]. 4.68+0.80n Upon comparison of S1 content with S2 content, either one of >, =, < FLAGS is turned ON from the size relation between the two.
Page 171
Classification
Lower significant shift
FIFO
Fifo write
Fifo read
Rotate Program branching
Function
SUP UP2 WUP DUP
S
K
8bits
91 UP1
UP1
S1
S2
4bits 8bits 16bits 32bits 8bits 16bits 32bits 8bits 16bits 32bits
255 SDOWN 256 DOWN 257 WDOWN 258 DDOWN 160 FIFW 161 WFIFW 162 DFIFW 163 FIFR 164 WFIFR 165 DFIFR
SDOWN DOWN
S
K
WDOWN
DDOW
FIFW WFIFW DFIFW
S
D1
D2
FIFR WFIFR DFIFR
S
D1
D2
Stack shift input
68 SFIN
SFIN
S
Stack shift output
69 SFOUT
SFOUT
D1
8bits 16bits 32bits Rotate to right 8bits Without 16bits carry 32bits 8bits With 16bits carry 32bits Rotate to left 8bits Without 16bits carry 32bits 8bits With 16bits carry Rotate 32bits to right/left Without 8bits 16bits carry 32bits
233 RRC 234 WRRC 235 DRRC 242 RR 243 WRR 244 DRR 236 RLC 237 WRLC 238 DRLC 245 RL 246 WRL 247 DRL 239 RLRC 240 WRLRC 241 DRLRC 248 RLR 249 WRLR 250 DRLR
RRC WRRC DRRC
S
K
RR WRR DRR
S
K
RLC WRLC DRLC
S
K
RL WRL DRL
S
K
Jump
D S
L/R RLRC T WRLRC DRLRC L/R
D2
S
Execution time (µs)
6.34+1.10n Data in area with S on its head address and with 5.20+0.92n data number designated with K are shifted to upper significant direction. The least significant data is 0. 5.52+0.92n 5.76+1.68n Data in areas from S1 up to S2 are shifted at unit of 1 4.52+0.92n byte. Least significant data remains unchanged. 6.62+0.94n Data in area with S on its head address and with 5.28+0.92n data number designated with K are shifted to lower 5.76+0.92n significant direction. Most significant data is 0. 5.88+1.68n 5.84 S content is transferred to the address shown with ( offset value shown with D1 address + D2 content). 6.36 Furthermore, +1 is added to D2 content. 7.12 5.88+1.00n S content is transferred to D2. Data in the area with S as its head address and with D1 content as its data number are shifted to lower 6.08+1.00n significant direction. Furthermore, -1 is added to D1 content. 6.40+1.84n The areas from S address up to D address are deemed as STACK and the content of S is all stacked.
However, 0 is deemed as "no data".
S content is transferred to D2.
The data from D1 address up to S-1 are shifted to upper significant direction. D1 content is made to 0.
6.68+0.84n 9.94+0.96n
3.72+0.48n S content and CARRY FLAG are rotated to the right, 3.72+0.48n by the bit number designated with K. 4.48+0.88n 3.72+0.48n S content is rotated to the right, by the bit number 3.72+0.48n designated with K. 4.52+0.88n 3.72+0.48n S content and CARRY FLAG is rotated to the left, by 3.72+0.48n the bit number designated with K. 4.48+0.88n 3.72+0.48n S content is rotated to the left, by the bit number 3.72+0.48n designated with K. 4.52+0.88n 4.52+0.48n S content and CARRY FLAG are rotated to the left 4.52+0.48n (L/R =ON) [right (L/R=OFF), by the bit number designated with K. 5.60+0.88n 4.52+0.48n S content is rotated to the left (L/R=ON) [right (L/R 4.52+0.48n =OFF)], by the bit number designated with K. 5.60+0.88n
RLR WRLR DRLR
S
272 JMP
JMP
Ln
Jumped into label No. Ln.
