Page 170

Comparison

Conversion

Parity calculation

Classification

Command word

Odd

83 MKP1

Even

81 MKP2

Odd

84 PCH1

Even

82 PCH2

BCD → Conversion to binary data

2 digits → 8bits

Binary → Conversion to BCD data

8bits → 2 digits

152 BIN 3 WBIN 153 DBIN 154 BCD 4 WBCD 155 DBCD

Parity bit create Parity check

4 digits → 16bits 8 digits → 32bits 16bits → 4 digits 32bits → 8 digits

Symbol

Function

Execution time

S

Most significant bit is set/reset so that the bit number of "1" becomes odd (MKP1) [Even (MKP2)], using the lower 7bits in the content of S as "source data". The result is stored in D.

3.96

MKP1 MKP2

PCH1 PCH2

D

CARRY FLAG is turned ON unless the bit number of "1" is odd (PCH1) [even (PCH2)] upon parity check of S content.

S

BIN WBIN DBIN

S

D

BCD data stored in S is converted to binary data and, thereafter, stored in D.

BCD WBCD DBCD

S

D

Binary data stored in S is converted to BCD data and, thereafter, stored in D.

(µs)

3.96 5.52 5.52 3.56 7.12 15.88 3.64 10~13 27~38

JIS →Conversion to binary data

156 JBIN

JBIN

S

D

K

Character and numeral data shown with K from the address of S are deemed as JIS code and then stored in the area having D as its head address, after converted to binary number.

Binary data → Conversion to JIS

157 BJIS

BJIS

S

D

K

The digit number shown with K from the address of S is deemed as hexadecimal number and the stored in the area having D as its head address, after converted to JIS code.

4 →16 DECODER

50 DECO

D

The content of S is stored in D, after its lower 4bit was decoded to hexadecimal data.

1.24

D

ON bit position, of 16 bits in the S content, is converted to binary data (two or more ON bits; Priority is given to the lower bit.) and the converted data is stored in lower 4 bits of D.

5.80

K

Binary 4bit data is converted to 7-segment data, but limited to the digit number shown with K from the address of S, and the converted data is stored in the area which of head address is D.

8.88+2.26n

DECO

S

16 →4 DECODER

51 ENCO

ENCO

7-SEGMENT DECODER

52 SEG

SEG

Hour, minute, second → Convert to sec

158 WTIM1

Sec → Convert to hour, minute, sec

159 WTIM2

WTIM2

S

Code conversion Setting

85 CDSET

CDSET

S1

WTIM1

S

S

D

S

D with S on its head is converted to binary data of 0.1 sec unit and the

S2

The content of S is deemed as binary data of 0.1 sec unit and converted to BCD type data of hour, minute and second. The converted data is stored in 4 bytes with D on its head.

47.83

D

The content of S1 is transferred to register shown with (D address +S2 content). The content of S1 is handled as BCD.

6.04

CDO1

S1

S2

D

Code conversion Output 2

87 CDO2

CDO2

S1

S2

D

BCD data stored in the register shown with (S2 address +S1 content) is transferred to D+1 and furthermore transferred to D after converted to binary data.

Bit reset

Bit extract

On bit counter

1 bit right shift n-bit right shift

Shift

1 bit left shift n bit left shift 1 bit right/left shift n bit right/left shift

11.20

D

86 CDO1

8bits 16bits 32bits 8bits 16bits 32bits 8bits 16bits 32bits 8bits 16bits 32bits 8bits 16bits 32bits 8bits 16bits 32bits 8bits 16bits 32bits 8bits 16bits 32bits 8bits 16bits 32bits 8bits 16bits 32bits 8bits 16bits 32bits

2.84+3.00n converted data is stored in D.

Code conversion Output 1

Comparison

3.08+3.92n

The BCD type data of hour, minute and second which is stored in 4 bytes

The content of register shown with (S2 address +S content ) is transferred to D. The content of S1 is handled as BCD.

Bit set Bit operation

No.

