Page 100
75
78
Master control error
Read out sequence program by peripheral device.
N N
Possible to know applicable applied command which resulted in error, from the error-related information.
Special module corresponding applied command not available.
The nesting of master control exceeds 16 multiple.
Y
Application instruction error 2
Y
*1
Install applicable special module.
Keep the nesting within 16 multiple. REPAIRED?
Y
N
Y
END
REPAIRED?
N
N
END
Error exists in applied command operand and data.
N
MC command and MCR command are not in pair.
Y
*1
Y Replace applicable special module.
Revise the program so that MC command and MCR command become a pair.
Error exists in applied command operand and data. Correct them. Y
Replace CPU module.
REPAIRED?
N
END
Replace CPU module. Y REPAIRED?
N
END
Replace I/O cable
REPAIRED?
N Replace the base.
5-40
Y
END
Page 101
79
7A
FOR-NEXT error
Read out sequence program by peripheral device.
Read out sequence program by peripheral device.
N
FOR command or FORN command and NEXT command are not in pair.
Y
N
*1
CALL command and RET command not in pair.
Y
Correct the program so that FOR command or FORN command and NEXT command become a pair.
Y
Y REPAIRED?
N
N
END
The nesting of FOR-NEXT or FORN-NEXT exceeds 128 multiple
Y
END
Replace CPU module.
*1
Keep the nesting at 128 multiple or less.
*1 See the error-related information.
Y REPAIRED?
N
*1
Correct the program so that CALL command and RET command become a pair.
REPAIRED?
N
RET error
END
Replace CPU module.
5-41
Page 102
7B
RETI error
Read out sequence program by peripheral.
Y
Is there a RETI instruction at the end of interrupt program?
N
*1
Add a RETI instruction.
Y
Repaired? N
N
End
Is there a RETI instruction anywhere other than at the end of interrupt program?
Y
*1
Delete the RETI instruction
Y Repaired? N
End
Replace CPU module.
*1 See the error-related information.
5-42
Page 103
7D
76
PRG. END execution
Label Table error
Read out sequence program by peripheral device.
Read out sequence program by peripheral device.
N
N No END command Y
LABEL command corresponding to JMP command not available.
Y
Add END command.
*1
Correct the program so that JMP command and LABEL command correspond to one another.
Y REPAIRED?
Y REPAIRED?
N N
END
N
Program structure such as jumps END command
N
Y
LABEL command corresponding to CALL command not available
Y Correct the program.
END
*1
Correct the program so that CALL command and LABEL command correspond to one another.
Y REPAIRED?
N
END
REPAIRED?
Y
N N
No RET command exists in subroutine.
END
Rewrite program and parameter.
Y Add RET command.
REPAIRED?
N
Y
Y
END
REPAIRED?
N
Replace CPU module.
END
Replace CPU module.
*1 see the error-related information.
5-43
Page 104
77
Parameter setup-value error
Read out parameter peripheral device.
N by
I/O address setup error
Check which module is error, from the error-related information.
I/O address allocation exceeds "1FF".
Parameter value out of the specified range
Y
Y
N Set I/O address allocation so as not to exceed "1FF".
Replace selector module.
Correct and write parameter value. Y
REPAIRED?
REPAIRED?
N
49
Y
N
END
END
Replace CPU module.
Replace CPU module.
REPAIRED?
Y
N
END
Replace I/O cables in sequence.
REPAIRED?
N
Replace the base.
5-44
Y
END
Page 105
81
88
Special module allocation-over
Total the common memory capacity of special modules. *1
Check the quantity of special modules in use.
N
Reduce the quantity of special modules in use.
The quantity of special modules in use exceeds 8 modules.
Y
Y REPAIRED?
N
Excessive No. of special modules
Reduce the quantity of special module in use.
END
Replace CPU module.
Y REPAIRED?
N
Y REPAIRED?
N
END
Replace CPU module.
END
Special module quantity over
Y REPAIRED?
N
END
Replace selector module.
REPAIRED?
N
Y END
Replace the base. *1 For the common memory capacity, refer to the consuming memory capacity described in the individual instruction manual for each module. Keep the total common memory capacity at 60K bytes maximum.
5-45
Page 106
82
Check which module is error, from the error-related information.
N
84
Special module parameter error
Special module installed imperfectly.
Special module error
Check which module is error, from the error- related information or special module ERROR
Check error existence or non-existence, in reference to the instruction manual for applicable module.
Y Error exists.
Install special module exactly.
REPAIRED?
N
Reset ERROR, in reference to the instruction manual for applicable module.
Y
N
N
Y
END
Check the respective installed condition of CPU module, selector modules, I/O modules, special modules, and I/O cables.
Y Error exists.
Foreign matter is included in connector which connects special module to the base.
Install exactly.
N
Y
Replace CPU module.
Remove foreign matter.
Y REPAIRED?
Y
N
REPAIRED?
N
END
Replace selector modules in sequence.
END
Replace special module.
Y REPAIRED?
N REPAIRED?
N
END
Replace the base.
Y Y
END
REPAIRED?
N Replace I/O cables in sequence.
5-46
END
Page 107
83
N
Excessive number of interrupt
Y
Is the number of interrupt modules over 4?
8A
External interrupt error
Does this error occur frequently?
N
Y
Reset/Start
Reduce the number of interrupt modules in use.
Y Repaired? Y
Repaired? N N
N End
END
Replace the external interrupt module.
*1
Replace CPU module Y Repaired? N Repaired? N N
Y
END
Replace CPU module. End
Replace I/O cables one by one.
Repaired? N N
Y End
Replace I/O base and CPU base one by one.
*1:Refer to the error-related information.
5-47
Page 108
86
89
Link communication error
Link module allocation error
Check which link module is error, from the error-related information.
Check which link module is error, from the errorrelated information.
Reset ERROR, in reference to the individual instruction manual for applicable link module.
Correct the link module allocation parameter of applicable module.
85
Link parameter error
Check which link module is error, from the error-related information.
Sequence CPU program alarm
A5
System program alarm
A7
System parameter alarm
AA
Correct the link parameter of applicable module.
Y
Is this error frequently occurred?
N Reset · start
Repair
Y
N
END
Replace battery
Repair N
Y
Y
Is battery charged adequately?
N
END
Charge battery.
Replace CPU module.
Repair N
5-48
Y
END
Page 109
8B
NC communication alarm 1
8C
NC communication alarm 2
8D
2-port RAM alarm 1
8E
Communication data verification alarm 1
Y
Does the error persist?
N Reset and start or reset the communication.
Restored
Y
N
N
Securely install.
End
Are the CPU and NC modules installed properly?
Y
1. CPU module fault 2. NC module fault 3. NC rack fault
5-49