8.00
Sub-routine call
273 CALL
CALL
Sn
Sub routine of label No. Sn is executed and steps following this command example are executed.
14.20
Return from sub routine
464 RET
RET
After termination of subroutine, the steps following the CALL command which called applicable subroutine are executed.
5.40 4.56 4.64
T
Repeating start
472 FOR
FOR
K
This command - NEXT command are repeated K times.
Repeating start (indirect)
476 FORN
FORN
S
This command - NEXT command are repeated by the frequency shown with S content. -1 is deducted from S content whenever executed.
Repeating end
480 NEXT
NEXT
Program from FOR and FORN commands up to this command is repeated by the frequency designated with FOR, FORN commands.
4.24(FORN)
440 MC 444 MCR
MC MCR
Output command of the master control range from SET up to RESET is controlled . Normally controlled if MO command input is ON and all OFF if the same command input is OFF.
5.96 3.86
I/O refresh
280 RIO
RIO
External input ON/OFF information is transferred to Device X and the ON/OFF information of Device Y is transferred to the external output unit.
23.28 +0.18n
Input refresh
281 RI
RI
D
K
External input data of Kbyte portion is transferred to Device X 8.84+1.32n from the address of D.
Output refresh
282 RO
RO
D
K
ON/OFF information on Device Y of Kbyte portion is transferred to external output unit from D address,
9.64+1.08n -
Master control I/O control
Symbol word
251 SUP 252 UP2 253 WUP 254 DUP
With carry
Label
Command
4bits 8bits 16bits 32bits
Shift
Upper significant shift
No.
Set Reset
K
4.04(FOR)
Main program start
448 START
START
Indicating start-up of main sequence program.
Main program end
452 END
END
Indicating end of main sequence program.
-
Program end
456 PEND
PEND
-
Label
460 LABEL
LABEL
Indicating end of sequence program including subroutine. Indicating division and jump of sequence program .
S,D: Register
H:Hexadecimal constant
K:decimal constant
Ln n: Label No.
7-52
1.48
Page 172
Others
Special Module
Classification
No.
Command
Symbol word
Function time (µs)
High speed counter data read High speed counter data write
316 HCR
HCR
S1
317 HCW
HCW
S1
S2
H
Common I/O data read
318 IOR
IOR
S1
S2
H
Directly reads internal memory of analog module.
3+120n
Common I/O data write
319 IOW
IOW
S1
S2
H
Directly writes data in internal memory of analog module.
15 +78.5n
304 SPR
SPR
S1
S2
S3
Directly reads internal memory of serial I/O module.
306 SPW
SPW
S1
S2
S3
Directly write data in internal memory of serial I/O module.
Annunciator
291 ANN
ANN
H
User defined clock
293 USC
USC
K1
Built-in clock 30 sec correction
292 ADJ
Special module byte data read Special module byte data write
S2
Directly reads internal memory of high speed counter module. Directly writes data in internal memory of high speed counter module.
Execution
151 3+115n
633 +250n 371 +383n
S
Message data and time in the 16Byte area with code H and S on its head
K3
User defined clock 1, 2 in special relay are set up.
75.42
ADJ
30 sec correction is made to the built-in clock. Less than 30 sec is rounded off. More than 30 sec is counted up as 1 minute.
188
The communication speed for peripheral equipment is changed into the speed designated with K.
55.46
K2 address are transferred to the annunciator area of special register.
141.88
Communication speed setting for peripheral equipment
288 BAUD
BAUD
Program stop
287 STOP
STOP
Run of sequence program is stopped.
-
Scan time reset
46 WDR
WDR
The scan time monitor timer is reset.
52
S,D: Register
H: Hexadecimal constant
K
K: Decimal constant
7-53
Page 173
(5) Exclusive applied commands for PC3J Transfer commands
Classification Bit block transfer 4bit 8bit 16bit
Inversion
Address constant transfer Binary
Constant addition
Arithmetic computation
Binary
BCD
Binary
Constant multiplication BCD
Command word
Function
27~39 +0.34n(Bit)
8.76+1.72n
121 BBMOV
BBMOV
Sh1 Dh2
K
Bit data with bit position represented by h1 of S at its head and with points represented by K is transferred to an area with bit position represented by h2 of D at its head.
