Page 11
1.
SYSTEM COMPONENTS
1.1.
Features TOYOPUC-PC3JG is the integrated system having such function as CPU function, communication function and I/O. Outside dimension of the CPU is the same with two slots module PC3J/PC2J and the CPU is mounted at CPU slot and slot 0 on base for PC3J/PC2J. Function of CPU is the same with PC3J-CPU. Such abundant communication function as device net also installed and additionally 64 I/O is equipped as standard. (1) Execution of three independent programs PC is required to provide three functions of "equipment control", " equipment diagnosis " and " information processing". A clear and easy-to-see program becomes available by making these three sequence programs independent from each other. The PC3J able to make each program and its data area perfectly independent from others improves the efficiency in creation and edit of electric circuits. (2) Built-in equipment information memory The PC3J Series can store various equipment information such as comments on sequence circuit, device symbols, cycle chart, etc. Based on these equipment information, the PC3J Series can display, by peripheral equipment (PCwin), etc., information of commented circuit diagrams, cycle charts, equipment diagnosis result, etc. which are very useful for further maintenance of equipment. (3) Compatibility with PC2J Sequence programs created in PC2 Series can be executed as are with this PC3J series, whereby further continued use of the conventional assets is ensured. (Waste is eliminated.) (4) Further use of PC2 Series peripheral devices allowed. The PC3J series is provided with "PC2 Compatible Mode" allowing further use of the peripheral devices for PC2 Series. (Note) PC2 Series peripheral equipment can not be used in mode other than "PC2 Compatible Mode". PC3J Series can be used as "PC2 Compatible Mode" by writing applicable program by PC2 Series peripheral equipment. The function extended in PC3J Series is not available for “PC2 Compatible Mode”. (5) Flexible user memory Twelve (12) different user memories are selectively available by allocation flexibly corresponding to user needs. (6) Built-in communication port Total two ports are equipped as standard; one is port for CMP link (computer link) or PC link or SN-I/F, the other port for DLNK-M2. (7) 64-point of I/O 32-point for signal I/O (16/16) and 32-point for device I/O are equipped as standard. (8) High speed processing Processing speed of basic commands at 0.08 µs/word (min) and that of applied commands at 0.60 µs/word (min) faster than those in PC2 allow high speed processing of versatile sequence programs such as "equipment control", "equipment diagnosis", " information processing", etc.
1-1
1
Page 12
System connection (1) In case of connected to PC3J/PC2J PC3JG-CPU Module
Cable for peripheral device connection
Base
Power module
Selector module
Communication adapter
I/O cable
Windows95 installed Personal computer *1
Base *2
*1 : commercially available computer Programmer software PCwin ( Ver5.0 or later )
I/O cable
*2 : 8slot-base(z) or selector-base
Base *2
I/O cable
Input module
Base *2
Output module
I/O cable
Special module
Base *2
I/O cable
Base
I/O cable
Base
I/O cable
Base
I/O cable
Base
I/O branch module
1.2.
I/O cable
Base *2
I/O cable
Base *2 Note. Keep total I/O extension cable length less than 10 meters. Keep I/O total extension cable length less than 5m and installation of maximum base installation 4 sets when I/O branch module is used.
I/O cable
Base *2
1-2
Page 13
(2) Programmable software (Hellowin, PCwin) If the past programmable software are used, the some functions in PC3JG are not usable.
(Note 3)
Programmable software
PC3JG
CPU mode
DLNK (Note 1) I/O 1024 points or less
Separate1-5
Single1-6
PC3JG
PC2 compatible
I/O 1024 points or more
Tool Diagnosis function function (Note 2)
hellowin PCwin before Ver4.5 PCwin Ver4.6 PCwin Ver5.0 or later (Note 1)
In case of I/O 1024 points or less and no diagnosis function for DLNK, set DLNK-M in the link parameter and the past programmable software is usable.
(Note 2) For the details of the tool function, see [12. Tool] or the PCwin manual. (Note 3)
PC3JG has the automatic switch function and make it possible to communicate faster than it is set by 38.4kbps. It is possible for PC3JG to communicate when it is set by 38.4Kbps or AUTO. High-speed communication would be possible by setting PCwin by AUTO. PC2J/PC3J series other than PC3JG communicates by 38.4kbps.
