Programmable Controller TOYOPUC PC3JG-P-CPU TIC-6088 / PC3JG-CPU TIC-6125 Operation Manual: 2. Installation and wiring

Pages 21 to 33 of 387, from Programmable Controller TOYOPUC PC3JG-P-CPU TIC-6088 / PC3JG-CPU TIC-6125 Operation Manual

The original document is the PDF (16 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Toyopuc OUT-15 and Toyopuc OUT-18

Page 21

2

Installation and wiring This Section describes the installing and wiring procedures and related cautions.

2.1

Environment for installation Avoid to install the PC at the following environments. (1)Place where ambient temperature exceeds the range of 0 to 55°C. (2)Place where ambient humidity exceeds the range of 30 to 85% RH. (3) Place where rapid temperature fluctuation results in dew condensation. (4)Place where corrosive gas and combustible gas exist inevitably. (5) Place where conductive powders such as dust, iron powder, etc., oil mist, salt content, and organic solvent exist much. (6)Place where strong electric field and strong magnetic field generate.

(7)Place where the product is exposed to direct sun ray. (8)Place where vibration and impact are transferred to the product (PC). When use environment is the above, please contain this equipment to the control box sealed in order to maintain good installation environment. Please do not keep the door of a control box opened wide. Moreover, when you use a fan etc. within a control box, please install so that a direct wind is not in charge of this equipment. Please be careful in order to cause an unexpected situation, when a coarse particulate adheres to the portion equivalent to which a wind is directly so much.

2-1

2

Page 22

2.2

Cautions in installing (1) For smooth drafting or easy module replacement, keep a space of at least 50mm between upper module/lower module and other structures and parts, as illustrated below.

(2) Absolutely avoid to use modules in vertical position and horizontal position. positions causes poor drafting in modules.

2-2

The use in such

Page 23

2.3

Actual mounting of each module (1) How to mount onto the base 1. Insert module's fixing claw in the lock (receptacle) hole of the base.

2. For mounting, push-in the module in arrow direction until it clicks. Check the claw and hook for exact insertion in the hole. Failure to fix exactly the module could cause operation error. Caution it ! Particularly when this PC is used at an environment where it is exposed to significant vibration and shock, it is recommended to screw each module to the base. (Screw size: M3 × 8, with washer)

These screws are not included in each module.

Prepare them at user side.

(2) How to remove module 1. Push down the upper hook of each module until it comes to end. 2. Draw the module frontward to remove it from the base, with its bottom supported, while pushing down its hook.

2-3

Page 24

2.4

Wiring

2.4.1 Cautions in wiring This paragraph describes the cautions to be observed in wiring of power cable or I/O cable, etc. (1) In wiring, separate the power line to the PC body (power module) from the power line to I/O devices and main circuit devices respectively.

Main power source I/O PC Power source Power source

PC body

Additional rack

I/O devices

(POWER1)

Main circuit Power source

Main circuit devices

(2)Select and use low-noise power cables between cables and between cable and ground. When these lines are very noisy, connect an insulated transformer to these lines.

I/O devices

PC body Insulated transformer

(3) Isolate the I/O signal line from main circuit line of high voltage and large current as far as possible. (keep a space of 100mm min between these two.) Avoid parallel wiring of these if possible.