259 STURN 260 TURN 261 WTURN
STURN TURN WTURN
S
K
Transfer to area with D as its head address in inverse sequence from last data in data area with S as its head address and with points represented by K.
320 MOVAD
MOVAD
D
S
323 +H 324 W+H
+H W+H
32bit
325 D+H
D+H
S
2 digits
326 +HP 327 W+HP
+HP W+HP +
S
8 digits
328 D+HP
D+HP
S
8bit 16bit
329 -H 330 W-H
-H W-H
S
32bit
331 D-H
D-H
S
2 digits 4 digits
332 -HP 333 W-HP
-HP W-HP
8 digits
334 D-HP
D-HP
S
8bit 16bit
335 *H 336 W*H
*H W*H
S
S
S
32bit
337 D*H
2 digits 4 digits
338 *HP 339 W*HP
*HP W*HP
S
8 digits
340 D*HP
D*HP
S
8bit 16bit
341 /H 342 W/H
/H W/H
S
D*H
D H
D H
K
D
Statistic processing
Logic computation
BCD
Constant logic product Constant logic sum Constant exclusive logic sum Sum Max value retrieval Min value retrieval
Others
Mean
32bit
343 D/H
D/H
2 digits 4 digits
344 /HP 345 W/HP
/HP W/HP
8 digits
346 D/HP
8bit 16bit
S
D/HP
S
347 ANDH 348 WANDH
ANDH WANDH
S
32bit
349 DANDH
DANDH
D
8bit 16bit
350 ORH 351 WORH
ORH WORH
32bit
352 DORH
DORH
8bit 16bit
353 XORH 354 WXORH
XORH WXORH
32bit
355 DXORH
8bit 16bit 32bit 8bit 16bit 32bit 8bit 16bit 32bit 8bit 16bit 32bit
362 STI1 363 WSTI1 364 DSTI1 374 MAX 375 WMAX 376 DMAX 377 MIN 378 WMIN 379 DMIN 380 AVE 381 WAVE 382 DAVE
S
S
MAX WMAX DMAX
MIN WMIN DMIN
AVE WAVE DAVE
H
H
S S1
S1
S1
S1
D
4.60
39~50 160~180
28~30
After S content and constant H were divided, the result is stored in address next to S and remainder stored in next next address . The data are all handled as binary value.
77~82
After S content and constant K were divided, the result is stored in D and
21.26 remainder stored in next address. The data are all handled as BCD.
56.92
D
After logic sum (OR) of S content and constant H was computed,the result is stored in D.
H
After logic sum (OR) of S content and constant H was computed,the result is stored in address next to S.
D
After exclusive logic sum (XOR) of S content and constant H was computed, the result is stored in D.
H
After exclusive logic sum (XOR) of S content and constant H was computed, the result is stored in address next to S.
149~164 2.40 2.40 3.96 2.40 2.40 3.96 2.72 2.72 3.96
S2
The sum in data area with S1 as head address and with number represented by S2 content is stored in D. The data are all handled as binary value.
S2
Maximum value in data area with S1 as head address and with number represented by S2 content is stored in D.
5.56+1.00n
S2
Minimum value in data area with S1 as head address and with number represented by S2 content is stored in D.
5.72+1.00n 5.72+1.00n
Mean value in data area with S1 as head address and with number
33.24+1.08n represented by S2 content is stored in D. The data are all handled as binary
82.08+1.32n
S2
Subroutine is closed when the conditions are met, and applicable
Conditional return
285 CRET
CRET
Area designated I/O refresh
295 ARIO
ARIO
Applied command flag clear mode setting Applied command flag clear mode resetting
300 SYS
SYS
4
1
0
300 SYS
SYS
4
0
0
S,D: Register , H: Hexadecimal constant
1.24
17~19
The data are all handled as binary value.
value and fractions over 4 at first decimal point are counted as one.
subroutine is called and executed from step next toCALL command.