1-3
Page 14
1.3
Table of System Components Equipment, device
Name PC3JG-P-CPU
PC3JG PC3JG-CPU
Type
Specification
TIC-6088 Memory 180K word (60×3) Input 32 points (5mA) output 32 points (0.3A:16 points),(0.05A: 16 points) TIC-6125 With computer link/PC link/ SN-I/F and DLNK-M2 function
Lithium battery
For PC3J CPU
TIP-5426 Rechargeable battery for PC3J CPU
Connector
Connector for external connection
TIP-5867
Selector Power unit
Base
Selector base
I/O cable
SELECTOR
THU-2765
POWER1
THV-2747 AC85~264V input,DC5V 4A output
POWER2
THV-2748 DC24V input,DC5V 4A output
8-slot base
THR-2766
8-slot base2
THR-2872 I/O connector 2 pieces
6-slot base
THR-2813
4-slot base
THR-2775
2-slot base
THR-2814
8 slot base 6 slot base 4 slot base
Output selector
Selector function internally stored dedicated base for 8 slots increasing selector Selector function internally stored dedicated base THR-5644 for 6 slots increasing Selector function internally stored dedicated base selector THR-5645 for 4 slots increasing THR-5643
I/O cable 0.5m
THY-2770
I/O cable 1m
THY-2771
I/O branch module
Input
For square shape connector soldering 40pin resin case
THU-2774
For additional base when other than 8-slot base 2 is used.
IN-11
THK-2749 16 points AC100V input
IN-12
THK-2750 16 points DC24V input
IN-22D
THK-2871 32 points DC24V input
OUT- 1
THK-2751 8 points triac output, 1A/point, 4A/8 points
OUT- 3
THK-2931 2A/point
OUT- 4
THK-5040 8 points triac output, 1A/point, 4A/8 points, AC100/240V
OUT-11
THK-2795 16 points triac output, 0.5A/point, 2A/8 points
OUT-12
THK-2752 16 points, relay contact output, 2A/point, 5A/8 points
OUT-15
THK-2790 16 points MOS-FET output (-) common , 1A/point, 4A/8 points
OUT-16
THK-2791 16 points MOS-FET output (+) common , 1A/point, 4A/8 points
OUT-18
THK-2753 16 points, transistor output (-) common, 0.5A/point, 2A/8points
OUT-19
THK-2754 16 points, transistor output (+) common, 0.5A/point, 2A/8points
8 points, relay independent contact output (AC240/DC24V)
1-4
Page 15
Name
Equipment, device
Type
Specification
OUT-28D
THK-2870 32 points transistor output (-) common , 0.2A/point, 2A/16 points
OUT-29D
THK-5025 points
Serial I/O
SIO
THK-2782 RS-232C 0.3~19.2Kbps 2ch
PC1 bus interface
PC1-I/O-I/F
THK-2783 For PC1 bus coupling
Output
32 points transistor output (+) common , 0.2A/point, 2A/16
High speed counter COUNTER
THK-2932 50kpps 1 and 2 phase
Pulse output
PULSE OUTPUT
THK-5109 245, 730pps forward pulse /reverse pulse
AD-1
THK-7936 1~5V,4~20mA,4 points
AD-2
THK-7937 1~10V,4 points
AD-3
THK-7938 -5~5V,4 points
DA-1
THK-7931 1~5V,4~20mA,2 points
DA-2
THK-7932 1~10V,2 points
AF1K-C
AF1K-C Control of Single-axis CNC Unit AF1K
MA1K-C
MA1K-C Control of Multi-axis Controller MA1K
PC/CMP link
C/CMP-LINK
2-port link
2 PORT-LINK
THU-2755 PC link (19.2/57.6 Kbps,16 ST, 512 points) or 1 port computer link (selection of 0.3~19.2Kbps 32 THU-2927 stations) 2 ports
PC/CMP link 2
PC/CMP-LINK2
THU-5139
2-port M-NET
2 PORT M-NET
THU-5093 M-NET SPEC.(8 stations, 256 points)
Analog input
Analog output
Motion controller
High speed PC link HPC-LINK
ME-NET
Options
ME-NET
2 ports
THU-2758 625Kbps, 32 stations, 2048 points, 1792 bytes THU-2797 1.25Mbps, 64 stations, 2048 points, 2048 bytes
ME -cable
TLY-2692 Cable set for coaxial cable lead-in
ME-BNCL
TLY-2693 BNC connector terminal end, L-shape for coaxial cable
ME-BNCP
TLY-2708 BNC connector for coaxial cable
High speed remote RMT-I/O M I/O, host High speed remote RMT-I/O S I/O, slave
FL-net Ethernet
4-wire communication available , subject to same specification as PC/CMP link.
THU-2756 HOST, 625Kbps, 2048 points, max. 31 stations THU-2757 Slave station
FL/ET-T-V2
THU-5998 FL-net, I/F (interface) for Ethernet
J-DLNK-M
THK-5398
J-DLNK-M-C
THU-6023 Master module conforming to DEVICENET
J-DLNK-M2
THU-6099
J-DLNK-S
THU-5441 Slave module conforming to DEVICENET
S-Link
S-LINK
THU-5291 I/F for SUNKS S-LINK
B7A-Interface
B7A-I/F
THU-5297 I/F for OMRON B7A 10 Input Points Type
Sub CPU
SUB-CPU
THC-5058 Memory 16K words, SIO function built in
Device net
For the details of special module and programmer, see the respective individual Instruction Manuals.