2-4

Page 25

(4) Isolate DC24V I/O cable from AC100V cable. (5) The recommended cable for I/O signal is as follows. Recommended The permissible current capacity of cable Terminal block cable size differs depending on ambient 2 temperature, insulator thickness, etc. 19P 0. 5mm (6) Use of the following crimp terminals is recommended. Manufacturer Type JAPAN Eyelet terminal 0.5 - 3.7, 1.25 - M3, 2 - S3 SOLDERLESS Rectangular TERMINAL end-open 1.25 - YS3A, 2 - YS3A TRADING terminal COMPANY LTD. Vinyl-insulated V0.5 -3.7, V1.25 - M3, V2 - S3 eyelet terminal Vinyl-insulated rectangular V1.25 - YS3A, V2 - YS3A end-open terminal (7) Wire the I/O signal cables using another duct separately from main circuit cable, whether inside or outside the control panel. When using the duct wiring system, earth the duct securely. (8) When wiring by use of same duct is inevitable, use a batch-shielded cable and connect its shield end to FG terminal of NC rack. (9) Output short-circuit protection The output module self-contains a fuse to protect itself from burning should a load be short-circuited. But this fuse can not protect the output module from overload. Therefore, use the output module within the ratings without fail. (10) Parallel connection of loads The number of loads which can be driven in parallel by the output module is determined by the starting current and rated current of loads actuated simultaneously. Therefore, connect the loads so that the starting current does not exceed the fuse rating and, in addition, the rated current does not exceed the rated output current (per point) of the output module. Table below shows the reference number of loads for which parallel drive by OUT-1 is available. Manufacturer

Type SRCa3631-0 FUJI SRC3631-5-2 ELECTRIC SRCa3631-2 CO., LTD. SC-4 Note: Use auxiliary relay for a load which exceeds the ratings. (11)Do not string a strong cable in 50mm zone from CPU module front. (12)FG connection FG terminal is provided on 5V terminal block of each base. When additional base is installed, connect FG to one FG terminal.

2-5

Quantity 4 3 2 1

Page 26

2.4.2

Wiring of power module

0.75 or 1.25 sq twist

AC1 or DC+

IN

AC85-264V(POWER1) or DC18-32v(POWER2)

AC2 or DC-

0.75 or 1.25 sq twist RUN1

To sequence control circuit RUN2

* For wiring to the terminal block, use crimp terminal (Eyelet or Y-shaped terminal for M3) without fail. Ex. Proper connection AC100V(POWER1) AC100V(POWER1)

DC24V (POWER2)

DC24V (POWER2)

CPU rack

CPU rack

Additional I/O rack

I/O cable

Additional I/O rack

I/O cable

5V , 0V wiring

Ex. Improper connection

AC100V(POWER1)

DC24V (POWER2)

CPU rack

AC100V(POWER1)

AC100V(POWER1) DC24V (POWER2)

DC24V (POWER2)

CPU rack

Additional I/O rack

I/O cable

Additional I/O rack

I/O cable

Avoid to wire another power cable separately from additional I/O rack.

2-6

Avoid to supply the power into the power module of CPU rack, with I/O cable wired between additional racks, without supplying the power into the power module of additional rack. When connecting I/O cable of additional rack, exactly wire the power cable to the power cable to the power module.

Page 27

2.4.3

Wiring for 5V power supply into additional I/O rack Where more than 8 additional I/O modules, etc. in total are used, it is possible to operate PC by supplying 5V power into additional I/O racks from other power module, provided that the total current consumption of all modules in additional I/O rack is not more than 4A. In supplying 5V power, wire each cable of 5V, 0V and FG from the left end terminal on each base. Furthermore, note the following in wiring.

(1)Be careful to avoid miss wiring of 5V, 0V and FG. (2)Use 5V cable and 0V cable as twisted. Isolate 5V cable from main circuit line of high voltage and large current as far as possible. (Keep a space of 100mm min between these two.) Avoid parallel wiring of these if possible. (3) Absolutely avoid 5V cable wiring of rack to rack to which power module is connected. Doing so could result in damage of modules due to parallel run of the power modules. (4)Recommended cable size and recommended crimp terminals for each wiring. Recommended cable size

Recommended crimp terminals

JAPAN SOLDER-LESS TERMINAL

TRADING COMPANY LTD.

5.5mm2 Eyelet terminals Rectangular end-open terminal

2-7

5.5-S3, V5.5-S3 (vinyl-insulated)

5.5-S3A,V5.5-S3A (vinyl-insulated)

Page 28

2.4.4

Connection method

(1) Wiring of SN-I/F, PC link and computer link (SN-I/F)Connect wires to each terminal + , - and 0V as shown below: Function

Terminal name Content L1+ Communication + SN-I/F L1Communication0V Communication 0V (shield inner shell) When you use as SN-I/F, please do not connect outside line to PC3JG and TOYOPUC-PCS.