D
22.76 55~67 stored in next address.
After logic product(AND) of S content and constant H was computed, the result is stored in address next to S.
D
4.52 6.92
After S content and constant H were divided, the result is stored in D and remainder
H
D
3.20 3.20
23.04
After logic product (AND) of S content and constant H was computed, the result is stored in D.
D
58~64
13~15
D
D
7.80 23.80
After S content and constant K were multiplied, the result is stored in D. The data are all handled as BCD.
After S content and constant K were divided, the result is stored in address next to S and remainder stored in next next address. The data are all handled as BCD.
K
S
DXORH
STI1 WSTI1 DSTI1
H
2.40
After S content and constant H were multiplied, the result is stored in the address next to S. The data are all handled as binary value.
address next to S. The data are all handled as BCD.
D
K
The data are all handled as binary number.
After S content and constant H were multiplied, the result is stored in D. The data are all handled as binary value.
After S content and constant K were multiplied, the result is stored in the
K H
After S content and constant K were deducted, the result is stored in D. The data are all handled as BCD. address next to S.
D
K
S
After S content and constant K were added, the result is stored in D. The data are all handled as BCD.
S content and constant K are deducted and the result is stored in the
H
H
4.04
S content and constant H are deducted and the result is stored in D. The data are all handled as binary number. D
H
S
S content and constant H are added and the result is stored in the address
D
K
S
After S content and constant H were added, the result is stored in D. Data are all handled as binary value.
After S content and constant H were deducted, the result is stored in D. The data are all handled as binary value.
K
8.76+1.72n 0.72
S content and constant K are added and the result is stored in the address next to S. The data are all handled as BCD.
H
8.76+2.36n
2.40
K H
(µs)
S is stored in D after changed into indirect address.
next to S. The data are all handled as binary number.
Binary
Constant dividing
Execution time
Symbol
8bit 16bit
BCD 4 digits
Constant deduction
No.
K
K:decimal constant
7-54
External I/O of Kbyte portion from D address are refreshed. Set up so that applied command flag is cleared at reading of applied command . Set up so that applied command flag is not cleared at reading of applied command.
6.12+0.84n 7.00+1.08n 7.80+1.52n 5.72+1.00n 6.20+1.60n
6.20+1.60n
131+1.44n 5.40 16.00+2.40n 81.70 82.10
Page 174
Others
Classification
No.
Comma
SYS Clock adjustment instruction (PC3J series ver2.6~) *1
300
SYS
Symbol nd word
S,D: Register , H: Hexadecimal constant
5
SYS
Function
S
0
Execution time (µs)
The clock in CPU is adjusted by “the minute second day hour year month week” of the 4-word which makes the address of S a head.
K:decimal constant
*1 PC3JG PC3JBG PC3JP can use this instruction. PC3JL, PC3JD, PC3JB, PC3JM can use this instruction since version 2.6. PC3J PC3JNF PC3JNM can not use this instruction.
(6) Exclusive applied commands for PC3JG
Others
Transfer commands
Classification
No.