17 CP 12 WCP 211 DCP 136 BSET 137 WBSET 138 DBSET 139 BRST 140 WBRST 141 DBRST 54 BPU 142 WBUP 143 DBUP 208 SUM 209 WSUM 210 DSUM 217 SFR 36 WSFR 218 DSFR 224 BSFR 225 WBSFR 226 DBSFR 219 SFL 37 WSFL 220 DSFL 227 BSFL 228 WBSFL 229 DBSFL 221 SRL 222 WSRL 223 DSRL 230 BSRL 231 WBSRL 232 DBSRL

CP WCP DCP

S1

S2

BSET WBSET DBSET

S

D

BRST WBRST DBRST

S

D

BUP WBUP DBUP

S1

S2

SUM WSUM DSUM

S

D

D SFR WSFR DSFR

S

T

BSFR WBSFR DBSFR

S

D SFL WSFL T DSFL BSFL WBSFL DBSFL

K

S

S

K

D

SRL L/R WSRL T DSRL

S

L/R BSRL T WBSRL DBSRL

S

7-51

6.04

8.20

2.84 2.84 4.36 2.00 D bit is set as designated in S content. 2.00 2.80 2.00 D bit is reset as designated in S content. 2.00 2.80 3.16 Bit content of S2 which is designated in S1 4.16 content is transferred to CARRY FLAG. 3.96 3~9 The sum of bits under ON, of bits in S content, is 3~16 counted and the result is stored in D. 3~30 2.76 S content is shifted by 1 bit to the right. The content entered in D is shifted to most significant bit and the content of least 2.64 significant bit is shifted to CARRY FLAG. 3.52 3.36+0.56n S content is shifted by designated bit number 3.36+0.56n (K) to the right. 3.80+0.96n 2.76 S content is shifted by 1 bit to the left. the content entered in D is shifted to most significant bit and the content of least 2.64 significant bit is shifted to CARRY FLAG 3.28 3.36+0.56n S content is shifted by designated bit number 3.36+0.56n (K) to the left. 3.88+0.96n 3.76 S content is shifted by 1 bit to the left (L/R=ON) 3.76 [right (L/R=OFF). 4.28 4.52+0.48n S content is shifted 1 bit by designated bit number (K) to the left (L/R=ON) 4.52+0.48n [right )L/R=OFF)]. 4.68+0.80n Upon comparison of S1 content with S2 content, either one of >, =, < FLAGS is turned ON from the size relation between the two.

Page 171

Classification

Lower significant shift

FIFO

Fifo write

Fifo read

Rotate Program branching

Function

SUP UP2 WUP DUP

S

K

8bits

91 UP1

UP1

S1

S2

4bits 8bits 16bits 32bits 8bits 16bits 32bits 8bits 16bits 32bits

255 SDOWN 256 DOWN 257 WDOWN 258 DDOWN 160 FIFW 161 WFIFW 162 DFIFW 163 FIFR 164 WFIFR 165 DFIFR

SDOWN DOWN

S

K

WDOWN

DDOW

FIFW WFIFW DFIFW

S

D1

D2

FIFR WFIFR DFIFR

S

D1

D2

Stack shift input

68 SFIN

SFIN

S

Stack shift output

69 SFOUT

SFOUT

D1

8bits 16bits 32bits Rotate to right 8bits Without 16bits carry 32bits 8bits With 16bits carry 32bits Rotate to left 8bits Without 16bits carry 32bits 8bits With 16bits carry Rotate 32bits to right/left Without 8bits 16bits carry 32bits

233 RRC 234 WRRC 235 DRRC 242 RR 243 WRR 244 DRR 236 RLC 237 WRLC 238 DRLC 245 RL 246 WRL 247 DRL 239 RLRC 240 WRLRC 241 DRLRC 248 RLR 249 WRLR 250 DRLR

RRC WRRC DRRC

S

K

RR WRR DRR

S

K

RLC WRLC DRLC

S

K

RL WRL DRL

S

K

Jump

D S

L/R RLRC T WRLRC DRLRC L/R

D2

S

Execution time (µs)

6.34+1.10n Data in area with S on its head address and with 5.20+0.92n data number designated with K are shifted to upper significant direction. The least significant data is 0. 5.52+0.92n 5.76+1.68n Data in areas from S1 up to S2 are shifted at unit of 1 4.52+0.92n byte. Least significant data remains unchanged. 6.62+0.94n Data in area with S on its head address and with 5.28+0.92n data number designated with K are shifted to lower 5.76+0.92n significant direction. Most significant data is 0. 5.88+1.68n 5.84 S content is transferred to the address shown with ( offset value shown with D1 address + D2 content). 6.36 Furthermore, +1 is added to D2 content. 7.12 5.88+1.00n S content is transferred to D2. Data in the area with S as its head address and with D1 content as its data number are shifted to lower 6.08+1.00n significant direction. Furthermore, -1 is added to D1 content. 6.40+1.84n The areas from S address up to D address are deemed as STACK and the content of S is all stacked.

