Programmable Controller TOYOPUC PC3JG-P-CPU TIC-6088 / PC3JG-CPU TIC-6125 Operation Manual: 6. Maintenance

Pages 115 to 119 of 387, from Programmable Controller TOYOPUC PC3JG-P-CPU TIC-6088 / PC3JG-CPU TIC-6125 Operation Manual

The original document is the PDF (16 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Toyopuc OUT-15 and Toyopuc OUT-18

Page 115

6 Maintenance 6.1 Battery Replacement (1) Lithium rechargeable battery (TIP-5426) The PC3JG CPU uses exclusive lithium rechargeable battery. This battery is always kept full charged by about 4 hours' current feed per day. If kept full charged, this battery can back up (*1) for one year or more subject to normal temperature (25°C). If "BATTERY VOLTAGE LOW" is detected, BATTERY ALM (error code 0022) is output. (Special relays V03 and VF0 turn ON.) If BATTERY ALM fails to turn OFF even after charged 8 hours or more or it turns ON immediately after charged, possible cause is expiry of the battery life. In such a case, replace with new battery. The battery replacement cycle as a guideline is 5 years though depending on the actual operating conditions. In replacing, use specific battery ( Charge type battery for PC3J-CPU: TIP-5426) (*2). Replace the battery by a maintenance man having the relevant expertise knowledge. *1 This lithium rechargeable battery backs up data memory ( data area for keep-relay , data register, etc.) and the built-in clock. The guaranteed back-up period subject to full charge is 6 months (at 25°C). The back-up function is provided to restore the contents of the data memory (the data areas in keep relay, data register, etc.) if they are cancelled. For the details, see "3-1-2 Battery, (3) Data Memory Back-up". User program (sequence program + parameters) and equipment information memory data (comment, etc.) are never cancelled even against power failure because they are stored in a flash memory which can hold such data even during power failure. *2 Appearance of lithium rechargeable battery (TIP-5426)

Lead wire, black (-) (Front side: vacant)

Lead wire, red (+) Connector (CPU side)

3-pin connector

6-1

6

Page 116

(2) Battery replacing procedure 1,5) Lithium rechargeable battery (TIP-5426)

9) Battery replaced seal

2) Set screw

3) Battery fixing plate 4) Battery connector

87654321 x1 x10

3) Battery fixing plate

Battery replacing procedure 1)

Prepare battery (TIP-5426) for replacing.

2)

Remove set screw for battery fixing plate. Pay adequate attention not drop the screw within main unit during operation.

3)

Remove battery fixing plate.

4)

Remove battery connector.

5)

Remove battery connector from side. Do not force the battery to remove with force otherwise fault could occur. Push back buttery once when battery is caught in main unit and remove again paying attention so that battery would not be caught in main unit. Pay attention battery would not be caught in main unit.

Remove battery from side. 6)

Replace old battery with new battery. Mount battery in reverse procedure of removing.

7)

Mount battery connector.

Red

Black Blank

Front side

6-2

Page 117

8)

Turn on power source and check that battery alarm is turned out (Special relay: VF0 is turned off.) using peripheral equipment (PCwin).

9)

Turn off power source and enter battery replaced date.

Note: Be sure to complete battery replacing operation (Battery replacing procedure 2) ~ 8) ) within five minutes after power source is turned off. For a while after power source is turned off data memory (such data area for keep relay and data register, etc.) and built-in clock are backed up by large capacity capacitor. User program (sequence program and parameter) and equipment information memory content including comment are would not be erased even battery is removed because they are stored in flash memory that maintains content even service interruption.

6-3

Page 118

LITHIUM BATTERY HANDLING PRECAUTIONS WARNING For proper replacement of the lithium battery, follow the instructions given in the Individual Instruction Manual for the battery. Where it is in normal use with our equipment, the lithium battery is worry free while in use, but where it is stocked as a spare or it is disposed as scrap after expiry of its life the battery must be handled with good care. Improper handling of the lithium battery could result in liquid leak, overheat, ignition, and bursting, in the worst case, resulting in breakdown of device and bodily injury. To avoid such possible trouble and accident, observe the precautions given below. (1) Don't throw the battery in fire. (2) Protect it from water splash. (3) Don't apply direct soldering to the battery. (4) Don't heat it. (5) Don't overhaul . (6) Don't short plus (+) and minus (-). (7) Avoid pressurizing and deforming. (8) Avoid force-discharging. (9) Don't charge . (10) Don't use in series or parallel. (11) When storing a spare battery, don't select a place of high temperature and high humidity and take a proper measure to prevent condensation. When disposing the battery as scrap, dispose it properly as incombustibles with good attention to the following instructions as well as observing the precautions given above , or otherwise dispose it properly in accordance with the applicable ordinance by each local administrative body. 1) In disposing, don't mix batteries together. Contain them one by one in a vinyl bag to avoid shorting. 2) Use a collective container of good-insulation material to contain batteries therein. 3) Don't contain them together with other metallic materials ( nails, steel wires, etc.) . 4) Protect them from rain and water. 5) Don't contain them together with other hazardous materials which are defined under "Fire Law". Also don't place them near such hazardous materials. 6) Don't place them near fire and at a location where they are exposed to high temperature. This “Crossed-out wheeled bin” symbol is for EU countries only. This “Crossed-out wheeled bin” symbol means that batteries and accumulators, at their end-of-life, should be disposed of separately from your household waste. In the European Union there are separate collection systems for used batteries and accumulators. Please, dispose of batteries and accumulators correctly at your local community waste collection/recycling centre.

6-4

Page 119

6.2 fuse replacement Fuse is provided at common of output for device (Y010 ~ Y01F: 16 points). “ERR43 or 4B” is displayed on message display when fuse blown is detected. Check rack No. and slot No. from error detailed information. Rack No. or slot No. becomes rack No. 0 or slot No. 0 when built-in fuse is blown. Note: The unit would not run when blown fuse is detected if fuse is blown at the time power source is turned on or CPU is stop state. In such a case “43” is displayed. Running of CPU is continued when blown fuse is detected. At this time “4B” is displayed.

Remove the cause of blown fuse then replace blown fuse with spare fuse. Depending on cause (In case that such current that fuse cannot blow off instantaneously should flow) fuse could not protect output element from breakage. Rated capacity of fuse is 3.2A. Fuse type : LM-32 (Daito Communication Apparatus Co., LTD.)

Output fuse 3.2A for control unit

Spare fuse

6-5