Manual · Toyopuc
Programmable Controller TOYOPUC PC3JG-P-CPU TIC-6088 / PC3JG-CPU TIC-6125 Operation Manual
Manual387 pagesPDF 16 MB
Operation manual for the TOYOPUC PC3JG-P-CPU (TIC-6088) and PC3JG-CPU (TIC-6125) programmable controllers and their I/O modules.
What this file really is
The old site listed this file as a manual for the Toyopuc HPC-LINK, OUT-15 and 2 more models. Filed as an OUT-15 user manual, this is the operation manual for the TOYOPUC PC3JG CPU modules, which includes the I/O and output module specifications.
Names · 2 models
The models it names
Filed with · 2 models
Also filed with these models on the old site
Summary
What is in it
The JTEKT operation manual for the TOYOPUC PC3JG CPU modules (PC3JG-P-CPU TIC-6088 and PC3JG-CPU TIC-6125). It covers system components, installation and wiring, initial CPU setting, test run, error alarms and troubleshooting, battery and fuse maintenance, and full specifications for the CPU, I/O, output modules such as the OUT-15, power and selector modules. Later chapters explain the link functions, the built-in computer link, PC Link and DLNK-M2, message display, SFC programming and dimensional drawings.
Its parts
- System Components
- Installation and Wiring
- Initial Setting
- Test Run
- Error Alarm
- Maintenance
- Specifications
- Link Function
- Built-in Function
- Message Display
- SFC Programming (Sequential Function Chart)
- Tool
From the manual
Key facts from this manual
Each line names its page in the PDF.
The operation manual (15th edition, November 2008) for the TOYOPUC PC3JG-P-CPU (TIC-6088) and PC3JG-CPU (TIC-6125) programmable controller. Its specification chapter also covers the system's modules, including the OUT-15 and OUT-18 DC output modules, the THU-2765 selector module and the power modules; the HPC-LINK appears only in the table of components. It explains installation, setup, error codes, battery and fuse maintenance and the module specifications.
- Module type
- 16-point DC output, (-) common: OUT-15 MOS-FET (THK-2790), OUT-18 transistor (THK-2753) p. 14
- Commons
- 8 points per common, insulated between commons p. 194, 196
- Isolation
- Photo coupler insulation p. 194
- Off-state leakage
- 0.1mA max p. 194
- Terminal block
- Detachable, held by top and bottom lock levers p. 200
- Ambient temperature
- 0 to 55 C (common to each module) p. 120
- OUT-15 rating
- Rated DC5/12/24V (4.75 to 30V), 1A per point, 4A per common; on 2ms, off 6ms max p. 194
- OUT-18 rating
- Rated DC12/24V (10 to 30V), 0.5A per point, 2A per common; on and off 1ms max p. 196
- Internal current (5V)
- OUT-15 310mA, OUT-18 136mA, all points on p. 194, 196
- Fuses
- OUT-15 6.3A per common; OUT-18 3.2A per common, soldered and not replaceable p. 194, 196, 202
- Fuse-blown detection
- OUT-15 lights its ALM LED and can stop the CPU (error code 43); OUT-18 has none p. 202
- THU-2765 selector
- Sets rack No. and head I/O address of an added base; 31mA, 35 x 130 x 110 mm, 0.16kg p. 207
- PC3JG CPU
- TIC-6088: 180K word memory, 32 inputs and 32 outputs built in p. 14
- Power modules
- POWER1 THV-2747 AC85 to 264V in; POWER2 THV-2748 DC24V in; both DC5V 4A out p. 14
What this manual walks you through
- Finding module part numbers in the system components table p. 14, 15
- Removing and refitting an I/O terminal block p. 200, 201
- Choosing whether a blown output fuse stops the CPU p. 202
- Setting the rack number and I/O address on the selector module p. 208
- Replacing the CPU battery p. 115, 116
- Understanding error ranks p. 61
- Reading the E/A lamp and the error code table p. 62, 63
- Adding up module current consumption p. 382
- Rush current on OUT-15 and OUT-16 outputs p. 385
- General specifications for every module p. 120
Good to know
- On the OUT-15 and OUT-16, rush current can flow for 1 to 2 ms when 24V is suddenly applied to the load, even with the output off. p. 385
- The manual states that this rush current is not enough to turn on ordinary valves (solenoids). p. 385
- On the OUT-15, the 2A rating for two points needs both points switched on and off together. p. 194
- The OUT-18 fuse only protects the circuit board from burning, not the output elements. p. 196
- On the selector module, rack No. F or a duplicated rack No. causes an error. p. 208
Questions this manual answers
What is the maximum load current of the TOYOPUC OUT-15?
1A per point, or 2A across two points switched together, with 4A per common. p. 194
Can the fuse on a TOYOPUC OUT-18 be replaced?
No. The OUT-18 fuse is soldered to the board and cannot be replaced. p. 202
What is the TOYOPUC THU-2765 used for?
It is the selector module used on an additional base, to set that rack's number and head I/O address. p. 207
What battery does the TOYOPUC PC3JG CPU use?
The TIP-5426 lithium rechargeable battery; the manual gives about 5 years as a replacement guideline. p. 115
What error code does a blown OUT-15 fuse cause?
With the error setup jumper on, the CPU stops RUN with error code 43; with it off, RUN continues and only the ALM LED lights. p. 202
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 44 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- FOREWORD1-3
- Pages 4 to 64-6
- Pages 7 to 107-10
- 1. SYSTEM COMPONENTS11-20
- 2. Installation and wiring21-33
- 3. Initial Setting, pages 34 to 4234-42
- 3. Initial Setting, pages 43 to 5143-51
- 3. Initial Setting, pages 52 to 5952-59
- Pages 60 to 6960-69
- Pages 70 to 7970-79
- Pages 80 to 8980-89
- Pages 90 to 9990-99
- Pages 100 to 109100-109
- Pages 110 to 114110-114
- 6. Maintenance115-119
- 7. SPECIFICATIONS, pages 120 to 129120-129
- 7. SPECIFICATIONS, pages 130 to 139130-139
- 7. SPECIFICATIONS, pages 140 to 149140-149
- 7. SPECIFICATIONS, pages 150 to 159150-159
- 7. SPECIFICATIONS, pages 160 to 169160-169
- 7. SPECIFICATIONS, pages 170 to 179170-179
- 7. SPECIFICATIONS, pages 180 to 189180-189
- 7. SPECIFICATIONS, pages 190 to 199190-199
- 7. SPECIFICATIONS, pages 200 to 209200-209
- 7. SPECIFICATIONS, pages 210 to 214210-214
- 8. Link function215-225
- 9. Built-in function, pages 226 to 235226-235
- 9. Built-in function, pages 236 to 245236-245
- 9. Built-in function, pages 246 to 255246-255
- 9. Built-in function, pages 256 to 265256-265
- 9. Built-in function, pages 266 to 275266-275
- 9. Built-in function, pages 276 to 285276-285
- 9. Built-in function, pages 286 to 295286-295
- 9. Built-in function, pages 296 to 305296-305
- 9. Built-in function, pages 306 to 315306-315
- 9. Built-in function, pages 316 to 325316-325
- 9. Built-in function, pages 326 to 335326-335
- 9. Built-in function, pages 336 to 345336-345
- 9. Built-in function, pages 346 to 355346-355
- 9. Built-in function, pages 356 to 359356-359
- 10. Message display360-367
- 11. SFC Programming(Sequential Function Chart)368-370
- Pages 371 to 379371-379
- Pages 380 to 387380-387
The file