However, 0 is deemed as "no data".

S content is transferred to D2.

The data from D1 address up to S-1 are shifted to upper significant direction. D1 content is made to 0.

6.68+0.84n 9.94+0.96n

3.72+0.48n S content and CARRY FLAG are rotated to the right, 3.72+0.48n by the bit number designated with K. 4.48+0.88n 3.72+0.48n S content is rotated to the right, by the bit number 3.72+0.48n designated with K. 4.52+0.88n 3.72+0.48n S content and CARRY FLAG is rotated to the left, by 3.72+0.48n the bit number designated with K. 4.48+0.88n 3.72+0.48n S content is rotated to the left, by the bit number 3.72+0.48n designated with K. 4.52+0.88n 4.52+0.48n S content and CARRY FLAG are rotated to the left 4.52+0.48n (L/R =ON) [right (L/R=OFF), by the bit number designated with K. 5.60+0.88n 4.52+0.48n S content is rotated to the left (L/R=ON) [right (L/R 4.52+0.48n =OFF)], by the bit number designated with K. 5.60+0.88n

RLR WRLR DRLR

S

272 JMP

JMP

Ln

Jumped into label No. Ln.

8.00

Sub-routine call

273 CALL

CALL

Sn

Sub routine of label No. Sn is executed and steps following this command example are executed.

14.20

Return from sub routine

464 RET

RET

After termination of subroutine, the steps following the CALL command which called applicable subroutine are executed.

5.40 4.56 4.64

T

Repeating start

472 FOR

FOR

K

This command - NEXT command are repeated K times.

Repeating start (indirect)

476 FORN

FORN

S

This command - NEXT command are repeated by the frequency shown with S content. -1 is deducted from S content whenever executed.

Repeating end

480 NEXT

NEXT

Program from FOR and FORN commands up to this command is repeated by the frequency designated with FOR, FORN commands.

4.24(FORN)

440 MC 444 MCR

MC MCR

Output command of the master control range from SET up to RESET is controlled . Normally controlled if MO command input is ON and all OFF if the same command input is OFF.

5.96 3.86

I/O refresh

280 RIO

RIO

External input ON/OFF information is transferred to Device X and the ON/OFF information of Device Y is transferred to the external output unit.

23.28 +0.18n

Input refresh

281 RI

RI

D

K

External input data of Kbyte portion is transferred to Device X 8.84+1.32n from the address of D.

Output refresh

282 RO

RO

D

K

ON/OFF information on Device Y of Kbyte portion is transferred to external output unit from D address,

9.64+1.08n -

Master control I/O control

Symbol word

251 SUP 252 UP2 253 WUP 254 DUP

With carry

Label

Command

4bits 8bits 16bits 32bits

Shift

Upper significant shift

No.

Set Reset

K

4.04(FOR)

Main program start

448 START

START

Indicating start-up of main sequence program.

Main program end

452 END

END

Indicating end of main sequence program.

-

Program end

456 PEND

PEND

-

Label

460 LABEL

LABEL

Indicating end of sequence program including subroutine. Indicating division and jump of sequence program .

S,D: Register

H:Hexadecimal constant

K:decimal constant

Ln n: Label No.

7-52

1.48

Page 172

Others

Special Module

Classification

No.

Command

Symbol word

Function time (µs)

High speed counter data read High speed counter data write

316 HCR

HCR

S1

317 HCW

HCW

S1

S2

H

Common I/O data read

318 IOR

IOR

S1

S2

H

Directly reads internal memory of analog module.

3+120n

Common I/O data write

319 IOW

IOW

S1

S2

H

Directly writes data in internal memory of analog module.

15 +78.5n

304 SPR

SPR

S1

S2

S3

Directly reads internal memory of serial I/O module.

306 SPW

SPW

S1

S2

S3

Directly write data in internal memory of serial I/O module.