Command
Symbol word
Function register address setting
371 BRSET
BRSET
S
Buffer Indirect loading register transfer
372 WBR
WBR
S
D
K
Indirect saving
373 WBW
WBW
S
D
K
Order the message command for DLNK-M2
302 MSET
MSET +
H
S
D
Order the I/O resister read-out instruction for TOYOPUC-PCS
370 CSET
CSET
H
S
D
S,D: Register , H: Hexadecimal constant
D
K:decimal constant
7-55
The Indirect address of the buffer register(EB) specified S is set to the 2 word area with D as the head address. Data in buffer registers which of address is the content of 2 word area with S as the head address is transferred to registers with D as the head address. Size is K. Registers with S as the head address is transferred to buffer registers which of address is the content of 2 word area with D as the head address. Size is K. Message of the number indicated with H which of head address is S are tranfered to DLNK-M2 indicated with H. The response data from DLNK-M2 are trnsfered to the area which of head address is D. I/O register read-out instruction of the number indicated with H which of head address is S are transferred to PCS. The response data from PCS are transferred to the area which of head address is D
Execution time (µs)
0.96
80+2n
80+2n
80+4n
60+4n
Page 175
7.2.8
Equipment Information Memory
The equipment information memory is available to store comments, etc. on sequence circuits separately from sequence program, parameters and data. This equipment information memory of 640KB capacity can normally store 10,000 points or more , where limited to the address comments only. The number of storable comments differs depending on the content of comment. Storing comments ,etc. in the equipment information memory is effected by peripheral equipment ( PCwin). The peripheral equipment (PCwin) can display commented circuit diagram, cycle chart, etc. by reading the information stored in the equipment information memory. Storing and reading in/from the equipment information memory can be made by the peripheral equipment (PCwin) for the PC3J , irrespective of CPU operation mode. The PC2 Series peripheral equipment (GL1, etc.) can not store and read data in/from the equipment information memory. Further, it is impossible to change the information stored in the equipment information memory and to store data in the same memory in sequence program. Also it is impossible to refer to the stored information in accordance with sequence program.
Peripheral Equipment (PCwin) Equipment Information Memory
640KB comments, etc.
User Memory Sequence program, Parameters, Data
PC3JG CPU Displays commented circuit diagram, etc. based on information stored in the Equipment Information Memory. 7-56
Page 176
7.3 Link specification (1) Communication port and Link function Communication port
Link function
Communication port L1
SN-I/F or PC link or Commputer link
Communication port DLNK
DLNK-M2
(Note)When the “Communication port L1” (built-in standard link) parameters are not set, acts as SN-I/F. It operates as CMP for PC2 interchangeable mode. (2) Computer link specification (Communication port L1) Items Interface standard Communication system Transmission line Communication speed Transmission distance Transmission form Number of stations Data type
Characters used Error detection *1
Specification Conforming to EIA RS-422 Start-stop synchronous, semi-dual Shielded twist bare cable 0.3,0.6,1.2,2.4, 4.8,9.6,19.2,38.4kbps
(Presetting*1)
Max 1 km (total length) 1:N Max 32 stations (Address No. 00 ~ 37) [set with octal number ) Start bit ...........1 bit Data length .....7 or 8 bit (presetting) Parity ..............1 bit (even parity Stop bit ...........1 or 2 bit (presetting) ASCII code Parity check, sum check
It is set up by the link parameter.
7-57 the link
Page 177
(3) PC link specification (Communication port L1) Items
Specification
I/O points Transmission points per station No. of stations
Max 512 points/1 port When 19/.2kbps/57.6kbps is selected : Max 384 points When NC×3 selected : Max 512 points Max 16 stations (master 1, slave 15 ) /1 line
I/O allocation Transmission distance
Minimum setting unit :8 points Max 1 km (total length)
Signal level
Conforming to EIA RS-422
Communication speed Synchronous system
19.2kbps / 57.6kbps / NC×3speed *1 Start-stop synchronous
Transmission system
Semi-dual system (2-wire type)
Bit composition
JIS 7 unit system, 10 bits
Check system
Vertical parity, horizontal parity (Even number)
Cable Transmission data at CPU stopping CPU operation against communication error Communication error under connection sequence
Shielded twist bare cable
(Presetting*2)
OFF data / Pre-stop data (Presetting*2) Stop/RUN continue (Presetting*2) As error /repeat (Presetting*2)
*1 This speed is set to communicate with NC machine corresponding to M-NET×3 speed. *2
It is set up by the link parameter.