(PC/CMP)Connect wires to each terminal + , - , 0V and FGas shown below: Function Computer link PC link

Terminal name L1+ L10V FG

Content Communication + CommunicationCommunication 0V (shield inner shell) connect to a base

FG

Method of wiring the terminal block. After crimping with a special stick terminal, the stick terminal is automatically fixed by inserting the stick terminal in the electric wire insertion hole. When the stick terminal is pulled out, After pushing a release button (orange) on the electric wire insertion hole side, the electric wire is pulled out. Recommended terminal : AI0.75-10GY made by phoenix contact (0.75sq for 1 wire) : AI-TWIN2X0.75-10GY made by phoenix contact (0.75sq for 2 wires)

Recommended crimping tool : CRIMPFOX ZA3 or CRIMPFOX UD63 made by phoenix contact. Note 1) cover the bar terminal with a mark tube for preventing a short circuit.

Recommended cable · Double shield O-VCTF-SS 2C×0.75mm2 CHUGOKU ELECTRIC WIRE & CABLE CO., LTD · Double shield UL2464-DSS 2C×20AWG CHUGOKU ELECTRIC WIRE & CABLE CO., LTD · Double shield UL2464-2SB 2×20AWG KURAMO ELECTRIC CO.,LTD. Note 1) Be sure to connect each cable with the power source cut off. Note 2) Cable shall be sequentially wired one by one from module to module. Do not wire them in batch. Note 3) To avoid operation error caused by external noise, do not make proximity wiring of communication cables in parallel to main circuit cable, etc. of high tension and strong current.

2-8

Page 29

SN-IF wiring diagram

PC3JG

TOYOPUC -PCS

+ -

+ -

0V

0V Maximum 3m

PC link wiring diagram PC link Key station

PC link

Branch station 1

+ 0V

+ 0V

FG

FG

PC link Branch

PC link Branch

··· station 2 station n

+ 0V

+ 0V

FG

FG

Maximum 1 km Computer link wiring diagram (In case high rank computer requests RS-422 half-duplex responding) High rank Computer

Computer link No. 0 station

Computer link No. 1 station

Computer link No. n station

···

+ 0V

+ 0V

+ 0V

+ 0V

FG

FG

FG

FG

Maximum 1 km

(In case high rank computer requests RS-232C responding) Be sure to use RS-232C/422 converter (Model TXU-2051) when computer is connected to high rank computer that responds to RS-232C. High rank Computer

RS-232C

Computer link No. 0 station RS-232C/422 Converter TXU-2051

Computer link No. 1 station

···

Computer link No. n station

+ 0V

+ 0V

+ 0V

FG

FG

FG

Maximum 1 km

2-9

Page 30

(2) Wiring of DLNK-M2 DLNK communication cable is composed of five wires: 1) communication power source wires (24V,0V), 2) communication data wires (CAN-H,CANL) and 3) shield wire (DRAIN). The five wires can be identified by respective color and are complied with device net specifications. (a) Wiring to DLNK-M2 Communication cable shall be connected as shown below: Each wire of five DLNK-M2 wires is sealed to identify the content of respective purpose. Confirm that wire color and seal color is coincidence with each other. Seal

Communication Terminal block

Red Function

White DLNK-M2

Blue

Black

Terminal name V+ CAN-H DRAIN CAN-L V-

Content Communication power source + (red) Communication data high (white) Shield (bare wire) Communication data LOW (blue) Communication power source – (black)

Bare wire

! Wiring to communication connector The communication connector of DLNK-M2 is screw less terminal. The ferrule is crimped to the portion that turned to covering of the cable end, and it is clamped only by inserting the ferrule in the wire insertion port of the connector. When removing a cable, a cable is removed where the upper of an orange lever is pushed with a small minus driver. The recommended ferrule and crimping tool Item