Annunciator

291 ANN

ANN

H

User defined clock

293 USC

USC

K1

Built-in clock 30 sec correction

292 ADJ

Special module byte data read Special module byte data write

S2

Directly reads internal memory of high speed counter module. Directly writes data in internal memory of high speed counter module.

Execution

151 3+115n

633 +250n 371 +383n

S

Message data and time in the 16Byte area with code H and S on its head

K3

User defined clock 1, 2 in special relay are set up.

75.42

ADJ

30 sec correction is made to the built-in clock. Less than 30 sec is rounded off. More than 30 sec is counted up as 1 minute.

188

The communication speed for peripheral equipment is changed into the speed designated with K.

55.46

K2 address are transferred to the annunciator area of special register.

141.88

Communication speed setting for peripheral equipment

288 BAUD

BAUD

Program stop

287 STOP

STOP

Run of sequence program is stopped.

-

Scan time reset

46 WDR

WDR

The scan time monitor timer is reset.

52

S,D: Register

H: Hexadecimal constant

K

K: Decimal constant

7-53

Page 173

(5) Exclusive applied commands for PC3J Transfer commands

Classification Bit block transfer 4bit 8bit 16bit

Inversion

Address constant transfer Binary

Constant addition

Arithmetic computation

Binary

BCD

Binary

Constant multiplication BCD

Command word

Function

27~39 +0.34n(Bit)

8.76+1.72n

121 BBMOV

BBMOV

Sh1 Dh2

K

Bit data with bit position represented by h1 of S at its head and with points represented by K is transferred to an area with bit position represented by h2 of D at its head.

259 STURN 260 TURN 261 WTURN

STURN TURN WTURN

S

K

Transfer to area with D as its head address in inverse sequence from last data in data area with S as its head address and with points represented by K.

320 MOVAD

MOVAD

D

S

323 +H 324 W+H

+H W+H

32bit

325 D+H

D+H

S

2 digits

326 +HP 327 W+HP

+HP W+HP +

S

8 digits

328 D+HP

D+HP

S

8bit 16bit

329 -H 330 W-H

-H W-H

S

32bit

331 D-H

D-H

S

2 digits 4 digits

332 -HP 333 W-HP

-HP W-HP

8 digits

334 D-HP

D-HP

S

8bit 16bit

335 *H 336 W*H

*H W*H

S

S

S

32bit

337 D*H

2 digits 4 digits

338 *HP 339 W*HP

*HP W*HP

S

8 digits

340 D*HP

D*HP

S

8bit 16bit

341 /H 342 W/H

/H W/H

S

D*H

D H

D H

K

D

Statistic processing

Logic computation

BCD

Constant logic product Constant logic sum Constant exclusive logic sum Sum Max value retrieval Min value retrieval

Others

Mean

32bit

343 D/H

D/H

2 digits 4 digits

344 /HP 345 W/HP

/HP W/HP

8 digits

346 D/HP

8bit 16bit

S

D/HP

S

347 ANDH 348 WANDH

ANDH WANDH

S

32bit

349 DANDH

DANDH

D

8bit 16bit

350 ORH 351 WORH

ORH WORH

32bit

352 DORH

DORH

8bit 16bit

353 XORH 354 WXORH

XORH WXORH

32bit

355 DXORH

8bit 16bit 32bit 8bit 16bit 32bit 8bit 16bit 32bit 8bit 16bit 32bit

362 STI1 363 WSTI1 364 DSTI1 374 MAX 375 WMAX 376 DMAX 377 MIN 378 WMIN 379 DMIN 380 AVE 381 WAVE 382 DAVE

S

S

MAX WMAX DMAX

MIN WMIN DMIN

AVE WAVE DAVE

H

H

S S1

S1

S1

S1

D

4.60

39~50 160~180

28~30

After S content and constant H were divided, the result is stored in address next to S and remainder stored in next next address . The data are all handled as binary value.

77~82

After S content and constant K were divided, the result is stored in D and

21.26 remainder stored in next address. The data are all handled as BCD.

56.92

D

After logic sum (OR) of S content and constant H was computed,the result is stored in D.

H

After logic sum (OR) of S content and constant H was computed,the result is stored in address next to S.

D

After exclusive logic sum (XOR) of S content and constant H was computed, the result is stored in D.