1-5
Page 16
Equipment, device I/O Monitor
Name PC3J/PC2J-I/O MOMITOR2*1
Type
Specification Monitor such as register
THA-5137 (I/O monitor cable : THY-2905 is required to connect with PC3JG.)
Programming software (CD-ROM version) for SFC : Japanese Programming software (CD-ROM version) for TJA-2031 SFC : English Software for Programming software (CD-ROM version) for PC3JG TJA-6285 SFC : French (forWindowsXp/2000) Programming software (CD-ROM version) for TJA-6233 SFC : Chinese Programming software (CD-ROM version) for TJA-6058 SFC : Czech TJA-2032
Programmer
PCwin
Peripheral equipment
I/O monitor cable THY-2905 Connection between I/O monitor and PC3G : 1.5m
Personal computer TXY-6071 Connection between TOYOPUC and PC (RS-232C) connection cable2 USB I/F cable
TXY-6266 Connection between TOYOPUC and PC (USB)
Refer to respective operation manual concerning peripheral equipment. *1 PC3JG division mode is not supported.
1-6
Page 17
1.4.
Name and function of each panel switch and each lamp
(1) PWR lamp
(4)Message display
(2) RUN lamp (5) MODE push button switch
(3) E/A lamp
(6) INC push button switch
(1) PWR lamp Indicates 5V power source is supplied on base unit. However the lamp is turned out when interruption of the power source is detected. (2) RUN lamp Indicates sequence program is under execution. Interlocked with RUN relay output for power supply module. (3) E/A lamp Lights when heavy or light abnormality and alarm are occurred. (4) Message display Displays state of CPU, ON/OFF display for I/O and error message. (5) MOD push button switch Display content on display is changed over. [RUN state]->[Error code]->[I/O]->[link communication state]->[Library information] (6) INC push button switch In case of [Error code] or [I/O], the next content is displayed.
1-7
Page 18
(9) Fuse for control output (10) Spare fuse (7)Connectorfor peripheral equipment
(11) Input/output for control (12) Input/output for signal
(8) Reset/start switch
(7) Connector for peripheral equipment Connects peripheral equipment. *The size of the screw of the connector is M3 . (8) Reset/start switch CPU becomes set state when switch is turned to “RESET” side and outer output and inner relay are made OFF to stop program running. When the switch is turned to “START” side program execution is started. However the program is not started if stop signal is issued from peripheral equipment. (9) Fuse for control output Fuse for (Y010 ~ Y01F). Capacity of fuse is 3.2A. (10) Spare fuse Spare fuse provided for control output. (11) Input/output for control Input is 16 points (5mA) and output is 16 points (0.3 A/point : 2A/16 points). Output for control is provided to drive relay and solenoid valve. (12) Input/output for signal Input is 16 points (5mA) and output is 16 points (0.05 A/point : 0.8A/16 points). Output for signal is provided to deliver signal to other device or LED lamp display. Do not connect such inductive load as relay or solenoid valve to output for signal.
1-8
Page 19
(14) DLNK setting switch (16) DLNK communication terminal block
(13) DLNK state display lamp
(13) DLNK state display lamp Displays state of DLNK. MS: Running state of the hardware in DLNK communicating part is displayed. Green on: Normal state. Green blinking: Loading state of switch. Red on: Hard error. Red blinking: switch setting error. NS: Running state of DLNK network is displayed. Green on: Normal state. Green blinking: On establishing the communication. Red on: Communicating on network is not possible. Red blinking: Communicating error in the slave. DE: Running state of the hardware in DLNK-CPU. Off: Normal state. Red on: Hardware error. Red blinking: Communicating error in the slave. (14) DLNK setting switch Sync: Switch of the synchronization of the communication scanning and the sequence scanning and the non-synchronization. OFF- non-synchronization, ON- synchronization Stop: Switch of stopping CPU on the communication error and running CPU. OFF-running, ON-stop Hold: Switch of that output are OFF on stopping CPU and are held. OFF-OFF, ON-hold (15) DLNK communication terminal block This is terminal block for DLNK.
1-9
Page 20
Product version seal (18) Battery replacing seal
(16) CPU version seal (17) G-S, PC-Link, Computer-Link state lamp
(20) Setting switch of the
(19) G-S, PC-Link, Computer-Link terminal block terminator for SN-I/F
(16) CPU version seal Indicates version of CPU. The version is stored at special register S2D1. (17) SN-I/F, PC-Link, Computer-Link state lamp The state of some one of SN-I/F, PC-Link or Computer-Link is displayed. Orange blinking: Communicating OFF: Stop communication (18) Battery replacing seal The seal is provided to enter the date the battery is replaced. (19) SN-I/F, PC-Link, Computer-Link terminal block This is terminal block for SN-I/F, PC-Link or Computer-Link. (20) Setting switch of the terminator for SN-I/F OFF: No connecting terminator, ON: Connecting terminator
1-10