(4) SN-I/F specification (Communication port L1) Items
Specification
Data link
I/O : 32byte,
Transmission distance
Signal level
Max 3 m (only inside of controller box) Parity ............. 1 bit (even parity) Data length .... 8 bit Stop bit........... 1 bit Conforming to EIA RS-422
Synchronous system
Start-stop synchronous
Transmission system
Semi-dual system (2-wire type)
Communication speed
288kbps
Cable
Shielded twist bare cable
Data type
7-58 register : 32byte
Page 178
(5) DLNK-M2 specification (Communication port DLNK) No.
Items
1 Data rate
Specification 500 / 250 / 125 Kbps
500Kbps
Below 100m
Below 6m
Total expansion of drop line Below 39m
250Kbps
Below 250m
Below 6m
Below 78m
125Kbps
Below 500m
Below 6m
Below 156m
Maximum cable distance
Data rate 2
Communication distance
(selectable by switch) Drop line length
Maximum number 3 of connected 64 units (master 1 unit slave 63 units) *1 nodes 4 Node address Master : 00 Slave : 01 ~ 63 I/O points number Input: Maximum 2048 points (256 bytes) 5 of DLNK Output: Maximum 2048 points (256 bytes) 6 I/O allotment Minimum unit of 8 points Communication 7 X·Y,M,L,EX · EY,EM,EL,GX·GY,GM *2 area 8 Function I/O refresh, message command *1 In the case of TOYOPUC DLNK, this applies only to the asynchronous mode. There are no relations in input and output type, and the number of maximum connection notebooks is restricted with synchronous mode in the following. Data rate
Maximum number of connected nodes
500kbps 250kbps 125kbps
9 7 6
*2 GX/GY and GM area can be used in the PC3JG separate mode.
7-59
Page 179
7.4 I/O Specification 7.4.1 Allocation of connector pin (a) PC3JG
Pin arrangement
0~1F(Left Connector) Pin No. A1 A2 A3 A4
When it was seen from the front of the module.
Signal COM2 (0V) COM2 (0V) COM2 (0V) COM2 (0V)
Pin No. B1 B2
20~3F(Right Connector) Signal
PWR2 (+24V) COM1 (+24V)
Pin No. A1 A2
Signal COM4 (0V) COM4 (0V)
Pin No. B1 B2
Signal PWR4 (+24V) COM3 (+24V)
B3
-
A3
-
B3
-
B4
-
A4
-
B4
-
A5
Y1F
B5
X0F
A5
Y3F
B5
X2F
A6
Y1E
B6
X0E
A6
Y3E
B6
X2E
A7
Y1D
B7
X0D
A7
Y3D
B7
X2D
A8
Y1C
B8
X0C
A8
Y3C
B8
X2C
A9
Y1B
B9
X0B
A9
Y3B
B9
X2B
A10
Y1A
B10
X0A
A10
Y3A
B10
X2A
A11
Y19
B11
X09
A11
Y39
B11
X29
A12
Y18
B12
X08
A12
Y38
B12
X28
A13
Y17
B13
X07
A13
Y37
B13
X27
A14
Y16
B14
X06
A14
Y36
B14
X26
A15
Y15
B15
X05
A15
Y35
B15
X25
A16
Y14
B16
X04
A16
Y34
B16
X24
A17
Y13
B17
X03
A17
Y33
B17
X23
A18
Y12
B18
X02
A18
Y32
B18
X22
A19
Y11
B19
X01
A19
Y31
B19
X21
A20
Y10
B20
X00
A20
Y30
B20
X20
The external connectors are the following.
Type Specification 40 pins , soldering type FCN-361J040-AU FCN-360C040-B 40 pins , case The size of the screw of the connector is M2.6 . Fujitsu*1 Fujitsu*1
Type for TMW TIP-5867
And, it Can be Connected with the FCN-360 jack type (for the gold plating) made by Fujitsu Takamisawa Component Ltd.. Be sure to use contact goods for the gold plating. *1 : Fujitsu Takamisawa Component Ltd.. 7-60