H

After exclusive logic sum (XOR) of S content and constant H was computed, the result is stored in address next to S.

149~164 2.40 2.40 3.96 2.40 2.40 3.96 2.72 2.72 3.96

S2

The sum in data area with S1 as head address and with number represented by S2 content is stored in D. The data are all handled as binary value.

S2

Maximum value in data area with S1 as head address and with number represented by S2 content is stored in D.

5.56+1.00n

S2

Minimum value in data area with S1 as head address and with number represented by S2 content is stored in D.

5.72+1.00n 5.72+1.00n

Mean value in data area with S1 as head address and with number

33.24+1.08n represented by S2 content is stored in D. The data are all handled as binary

82.08+1.32n

S2

Subroutine is closed when the conditions are met, and applicable

Conditional return

285 CRET

CRET

Area designated I/O refresh

295 ARIO

ARIO

Applied command flag clear mode setting Applied command flag clear mode resetting

300 SYS

SYS

4

1

0

300 SYS

SYS

4

0

0

S,D: Register , H: Hexadecimal constant

1.24

17~19

The data are all handled as binary value.

value and fractions over 4 at first decimal point are counted as one.

subroutine is called and executed from step next toCALL command.

D

22.76 55~67 stored in next address.

After logic product(AND) of S content and constant H was computed, the result is stored in address next to S.

D

4.52 6.92

After S content and constant H were divided, the result is stored in D and remainder

H

D

3.20 3.20

23.04

After logic product (AND) of S content and constant H was computed, the result is stored in D.

D

58~64

13~15

D

D

7.80 23.80

After S content and constant K were multiplied, the result is stored in D. The data are all handled as BCD.

After S content and constant K were divided, the result is stored in address next to S and remainder stored in next next address. The data are all handled as BCD.

K

S

DXORH

STI1 WSTI1 DSTI1

H

2.40

After S content and constant H were multiplied, the result is stored in the address next to S. The data are all handled as binary value.

address next to S. The data are all handled as BCD.

D

K

The data are all handled as binary number.

After S content and constant H were multiplied, the result is stored in D. The data are all handled as binary value.

After S content and constant K were multiplied, the result is stored in the

K H

After S content and constant K were deducted, the result is stored in D. The data are all handled as BCD. address next to S.

D

K

S

After S content and constant K were added, the result is stored in D. The data are all handled as BCD.

S content and constant K are deducted and the result is stored in the

H

H

4.04

S content and constant H are deducted and the result is stored in D. The data are all handled as binary number. D

H

S

S content and constant H are added and the result is stored in the address

D

K

S

After S content and constant H were added, the result is stored in D. Data are all handled as binary value.

After S content and constant H were deducted, the result is stored in D. The data are all handled as binary value.

K

8.76+1.72n 0.72

S content and constant K are added and the result is stored in the address next to S. The data are all handled as BCD.

H

8.76+2.36n

2.40

K H

(µs)

S is stored in D after changed into indirect address.

next to S. The data are all handled as binary number.

Binary

Constant dividing

Execution time

Symbol

8bit 16bit

BCD 4 digits

Constant deduction

No.

K

K:decimal constant

7-54

External I/O of Kbyte portion from D address are refreshed. Set up so that applied command flag is cleared at reading of applied command . Set up so that applied command flag is not cleared at reading of applied command.

6.12+0.84n 7.00+1.08n 7.80+1.52n 5.72+1.00n 6.20+1.60n

6.20+1.60n

131+1.44n 5.40 16.00+2.40n 81.70 82.10

Page 174

Others

Classification

No.

Comma

SYS Clock adjustment instruction (PC3J series ver2.6~) *1

300

SYS

Symbol nd word

S,D: Register , H: Hexadecimal constant

5

SYS

Function

S

0

Execution time (µs)

The clock in CPU is adjusted by “the minute second day hour year month week” of the 4-word which makes the address of S a head.

K:decimal constant

*1 PC3JG PC3JBG PC3JP can use this instruction. PC3JL, PC3JD, PC3JB, PC3JM can use this instruction since version 2.6. PC3J PC3JNF PC3JNM can not use this instruction.

(6) Exclusive applied commands for PC3JG

Others

Transfer commands

Classification

No.

