Page 110

5.7.3

I/O module trouble analysis This paragraph describes trouble items in input circuits and output circuits, and the method of corrective actions to be taken against them. (1)

EX.)

(LS1) X000

How to search error content

When the output load of OUTPUT module fails to turn ON;

(LS2) X001

Y020

Y020

Output load fails to turn ON.

OUTPUT module "RUN" LED is lighting?

N

ON

Y Y

OUTPUT module "ALARM" LED is lighting?

Replace OUTPUT module fuse.

Fuse blown even after replacement.

OFF INPUT

N The external supply power of OUTPUT module is connected?

N

Power voltage for loads is applied?

Rush current N is within the specification range of OUTPUT module?

wiring to each load and load itself.

What V is the voltage between each terminal and COM terminal of OUTPUT modules?

OV

Check input signal for OFF

Faulty NPUT module. Replace it. I/O address allocation parameter correct?

N

Y Correct the parameter.

Y Check and reset the

N

What V is the voltage between INPUT module and COM terminal?

N Check the power wiring for loads and reset the power line.

Y

Module "RUN" LED is lighting?

Y

Connect the external supply power line.

Y Check rush current when loads turns ON simultaneously under maximum condition.

Output Status monitor monitor ON?

OV

Supply power voltage voltage for load Change output relay No. and keep the simultaneous ON current of loads under maximum condition at the specified current and less.

Faulty OUTPUT module. Replace it.

Check and reset the wiring to loads and each load itself.

For any inquiry, feel free to contact JTEKT CORPORATION Higashi-Kariya Works, After-Sale Service Section

Check and reset external wirings and external input devices.

<Note 1> Against fuse blown in OUTPUT Module, CPU outputs error code "43", in addition to UTPUT Module "ALARM" LED ON. <Note 2> "RUN" LED is lit by internal circuit after insulated by photo coupler. Therefore, it does not light even when voltage is applied thereto from an external input terminal, unless DC5V power voltage is applied thereto.

IN

Input

COM

Circuit

<Note 3>

Insulation by photo coupler

Internal circuit

"RUN" LED

DC5V

For OUTPUT modules OUT-18, OUT-19, OUT-28D, OUT-29D, ALM LED does not light even against troubles such as fuse blown, etc

5-50

Page 111

(2)

Input circuit troubles and corrective actions

EX. 1)

Phenomena

Causes

Corrective actions and measures

Input signal OFF fail

· Leak current in external device (Current leak from TRIAC output snubber circuits (C,R) and surge absorber, etc.)

· Insert a bleed resistor between the terminals of input module to divide leak current in external device and to there by reduce input current to the input module.

Leak current

~

AC input module

Input signal OFF fail

· Current leak from Limit switch neon lamp

Leak current

~ EX. 3)

Input signal OFF fail

AC input module

Power source · Leak current caused by inter-cable capacity of wired cables.

Leak current

~

~ Input current <Input module OFF current>

Power source EX. 2)

* Bleed resistor

AC input module

· Identical to EX.1 · Or use a limit switch with less leak current.

· Identical to EX. 1 · Or use DC input power.

AC input module

Power source EX. 4)

Input signal OFF fail

· Leak current from two-wire sensors (proximity switch, photo switch) and limit switch with LED.

Leak current

EX. 5)

Input signal OFF fail

· Identical to EX. 1 · Or use switches with less leak current.

DC input module

· Drive power cable is wired in parallel · Isolate the drive power cable. to input signal cables and, as a result, over-noise is continuously transferred into the line. And the noise can not be removed even by noise removal circuit in the input module.

5-51

Page 112

* On previous page: How to decide bleed resistance Input device

Assuming input device current at OFF to be I, terminal-COMMON voltage at this time is determined as follows; V = I×2.5kΩ (IN-12 input resistance). The input device does not turn OFF unless this V value meets OFF voltage 7.2V and below. For that, connect a bleed resistor to there by reduce input impedance.

DC input Module IN-12

Current I

DC input Module IN-12

I = Leak current of device (mA) R = Bleeder resistance value (kΩ) W = W-number of bleeder resistor (W)

Bleeder resistance value is OK if it is such a value that terminal-COMMON voltage V comes to 72V or less. 2.5 × R From

[kΩ] × I <= 7.2 [V] 2.5 + R 18 R <=

[kΩ] 2.5 × I - 7.2

Also, W-number of resistor is determined as follows. (24 [V])2 From

W >=

× 2 (margin) R (kΩ) 1.15

W >=

EX.)

[W] R At leak current 5 mA.

From 18 R <= 2.5 × I - 7.2 R <= 3.39 [kΩ] R = 3kΩ assumed.

W-number of bleeder resistor:

1.15 From

W >=

[W] R

W >= 0.383 [W] W-number comes to 1 W= [W] 2

5-52

Page 113

(3)

Output circuit troubles and corrective actions Phenomena

EX. 1)

EX. 2)

At output OFF, overvoltage is applied to loads and OUTPUT module.

Load OFF fail.

Causes

Corrective actions and measures

· When half-wave rectification is internally made in load. (Some solenoid are half-wave rectification type.) Load

Output module

D1

Output module

C V1 R

· Connect OUTPUT module to load using a full-wave rectifier.

C R

~

V2

Load

· At output OFF, on occasion V1, and V2 come to 140V and around 200V respectively. · Leak current due to self - contained surge killer. Output module

C R

Output module

C R

EX. 3)

Output transistor breaks down. (Transistor output)

Load Leak current

A method of using valve (Hoko Industries, RF Valve) with full-wave rectifier is also available. · On occasion relays and neon lamps of small hold current fail to turn OFF. In such a case, connect a proper resistor in parallel to the load.

~

Induced Load

~

· Rush current of incandescent bulbs OUT

~

L

+ -

COM

On occasion, 10X or more rush current flows across the bulb momentarily at lighting.

·Output does not turned off occasionally when a low current inductive load is connected. In this case, please connect a suitable resistance (a bleeder resistance) in parallel with a load.(about 2kΩ) An inductive load which have a rectifer such as a bulit-in diode bridges is not possible to use. · To restrain rush current, flow the dark current equivalent to 1/3 –1/5 of the rated current of incandescent bulb. Output module (-)COM OUT L + Dark current COM(-)

Output module (+)COM OUT COM(-)

EX. 4)

When an inductive load is connected, output module results in Fuse blown.

· When loads connected to same fuse are started-simultaneously, the total starting current exceeds significantly the fuse rating.

5-53

Dark current L

+ -

· Take a proper measure not to allow the total start in current of loads, which are started simultaneously, to exceed the fuse rating.

Page 114

Phenomena EX. 5)

EX. 6)

Load OFF fail. (Parallel connection of output)

Output Transistor Breaks down. Transistor output module

Causes

Corrective actions and measures

· Leak current due to self-contained surge killer.

· When driving a load to which two output points of output module are connected, leak current due to self-contained surge killer comes to double. To prevent it, apply parallel processing by program.

Output module

Load

C R

Leak current

C R

Leak current

~

· Voltage was compulsorily applied to a load from another power source to check the wiring of output signal cables.

· Avoid how to check as described left. Even when E1 input voltage is turned OFF, current flows a diagrammed left though depending on power source.

Another power source + E2 Load

+ E1

5-54