Type Manufacturer Kind of cable Communication line Power supply line Shield line Thin Cable AI 0,25-8 YE AI 0,5-10 WH AI 0,5-10 WH Phoenix Contact Ferrule Thick Cable A 1-10 AI 2,5-10 BU A1-10 or AI 1-10 RD Inc. AI:Ferrule with plastic sleeve , A:Ferrule without plastic insulating sleeve crimping tool CRIMPFOX ZA3, CRIMPFOX UD6-4 Note 1: The recommended ferrule mentioned above is a suitable ferrule for recommended communications cable (refer to (c)). Please use a suitable ferrule for the size of the conductor and the size of the insulator of each electric wire when you use a communication cable other than recommended one. Note 2: Up to 1 ferrule can be inserted into a single insertion port. When connecting two wires, Twin-Ferrule is used. Note 3: Please mounts the terminating resistor in the branch unit.

2-10

Page 31

(b)Wiring to branch unit The following branch units are recommended. Please refer to each maker's manual for use. Please consider that if there is something specified for the end user. Type DCN1-1C DCN1-3C

Manufacturer OMRON OMRON

(c)Type of recommended communication cable Be sure to use communication cable that is complied with device net specifications. We recommend using following products as communication cable. Use these products depending on your requirement. ■Recommended communications cable Kind of cable Thin Cable Thick Cable Manufacturer OMRON CORPORATION. DCA1-5C10 DCA2-5C10 SHOWA ELECTRIC WIRE & CABLE CO.,LTD. TDN24U TDN18U KURAMO ELECTRIC CO.,LTD. KND-SB(THIN) KND-SB(THICK) Note: The cable mentioned above is for fixed part. Please inquire of each maker about the cable for the moving part. (d)Terminator Be sure to install terminators at both ends of main line to stabilize communication line. Use 121Ω 1/4W metal film resistor as terminator.

2-11

Page 32

(e) Connection of Communication Power Source Supply 24 V DC to the network power supply lines (V+, V-). The network power supply is applied by using one of the terminal blocks inside the relay box or Tbranch. Connect the network power supply so that 24 V (+) and 24 V (-) are supplied to the communication cable red and black lines respectively.

Black To node Communication cable

Network Power Supply (24 V DC)

Red Black

To node

Relay box · T branch

Red

* The wiring diagram for other than the power line is omitted.

(f) Communication Cable Grounding Connect the communication cable shielding wire (DRAIN) to the earth (ground). Provide grounding only in one place of the network so that no ground loop is produced. Provide this grounding as near the network center as possible, and do this with the relay box or Tbranch. As shown below, connect the communication cable shielding wire with the earth terminal of network power supply <FG> for Class-D grounding (Class-3 grounding).

To node Communication cable To node

Network Power Supply (24 V DC)

Shielding wire Relay box · T branch * The wiring diagram for other than the shielding wire is omitted.

2-12

FG

Page 33

(g) Order of wiring and relation of station number i. There is no need to wire the master and slaves in order. (Refer to the figure below.) End terminal station

Master

Slave1

Slave2

Slave3

End terminal station

End terminal station

Slave1

Master

Slave3

Slave2

End terminal station ii. Wire the communication cable from module to module. In the case of wiring in multi-drop method, be sure to use relay box or T branch. Master

Slave2

Slave3

Slave2

Master

Slave3

Slave1

O Good

× Bad Slave1

Slave1

Master

Slave2

Master

Slave3

Relay box or T branch O Good

Slave2

Slave1

Slave3

(h) Parallel approach with the power line Avoid parallel adjacent wiring of the communication cable with high voltage power cable such as power line or so. Arrange the communication line by separate duct from power circuit cable both in and outside of the control panel. In the case of pipe wiring, ground pipe in a secure manner.

2-13