Command

Symbol word

Function register address setting

371 BRSET

BRSET

S

Buffer Indirect loading register transfer

372 WBR

WBR

S

D

K

Indirect saving

373 WBW

WBW

S

D

K

Order the message command for DLNK-M2

302 MSET

MSET +

H

S

D

Order the I/O resister read-out instruction for TOYOPUC-PCS

370 CSET

CSET

H

S

D

S,D: Register , H: Hexadecimal constant

D

K:decimal constant

7-55

The Indirect address of the buffer register(EB) specified S is set to the 2 word area with D as the head address. Data in buffer registers which of address is the content of 2 word area with S as the head address is transferred to registers with D as the head address. Size is K. Registers with S as the head address is transferred to buffer registers which of address is the content of 2 word area with D as the head address. Size is K. Message of the number indicated with H which of head address is S are tranfered to DLNK-M2 indicated with H. The response data from DLNK-M2 are trnsfered to the area which of head address is D. I/O register read-out instruction of the number indicated with H which of head address is S are transferred to PCS. The response data from PCS are transferred to the area which of head address is D

Execution time (µs)

0.96

80+2n

80+2n

80+4n

60+4n

Page 175

7.2.8

Equipment Information Memory

The equipment information memory is available to store comments, etc. on sequence circuits separately from sequence program, parameters and data. This equipment information memory of 640KB capacity can normally store 10,000 points or more , where limited to the address comments only. The number of storable comments differs depending on the content of comment. Storing comments ,etc. in the equipment information memory is effected by peripheral equipment ( PCwin). The peripheral equipment (PCwin) can display commented circuit diagram, cycle chart, etc. by reading the information stored in the equipment information memory. Storing and reading in/from the equipment information memory can be made by the peripheral equipment (PCwin) for the PC3J , irrespective of CPU operation mode. The PC2 Series peripheral equipment (GL1, etc.) can not store and read data in/from the equipment information memory. Further, it is impossible to change the information stored in the equipment information memory and to store data in the same memory in sequence program. Also it is impossible to refer to the stored information in accordance with sequence program.

Peripheral Equipment (PCwin) Equipment Information Memory

640KB comments, etc.

User Memory Sequence program, Parameters, Data

PC3JG CPU Displays commented circuit diagram, etc. based on information stored in the Equipment Information Memory. 7-56

Page 176

7.3 Link specification (1) Communication port and Link function Communication port

Link function

Communication port L1

SN-I/F or PC link or Commputer link

Communication port DLNK

DLNK-M2

(Note)When the “Communication port L1” (built-in standard link) parameters are not set, acts as SN-I/F. It operates as CMP for PC2 interchangeable mode. (2) Computer link specification (Communication port L1) Items Interface standard Communication system Transmission line Communication speed Transmission distance Transmission form Number of stations Data type

Characters used Error detection *1

Specification Conforming to EIA RS-422 Start-stop synchronous, semi-dual Shielded twist bare cable 0.3,0.6,1.2,2.4, 4.8,9.6,19.2,38.4kbps

(Presetting*1)

Max 1 km (total length) 1:N Max 32 stations (Address No. 00 ~ 37) [set with octal number ) Start bit ...........1 bit Data length .....7 or 8 bit (presetting) Parity ..............1 bit (even parity Stop bit ...........1 or 2 bit (presetting) ASCII code Parity check, sum check

It is set up by the link parameter.

7-57 the link

Page 177

(3) PC link specification (Communication port L1) Items

Specification

I/O points Transmission points per station No. of stations

Max 512 points/1 port When 19/.2kbps/57.6kbps is selected : Max 384 points When NC×3 selected : Max 512 points Max 16 stations (master 1, slave 15 ) /1 line

I/O allocation Transmission distance

Minimum setting unit :8 points Max 1 km (total length)

Signal level

Conforming to EIA RS-422

Communication speed Synchronous system

19.2kbps / 57.6kbps / NC×3speed *1 Start-stop synchronous

Transmission system

Semi-dual system (2-wire type)

Bit composition

JIS 7 unit system, 10 bits

Check system

Vertical parity, horizontal parity (Even number)

Cable Transmission data at CPU stopping CPU operation against communication error Communication error under connection sequence

Shielded twist bare cable

(Presetting*2)

OFF data / Pre-stop data (Presetting*2) Stop/RUN continue (Presetting*2) As error /repeat (Presetting*2)

*1 This speed is set to communicate with NC machine corresponding to M-NET×3 speed. *2

It is set up by the link parameter.

(4) SN-I/F specification (Communication port L1) Items

Specification

Data link

I/O : 32byte,

Transmission distance

Signal level

Max 3 m (only inside of controller box) Parity ............. 1 bit (even parity) Data length .... 8 bit Stop bit........... 1 bit Conforming to EIA RS-422

Synchronous system

Start-stop synchronous

Transmission system

Semi-dual system (2-wire type)

Communication speed

288kbps

Cable

Shielded twist bare cable

Data type

7-58 register : 32byte

Page 178

(5) DLNK-M2 specification (Communication port DLNK) No.

Items

1 Data rate

Specification 500 / 250 / 125 Kbps

500Kbps

Below 100m

Below 6m

Total expansion of drop line Below 39m

250Kbps

Below 250m

Below 6m

Below 78m

125Kbps

Below 500m

Below 6m

Below 156m

Maximum cable distance

Data rate 2

Communication distance

(selectable by switch) Drop line length

Maximum number 3 of connected 64 units (master 1 unit slave 63 units) *1 nodes 4 Node address Master : 00 Slave : 01 ~ 63 I/O points number Input: Maximum 2048 points (256 bytes) 5 of DLNK Output: Maximum 2048 points (256 bytes) 6 I/O allotment Minimum unit of 8 points Communication 7 X·Y,M,L,EX · EY,EM,EL,GX·GY,GM *2 area 8 Function I/O refresh, message command *1 In the case of TOYOPUC DLNK, this applies only to the asynchronous mode. There are no relations in input and output type, and the number of maximum connection notebooks is restricted with synchronous mode in the following. Data rate

Maximum number of connected nodes

500kbps 250kbps 125kbps

9 7 6

*2 GX/GY and GM area can be used in the PC3JG separate mode.

7-59

Page 179

7.4 I/O Specification 7.4.1 Allocation of connector pin (a) PC3JG

Pin arrangement

0~1F(Left Connector) Pin No. A1 A2 A3 A4

When it was seen from the front of the module.

Signal COM2 (0V) COM2 (0V) COM2 (0V) COM2 (0V)

Pin No. B1 B2

20~3F(Right Connector) Signal

PWR2 (+24V) COM1 (+24V)

Pin No. A1 A2

Signal COM4 (0V) COM4 (0V)

Pin No. B1 B2

Signal PWR4 (+24V) COM3 (+24V)

B3

-

A3

-

B3

-

B4

-

A4

-

B4

-

A5

Y1F

B5

X0F

A5

Y3F

B5

X2F

A6

Y1E

B6

X0E

A6

Y3E

B6

X2E

A7

Y1D

B7

X0D

A7

Y3D

B7

X2D

A8

Y1C

B8

X0C

A8

Y3C

B8

X2C

A9

Y1B

B9

X0B

A9

Y3B

B9

X2B

A10

Y1A

B10

X0A

A10

Y3A

B10

X2A

A11

Y19

B11

X09

A11

Y39

B11

X29

A12

Y18

B12

X08

A12

Y38

B12

X28

A13

Y17

B13

X07

A13

Y37

B13

X27

A14

Y16

B14

X06

A14

Y36

B14

X26

A15

Y15

B15

X05

A15

Y35

B15

X25

A16

Y14

B16

X04

A16

Y34

B16

X24

A17

Y13

B17

X03

A17

Y33

B17

X23

A18

Y12

B18

X02

A18

Y32

B18

X22

A19

Y11

B19

X01

A19

Y31

B19

X21

A20

Y10

B20

X00

A20

Y30

B20

X20

The external connectors are the following.

Type Specification 40 pins , soldering type FCN-361J040-AU FCN-360C040-B 40 pins , case The size of the screw of the connector is M2.6 . Fujitsu*1 Fujitsu*1

Type for TMW TIP-5867

And, it Can be Connected with the FCN-360 jack type (for the gold plating) made by Fujitsu Takamisawa Component Ltd.. Be sure to use contact goods for the gold plating. *1 : Fujitsu Takamisawa Component Ltd.. 7-60